English

4

2. Setting the address of wireless remote controller (It is factory set to “ 1 ” )

Setting from the remote controller

1.

Hold down the 

 

button and the 

 

button for at 

least 4 seconds to get the Field Set mode.
(Indicated in the display area in the figure at right.)

2.

Press the 

 

button and select a multiple setting (A/

b). Each time the button is pressed the display switches 
between “A” and “b”.

3.

Press the “

” 

button and “

” 

button to set the 

address.

Address can be set from 1 to 6, but set it to 1 ~ 3 and to 
same address as the receiver. (The receiver does not work 
with address 4 ~ 6.)

4.

Press the 

 button to enter the setting.

5.

Hold down the 

 button for at least 1 second to quit 

the Field Set mode and return to the normal display.

Multiple settings A/b

When the indoor unit is being operating by outside control (central remote controller, etc.), it sometimes does 
not respond to ON/OFF and temperature setting commands from this remote controller.  Check what setting 
the customer wants and make the multiple setting as shown below.

3.

Stick the Unit No. label on the air outlet of the 

decoration panel and the back of the wireless 
remote controller.

[PRECAUTIONS]

Set the Unit No. of the receiver and the wireless 
remote controller to be equal. If the settings differ, 
the signal from the remote controller cannot be 
transmitted.

Remote controller

Movement when the operation is controlled by the 
other air conditioners and equipment

Multiple setting

Remote controller display

A: Standard

All items displayed.

When operation changeover, temperature setting or 
the like is carried out from the remote controller, the 
indoor unit rejects the instruction.
(Signal receiving sound “peeh” or “pick-pick-pick”)
As a result, a discrepancy between the operation 
state of the indoor unit and the indication of the 
remote controller display occurs.

b: Multi System

Operations remain dis-
played shortly after exe-
cution.

Since the indication of the remote controller is turned 
off, no discrepancy such as mentioned above occurs.

MODE

TIMER

RESERVE CANCEL

DOWN

UP

/TEST

SWING

FAN

TIME

TEMP

ON

OFF

SETTING

Mode

3

2

4

1

Address

Multiple setting

5

/TEST

FAN

UP

DOWN

1

2

3

4

5

6

RESERVE

/TEST

Unit No. label

Wireless remote controller

Decoration
panel

Содержание BRC7E530W

Страница 1: ...e injury or damage to equipment NOTE These instructions will ensure proper use of the equipment CAUTION Refer also to the installation manual attached to the indoor unit and the installation manual at...

Страница 2: ...e direction of the receiver The direct transmitting distance of the remote controller is approximately 7 meters The signal cannot be transmitted if something such as curtains blocks the receiver and t...

Страница 3: ...he indoor unit Be sure to turn off power before removing the control box lid 2 Determination of address and MAIN SUB remote controller If setting multiple wireless remote control lers to operate in on...

Страница 4: ...shown below 3 Stick the Unit No label on the air outlet of the decoration panel and the back of the wireless remote controller PRECAUTIONS Set the Unit No of the receiver and the wireless remote cont...

Страница 5: ...f the panel temporary suspension of the decoration panel Be sure to push the harness to the groove 3 Attach the decoration panel to the indoor unit Refer to the installation manual attached to the dec...

Страница 6: ...e FIELD SET MODE is entered 2 Select the desired MODE NO with the button 3 Push the button and select the FIRST CODE NO 4 Push the button and select the SECOND CODE NO 5 Push the button and the presen...

Страница 7: ...03 10 0 Filter Contamination Heavy Light Setting for spacing time of dis play time to clean air filter Setting for when filter contamination is heavy and spacing time of display time to clean air fil...

Страница 8: ...unit if it does not operate 2 Refer to the installation manual attached to the outdoor unit for individual operation system types Order Operation 1 Open gas side stop valve 2 Open liquid side stop val...

Отзывы: