Set Heat Pump Unit Systems Options

The items in the system menu control application specific functions 
for heat pump units. Entering the system options requires entering 

Password 2.

Table 12: Set Heat Pump Unit Systems Options

Procedure

Steps

Display

Starting display

1.  Start at the temperature display.

2.  Enter Password 2. The display changes to the MAIN menu display.

 

   

Choose and set the heat pump system options

1.  From the MAIN menu, press either the 

 or 

 button to 

 

select SYSTEM.

2.  Press Enter. The SYSTEM menu opens.
3.  Choose any of the following items.

• 

LOCAL OVRD TIME

• 

FAN DELAY OFF

• 

OCCUPIED FAN

• 

 MIN OFF TIME

• 

STAGE DELAY

• 

ECON ENABLE

• 

MIN ECON DAMPER

• 

ECON ENABLE TEM

• 

MIN DAT (optional)

• 

REV VLV PLRTY

• 

AUX HEAT (optional)

• 

AUX HT LOCKOUT (optional)

• 

COMP LOCK TEMP

   

   

Set the local override time

From the SYSTEM menu choose LOCAL OVRD TIME to set the time 

 

the BACnet™ Thermostat will hold an override temperature setpoint

 

as the active setpoint. At the end of the period, the 

BACnet

 

Thermostat will use either an occupied or unoccupied setpoint as  

the active setpoint.

Set the fan delay

From the SYSTEM menu choose FAN DELAY OFF to set the time the 

system fan will continue to run after the last heating or cooling stage 

is turned OFF.

Set the occupied fan control

From the SYSTEM menu choose OCCUPIED FAN to choose the 

following:

• 

When ON, the fan will run continuously when the 

BACnet

 

Thermostat schedule is ON (occupied).

• When the 

BACnet

 Thermostat schedule is OFF (Unoccupied) the 

fan will run only when there is a call for heating or cooling.

Set up staged cooling and heating

To set up staged cooling and heating do the following:
1.  From the SYSTEM menu choose MIN OFF TIME to enter the time a 

stage must remain turned off before it can be turned on again.

2.  From the SYSTEM menu choose STAGE DELAY to enter the time the 

first stage must remain turned on before the second stage can be 

turned on.

   

Program Set-Up

Содержание BACnet Series

Страница 1: ...ce procedures If you service this unit you assume responsibility for any injury or property damage which may result In addition in jurisdictions that require one or more licenses to service the equipm...

Страница 2: ...mmissioning Functions 13 Set Up Communications 15 Set the Time and Date 16 Setting the Occupancy Schedule 17 Set Rooftop Unit System Options 18 Set Heat Pump Unit Systems Options 20 Advanced Options 2...

Страница 3: ...MAC address baud rate user adjustments and application con figuration values are set from password protected front panel controls All models feature an integrated BACnet schedule and hardware real ti...

Страница 4: ...l relay outputs is 3 amperes 72VA Connectors Screw terminal block mounted to backplate Wire size 14 22 AWG Communications BACnet MS TP Integral peer to peer BACnet MS TP network communications Network...

Страница 5: ...e power limited circuits Weight Approx 6 ounces 170 grams Case Material Flame retardant plastic Dimensions Figure 1 BACnet Thermostat Dimensions Table 1 BACnet Thermostat Dimensions A B C 3 50 in 89 m...

Страница 6: ...l plate kit Routing the connecting cable or cables from the BACnet Thermostat to the equipment it is controlling Block leaks and airflow from conduits with plumber s putty or similar material If repla...

Страница 7: ...or Discharge Air Temperature Connect a 10k Type II thermistor temperature probe to the discharge air temperature DAT input The input includes the internal pull up resistor Follow the instructions supp...

Страница 8: ...outputs may represent analog or digital signals Connecting Power The BACnet Thermostat requires an external 24 volt AC power source Use the following guidelines when choosing and wiring transformers...

Страница 9: ...urrent changes Done Push this button at any point while entering a value For example if you have entered the first two digits of a password and the remaining two digits are correct pushing Done comple...

Страница 10: ...ing the Active Setpoints To enter or change the active temperature setpoints you may need to enter a user password NOTE In the following procedure the current active setpoint either cooling or heating...

