SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
180
2.7
Blower Motor Not Running
Error Code
A6
Applicable
Models
FXTQ-TA
Outline
Error is issued if the indoor unit determines that the indoor fan motor cannot rotate, regardless of
the rotation command from indoor unit.
Error Decision
Conditions
Determining successive abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
If that figure falls below 50 rpm 5 times successively, it is deemed abnormal operation.
If, during operation, the rotation command is stopped, the 5-second interval check is halted and
the counted number will be cleared.
Determining long-term abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
Performs rotation sampling 720 times (takes approx. one hour), and if the rotation speed falls
below 50 rpm over 100 times, it is deemed abnormal operation.
When the sampling reaches 720 times, the counted number will be cleared and the 720 times
sampling restarts.
If, during this, the rotation command is stopped, the 5-second interval check is halted, but the
counted number will be kept.
When the rotation command is restarted, the checks will resume.
Error Reset
Conditions
Reset by remote controller
Supposed
Causes
Fan or motor obstruction
Power interruption (low voltage)
Incorrect or loose wiring
Corrective
Actions
Check for obstruction on the fan or motor.
Verify the input voltage at the motor.
Check wiring or tighten wiring connections if needed.
Replace the indoor unit PCB or motor.
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...