5
English
Installation Guidelines
• Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below.
• For any of the following installation patterns, the wall height on the outlet side should be 1200mm or less.
Precautions on Installation
• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10
foundation bolts, nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface.
More than 50
Direction
of air
1200
or less
More than 100
More than 50
More than 50
More
than 100
More than 150
Top view
Side view
Top view
More than 150
More than 300
More than 50
unit: mm
Wall facing one side
Wall facing two sides
Wall facing three sides
20