Service Check Function
SiBE04-809
74
Service Diagnosis
3.
Service Check Function
In the
ARC433
series
remote controller
, the temperature display sections on the main unit
indicate corresponding codes.
Check Method 1
1. When the timer cancel button is held down for 5 seconds, a “
00
” indication flashes on the
temperature display section.
2. Press the timer cancel button repeatedly until a continuous beep is produced.
The code indication changes in the sequence shown below, and notifies with a long beep.
Note:
1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To cancel the code display, hold the timer cancel button down for 5 seconds. The code
display also cancels itself if the button is not pressed for 1 minute.
No.
Code
No.
Code
No.
Code
1
00
12
F6
23
A1
2
U4
13
C7
24
E1
3
L5
14
A3
25
UA
4
E6
15
H8
26
UH
5
H6
16
H9
27
P4
6
H0
17
C9
28
L3
7
A6
18
C4
29
L4
8
E7
19
C5
30
H7
9
U0
20
J3
31
U2
10
F3
21
J6
32
EA
11
A5
22
E5
33
AH
<
ARC433B41
>
(R8358)
TIMER CANCEL button
Содержание ARXG35E3V1B
Страница 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series...
Страница 11: ...Introduction SiBE04 809 x...
Страница 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE04 809 12 Printed Circuit Board Connector Wiring Diagram...
Страница 207: ...Wiring Diagrams SiBE04 809 196 Appendix...