Databook Modular T - October 2022 - Rev. 00
19
Size 06
Supply
Exhaust
Volume Flow rate
ESP
Volume Flow rate
ESP
2700
100
2700
100
RPM
RPM
2280
2284
Fan speed (High
–
Ultra High)
17(27)-4-02
Fan Curve Supply
Fan Curve Return
19(29)-2-12
19(29)-3-10
Size 07
Supply
Exhaust
Volume Flow rate
ESP
Volume Flow rate
ESP
3900
100
3900
100
RPM
RPM
2143
2155
Fan speed (High
–
Ultra High)
17(27)-4-02
Fan Curve Supply
Fan Curve Return
19(29)-2-10
19(29)-3-08
4.11. Antifreeze Logic
4.11.1. Pro Version
This function is used to avoid plate heat exchanger freezing as it activates a sequence of actions to counteract
the risk of frost formation.
The antifreeze logic is activated whenever outdoor and exhaust temperatures fall below pre-set values and
pressure drop across the heat exchanger, monitored thanks to a pressure transducer, exceeds a pre-set
threshold for a specific time duration. Once the logic is active, the actions performed are the following:
Antifreeze
disabled
No action
Antifreeze
enabled
1)
Bypass damper is gradually open up to 100% (only if heating coil present)
2)
Supply airflow is gradually reduced and return airflow is gradually increased up to a
20% variation
3)
Pre-heating coil is activated (if present)
4)
Unit goes in alarm if the last action performed is not effective to exit freeze condition
in less than 30 min.
An auto-reset is performed after 1 hour, after which the unit starts again
automatically.
Содержание ATB03RA
Страница 21: ...Databook Modular T October 2022 Rev 00 21...
Страница 44: ...Databook Modular T October 2022 Rev 00 44 6 4 Dimensional Drawings Dimension Drawing Size 03...
Страница 45: ...Databook Modular T October 2022 Rev 00 45 Dimension Drawing Size 04...
Страница 46: ...Databook Modular T October 2022 Rev 00 46 Dimension Drawing Size 05...
Страница 47: ...Databook Modular T October 2022 Rev 00 47 Dimension Drawing Size 06...
Страница 48: ...Databook Modular T October 2022 Rev 00 48 Dimension Drawing Size 07...