BRC1E52B7
Installation manual
4PW72364-1 – 11.2011
12
5. Power-on
● Check for completion of indoor/outdoor units wiring.
● Check for closing of switch box cover of indoor and outdoor units before power-on.
5-1
Followings are displayed after
power-on.
"Checking the connection
Please stand by"
During above display, backlight
does not light by button operation.
When 1 indoor unit is
controlled by 2 remote
controllers:
Be sure to set sub remote
controller during above display.
Press and hold 4 seconds or
longer the Operation mode
selector button of the remote
controller to be set.
When the display is changed from
main remote controller to sub
remote controller, the setting is
completed.
5-2
Basic screen is displayed.
If sub remote controller is not set at power-on in the case
of one indoor unit controlled by two remote controllers,
"Error code: U5" is displayed in the connection checking
screen.
Select the sub remote controller by pressing the
Operation mode selector button of either one of the
remote controllers for 4 seconds or longer.
If the basic screen is not displayed more than 2 minutes
after "sub remote controller" display, shut off the power
supply and check the wiring.
CAUTION
When selecting a different language, refer to
12
.
Language
. (See page 23.)
NOTE
<Main remote controller>
<Sub remote controller>
5-1
Checking the connection.
Please stand by.
Off reminder Timer
Main RC
Checking the connection.
Please stand by.
Error Code U5
Main RC
5-1
Checking the connection.
Please stand by.
Off reminder Timer
Main RC
Checking the connection.
Please stand by.
Error Code U5
Main RC
Press and hold 4 seconds
or longer the Operation
mode selector button of sub
remote controller side.
Checking the connection.
Please stand by.
Off reminder Timer
Sub RC
<Basic screen>
5-2
Fan
<Basic screen>
5-2
Fan