www.DaikinApplied.com 41
IM 1083-3
Form: 573882Y
Group:
Unit Ventilator
Type:
Basic Unit Data
Date:
July 2017
Warranty
Daikin Applied Unit Ventilator
Warranty Registration Form
Check, test & start procedure for Unit Ventilators
This form must be completely filled out and returned to, Daikin Warranty Department within ten days in order to comply with the terms of the Daikin
Applied warranty. Forms should be returned to Daikin Applied Warranty Department, P.O. Box 920, Auburn, NY 13021-0920.
Sales Office: ___________________________________S.O.#: _______________________ Date Started: _______________
Job Name: _____________________________________________G.O. # __________________________________________
Job Location: ___________________________________________________________________________________________
Unit Location: _____________________________ Unit Tagging: __________________________________________________
Model No: _________________________________ Serial No.: __________________________________________________
Supply Voltage: L1/L2 __________ L2/L3 ____________ L3/L1 ______________ Rated: _____________________________
Room Fan Motor Amps: T1: ___________ RPM _________
Nameplate Rating: ___________________________
I . Initial check
A. Does electrical service correspond to unit nameplate? ................................................................................. Yes
No
B. Are all electrical power connections tight? ................................................................................................... Yes
No
C. Does all field wiring conform to unit electrical schematic? ........................................................................... Yes
No
D. Is unit installed per IM bulletin? .................................................................................................................... Yes
No
F. Cabinet paint O.K.? ...................................................................................................................................... Yes
No
G. Cabinet bent? ............................................................................................................................................... Yes
No
H. Do outdoor and indoor fans turn freely? ....................................................................................................... Yes
No
I. Are all setscrews on outdoor and indoor fan couplings tight? ...................................................................... Yes
No
J. Are end bearing bolts on outdoor and indoor fan shaft tight? ....................................................................... Yes
No
K. Have the fan shaft end bearing and room fan motor been oiled (if applicable)? .......................................... Yes
No
L. Are outdoor air and return air dampers operating properly? ......................................................................... Yes
No
M. Is the filter clean? ......................................................................................................................................... Yes
No
N. Is there excessive noise or vibration? . ........................................................................................................ Yes
No
If Yes, corrective action (if any) ______________________________________________________________________________
Il . Controls check
A. Does the unit have Daikin controls (MicroTech)? .......................................................................................... Yes
No
lf No, control company _____________________________________________________________________________________
If controls are not by Daikin, skip to Section III.
B. Condensate disposal system operating O.K. (drainIess AED)? .................................................................... Yes
No
C. Does unit start and perform per sequence of operation as stated in OM? .................................................... Yes
No
D. If the unit has a unit mounted sensor, has the insulation been
removed from the sampling chamber inlet? .................................................................................................. Yes
No
E. Are all sensors installed and insulated properly? .......................................................................................... Yes
No
F. If the unit has MicroTech controls, room setpoint: _______°F Deadband 6° or _______°F
III . Refrigeration system
A. Has all field piping been leak tested to 100 psig (AVS, AVV, AVR, AHF, AHV & AHR) .................................. Yes
No
B. Is expansion valve bulb properly installed and insulated ............................................................................... Yes
No
C. High pressure control cutout (if applicable) _________ psig
D. Crankcase heater operating O.K.? ................................................................................................................ Yes
No
E. Reversing valve operating O.K.? .................................................................................................................. Yes
No
F. Emergency heat operating O.K.? ................................................................................................................. Yes
No
G. Piping correct (AVS, AVV, AVR, AHF, AHV & AHR to remote condensing unit)? .......................................... Yes
No
H. Checked for refrigerant leaks? ..................................................................................................................... Yes
No
IV . Hydronic piping check
A. Is unit piping correct (the remainder of this section applies only to units with Daikin controls)? ................... Yes
No
B. Is the modulating control valve(s) piped correctly (valve controlled units)? .................................................. Yes
No
C. Is the modulating control valve(s) placed in the upright position (valve controlled units)? ............................ Yes
No
D. Is 2 - position control valve(s) piped correctly (face and bypass)? ................................................................ Yes
No
Содержание ARQ
Страница 2: ......