Страница 11: ...he system will only heat the space Cool The system will only cool the space Auto The system will switch between heating and cooling Off The system is turned OFF 3 Press the Enter button to save the se...

Страница 12: ...t the next digit of the password 4 Press either the or button to turn the override ON or OFF Override Off The controller uses the unoccupied setpoint as the active setpoint Override On The controller...

Страница 13: ...all of the functions that can be set in the controller Not all functions are available on every model of controller Enter the Commissioning Mode For access to the commissioning functions you will nee...

Страница 14: ...select SETPOINT 2 Press Enter The SETPOINT menu opens 3 Choose and set each of the following setpoints OCC COOL The cooling setpoint that is used as the active setpoint when the system is occupied OCC...

Страница 15: ...work communication properties 1 From the MAIN menu press either the or button to select COMM 2 Press Enter The COMM menu opens up 3 Choose and set the following properties DEVICE ID This is the BACnet...

Страница 16: ...nu opens 3 Choose SET CLOCK and then press Enter The SET CLOCK menu opens Choose a clock function to set Choose one of the features in the SET CLOCK menu to change the date time or Daylight Saving Tim...

Страница 17: ...Monday to Friday Saturday and Sunday are not changed WEEKEND Sets the schedule for Saturday and Sunday Monday to Friday remain unchanged INDIVIDUAL DAYS Sets the schedule for just the selected day of...

Страница 18: ...ENABLE MIN ECON DAMPER ECON ENABLE TEM MIN DAT HEATING FAN Set the local override time From the SYSTEM menu choose LOCAL OVRD TIME to set the time the BACnet Thermostat will hold an override temperatu...

Страница 19: ...er application 2 From the SYSTEM menu choose MIN ECON DAMPER to set the minimum position for the economizer damper 3 From the SYSTEM menu choose ECON ENABLE TEM Enter the value that the outside air te...

Страница 20: ...the time the BACnet Thermostat will hold an override temperature setpoint as the active setpoint At the end of the period the BACnet Thermostat will use either an occupied or unoccupied setpoint as th...

Страница 21: ...ve Heating The O B output terminal is active on a call for heating Active Cooling The O B output terminal is active on a call for cooling Set up auxiliary heat Optional feature From the SYSTEM menu ch...

Страница 22: ...ACnet Thermostat The Metric version displays temperature in Celsius and uses metric values for units of measure The English version displays temperature in Fahrenheit and uses English values for units...

Страница 23: ...button is pushed BLANKING Choose one of the blanking options CLOCK An analog clock replaces the temperature and mode icons BACKLIGHT OFF The display brightness changes to the level set by DIM LEVEL af...

Страница 24: ...nt Limits No cooling setpoint can be higher than any heating setpoint If a user is adjusting a setpoint and it comes with the range set by Minimum Setpoint Differential the corresponding setpoint will...

Страница 25: ...or hot water systems Typically the BACnet Thermostat controls gas heat electric heat or direct expansion DX cooling with stage heating and cooling Staged cooling or heating can be mixed with a modula...

Страница 26: ...he Discharge Air Temperature rises above the Discharge Air Temperature setpoint The Discharge Air Temperature setpoint resets between room temperature and the limit for minimum discharge air temperatu...

Страница 27: ...when the BACnet Thermostat is connected to a network The remote temperature sensor RS is optional For single stage heating do not connect W2 For single stage cooling do not connect Y2 Connect outputs...

Страница 28: ...ed to a network The outdoor air temperature sensor OAT is required for compressor lockout based on outside air temperature The remote temperature sensor RS is optional For single compressor installati...

Страница 29: ...o set the following Device Instance MAC address Baud Use the following principles when wiring the BACnet Thermostat to an MS TP network Connect no more than 128 addressable BACnet devices to one MS TP...

Страница 30: ...IO DAPPS www daikinac com 30 Notes...

Страница 31: ...IO DAPPS www daikinac com 31 Notes...

Страница 32: ...t incurring obligations Training and Development Now that you have made an investment in modern efficient Daikin equipment its care should be a high priority For training information on Daikin HVAC pr...

Отзывы: