Daikin BRC1E52A7 Скачать руководство пользователя страница 20

Installation manual BRC1E52A7

19

 

4PW71264-1 – 10.2011

Remote controller display

Description

No display

 

● Power outage, power voltage error or open-phase 

 

Wrong wiring (between indoor and outdoor units)

 

● Indoor PC-board assembly failure

 

Remote controller wiring disconnection

 

Remote controller failure

 

Fuse blown (outdoor unit)

Display of "Checking the connection

 

Please stand by" is turned on. 

*

 

● Indoor PC-board assembly failure

 

Wrong wiring (between indoor and outdoor units)

 

*

Though "Checking the connection

 

Please stand by" is displayed for 90 seconds at maximum after power-on, this does not mean a failure. 

(Determine after 90 seconds.)

8. Checking procedure of Error History

8-1 

Press and hold Cancel button for 

4 seconds or longer in the basic 

screen. Service Settings menu is 

displayed. 

8-2 

Select 

 Error History 

 in the Service 

Settings menu, and press Menu/Enter 

button. The Error History menu screen 

is displayed. 

8-3 

Select 

 RC Error History 

 in the Error 

History menu, and press Menu/Enter 

button. 

 Error codes and unit No. can be 

confirmed in the error record display 

screen.

8-4 

In the Error History, 10 items from the 

latest are displayed in order. 

8-5 

Press Cancel button in the Error 

History display screen 3 times. 

 

The basic screen returns.

8-1

<Basic screen>

<Service Settings menu screen>

8-2

Return

Setting

Service Settings

Indoor unit AirNet Address

Outdoor unit AirNet Address

Error History

Indoor Unit Status

Outdoor Unit Status

Forced Fan ON

1/3

Press Menu/Enter button.

8-3

Return

Setting

Error History

RC Error History

Indoor unit Error History

2/2

Press Menu/Enter button.

8-4

8-5

Return

RC Error History

  Unit Error 

Date 

Time

 01 ––  ––          ––

/

––

/

––  ––:––

 02 ––  ––          ––

/

––

/

––  ––:––

 03 ––  ––          ––

/

––

/

––  ––:––

 04 ––  ––          ––

/

––

/

––  ––:––

1/3

Unit No.

Latest record

Содержание BRC1E52A7

Страница 1: ...Be sure to read this installation manual before conducting the installation of this product BRC1E52A7 WIRED REMOTE CONTROLLER INSTALLATION MANUAL...

Страница 2: ...ions and menu items of remote controller buttons 10 5 Power on 12 6 Field settings 13 7 Test operation method in the case of SkyAir 16 8 Checking procedure of Error History 19 9 Registration method of...

Страница 3: ...regarding relocation and reinstallation of the remote controller Improper installation work may result in leakage electric shocks or fire hazards Install the remote controller in accordance with the i...

Страница 4: ...Corroding of copper pipes or soldered parts may result in refrigerant leakage 3 Near machinery emitting electromagnetic radiation Electromagnetic radiation may disturb the operation of the control sys...

Страница 5: ...hole to the center of the wiring through hole on the controller lower case when making the hole 8 10 External view of the remote controller Through hole 8 10 Lower case Through hole 48 5 40 3 3 Remove...

Страница 6: ...e burr with a file or the like 3 4 3 Upper outlet 3 4 4 Upper center outlet Cut off thin area hatched area with nippers or the like and then remove burr with a file or the like Cut off thin area hatch...

Страница 7: ...of two wires Sheath stripping length 150 mm for upper outlet 200 mm for upper center outlet Connect the terminals P P1 N P2 of the remote controller upper case with the terminals P1 P2 of the indoor u...

Страница 8: ...t P1P2 3 5 3 Upper outlet Install attached wiring retainer to prevent wiring pinch according to left figure PC board Indoor unit Wiring retainer Wiring retainer Upper case Lower case Upper case Wiring...

Страница 9: ...lower case In the case of wiring center upward drawing or rearward drawing see wiring procedure first as wiring with the case is needed before fixing 3 6 1 In the case of installation on the wall Sec...

Страница 10: ...ect flat place for installation face as possible And do not tighten the installation screws too much not to deform the lower case CAUTION 3 7 Install the upper case as original condition Align the upp...

Страница 11: ...anguage Depending on connected model 4 Up button Used to raise the set temperature The next items on the upper side will be highlighted The highlighted items will be scrolled continuously when the but...

Страница 12: ...or unit AirNet Address Outdoor unit AirNet Address Error History Indoor Unit Status Outdoor Unit Status Forced Fan ON Switch Main Sub Controller Filter Indicator Test Filter Auto Clean Brush Filter In...

Страница 13: ...controlled by two remote controllers Error code U5 is displayed in the connection checking screen Select the sub remote controller by pressing the Operation mode selector button of either one of the r...

Страница 14: ...SECOND CODE NO of the FIRST CODE NO to be changed and select desired SECOND CODE NO by using Up Down button Multiple identical mode number settings are available In the case of group setting all of S...

Страница 15: ...COND CODE NO Note 2 01 02 03 04 10 20 0 Filter Contamination Heavy Light Setting for spacing time of display time to clean air filter Setting for when filter contamination is heavy and spacing time of...

Страница 16: ...c pressure setting according to the connected duct resistance for FHYK follow the high ceiling setting Normal High static pressure Low static pressure Normal High ceiling 15 25 3 Drain pump operation...

Страница 17: ...k After air purge by vacuum pump refrigerant pressure may not rise even though the stop valve is opened The reason is that refriger ant system of the outdoor unit is blocked by electrical expansion va...

Страница 18: ...test operation finishes If interior work is not completed after the test operation finish explain to the customer that operation should not be performed until the interior work comple tion to protect...

Страница 19: ...the indoor unit After the failure diagnosis finishes press and hold On Off button for 4 seconds or longer in the Mainte nance Information screen to erase the error code record Failure diagnosis metho...

Страница 20: ...ic screen Service Settings menu is displayed 8 2 Select Error History in the Service Settings menu and press Menu Enter button The Error History menu screen is displayed 8 3 Select RC Error History in...

Страница 21: ...ter button Setting confirmation screen is displayed 9 6 Select Yes and press Menu Enter button Setting details are determined and Service Settings menu screen returns 9 7 Press Cancel button once The...

Страница 22: ...Enter button 10 2 Press Cancel button twice The basic screen returns Basic screen 10 1 Cool Set to Cool 28 C Press Menu Enter button Main menu screen Return Setting Main menu Quick Start Ventilation E...

Страница 23: ...ric changes continuously Day of the week is set automatically 11 4 Press Menu Enter button Setting confirmation screen is displayed 11 5 Select Yes and press Menu Enter button Setting details are conf...

Страница 24: ...Up Down buttons to select Language on the Language screen English Deutsch Fran ais Espa ol Italiano E Nederlands Portugues Pycc rk e Polski Pressing Menu Enter button Setting details are confirmed an...

Страница 25: ...unit Make sure that this controller is set to main factory set first change the restrictions to the setting you prefer and only then set the remote controller to sub 13 7 To lock menu button in basic...

Страница 26: ...s sub start with only connecting this controller to the unit Make sure that this controller is set to main factory set first change the restrictions to the setting you prefer and only then set the rem...

Страница 27: ......

Страница 28: ...Copyright 2011 Daikin 4PW71264 1 10 2011...

Отзывы: