16
Characteristics of Dry Operation
Dry mode repeats the weak cooling operation intermittently to dehumidify the room without dropping
the room temperature as much as possible for the prevention of
excessive cooling.
Setback
periods.
Note
•
This function will temporarily start an air conditioner that was previously turned off by the user or
turned off from a schedule setting/off timer.
•
This function is disabled by default. This function can be changed enable/disable by Main Menu.
(Refer to page 34)
For example:
Setback temperature: cool 35°C, Heat 10°C
Recovery Differential: cool -2°C, Heat +2°C
•
If the room temperature drops below 10°C, the air conditioner starts operating in Heating
automatically. As soon as it reaches 12°C, the air conditioner returns to its original status.
•
If the room temperature goes above 35°C, the air conditioner starts operating in Cooling
automatically. As soon as it reaches 33°C, the air conditioner returns to its original status.
The differential can be adjusted in the Setback condition menu (Refer to page 36).
The setback temperature can be set on Basic screen during the air conditioner is turned off. Or
the setback temperature can be set in the schedule (Refer to page 46).
Operation
The setback cannot be enabled when a centralized control equipment is connected.
1
Cool
Setback
Cool
35
°C
The Setback icon “
” blinks when the air
conditioner is turned on under the Setback control.