SiBE041525F
Check
Service Diagnosis
84
Step 3
Activate power transistor test operation from the indoor unit.
(1) Turn the power on.
(2) Press the center of the
TEMP
button and the
OFF
button on the remote controller at the
same time.
(3) Select
T
with the
TEMP
or
TEMP
button.
(4) Press the
FAN
button.
(5) Press the
FAN ONLY
button to start the power transistor test operation.
Diagnose method (Diagnose according to 6 LEDs lighting status.)
(1) If all the LEDs are lit uniformly, the compressor is defective.
→
Replace the compressor.
(2) If the LEDs are not lit uniformly, check the power module.
→
Refer to
Check No.22
.
(3) If NG in
Check No.22
, replace the power module.
(Replace the main PCB. The power module is united with the main PCB.)
If OK in
Check No.22
, check if there is any solder cracking on the PCB.
(4) If any solder cracking is found, replace the PCB or repair the soldered section.
If there is no solder cracking, replace the PCB.
Caution
(1) When the output frequency is low, the LEDs blink slowly. As the output frequency increases,
the LEDs blink quicker. (The LEDs look like they are lit.)
(2) On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
(R22990)
(3)
(2)
(5)
(4)
(2) (3)
(R19646)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.
Содержание ARX20K2V1B
Страница 12: ...SiBE041525F 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 15: ...SiBE041525F Specifications 4 Part 2 Specifications 1 Specifications 5 ...
Страница 16: ...Specifications SiBE041525F 5 Specifications 1 Specifications See corresponding databook ...
Страница 51: ...SiBE041525F Remote Controller 40 Part 5 Remote Controller 1 Remote Controller 41 ...