IM 1083-3
14 www.DaikinApplied.com
Installing the VentiMatic Shutter
Assembly
The Daikin Applied VentiMatic Shutter Assembly is a one-way
shutter. It is a continuously variable, gravity-actuated, room
exhaust vent that operates in direct response to positive static
pressure, opposing any airflow into the room resulting in a
slight positive pressure.
The VentiMatic Shutter Assembly is mounted on an installed
wall louver. For larger units with 100% ventilation air dampers,
two VentiMatic Shutters may be mounted side by side on the
same louver, (Figure 26).
The size and appearance of the wall louvers with or without
optional grilles used with the unit ventilator, and the VentiMatic
Shutter, are identical.
When installing VentiMatic Shutter(s) on the wall louver, make
sure all moving parts are free to operate unobstructed and
placed level and plumb for proper operation. If optional steel
interior wall grille is furnished, install as shown in Figure 24.
Figure 24: Louver, VentiMatic Shutter, interior wall grille
details, dimensions
C
)
As Directed By Architect
3/4" (19mm) Approx.
7"
(178mm)
Cement Mortar
Steel Interior Wall
Grille(Optional)
See Note 3
12
5
⁄
8
"
(314mm)
3/4" (19mm) Approx.
Bird
Screen
Do Not Block Drain Holes With Caulk or Mortar
Not Less
Than 9"
(229mm)
Cement Mortar
Notes:
1 .
Horizontal blade wall louver shown. Vertical blade wall
louver also available with Ventimatic shutter.
2 .
Optional exterior grille matches unit ventilator wall louver
in material and design. Mounted on wall louvers.
3 .
Optional steel interior wall grille should be used to conceal
the interior wall opening whenever the Ventimatic shutter
is not located behind shelf cabinets. Hardware to mount
the interior wall grille is not included.
CAUTION
For proper operation, the VentiMatic shutter assembly must be
mounted on the same wall as the unit ventilator louver(s) to neu-
tralize wind effect.
Table 3: Recommended wall openings for wall louvers
B
C
Recommended
Wall Openings
For Wall
Louvers
Maximum Number of
VentiMatic Shutters
Which Can Be
Mounted On Stan-
dard Louver
VentiMatic
Shutter(s)
Air Capacity
Maximum
Length Height
24
ʺ
Shutter
36
ʺ
Shutter
cfm
L/s
48"
(1219)
51"
(1295)
48
5
⁄
8
"
(1222)
10
7
⁄
8
"
(267)
2
0
1000
472
60"
(1524)
63"
(1600)
60
5
⁄
8
"
(1527)
10
7
⁄
8
"
(267)
1
1
1250
590
72"
(1829)
75"
(1905)
72
5
⁄
8
"
(1832)
19
7
⁄
8
"
(495)
0
2
1500
708
Figure 25: Single VentiMatic Shutter & wall louver
Aluminum Wall Louver Assembly
With Bird Screen (See Note 1)
See
Steel VentiMatic
Shutter Assembly
4
1
⁄
8
"
(105mm)
23
7
⁄
8
" (606mm) or
35
7
⁄
8
" (911mm)
2" (51mm)
10
3
⁄
8
"
(264mm)
2.14" 51mm
Decorative Exterior Grille Also Available, see Note 2
(Bird Screen not shown)
Outside
Figure 26: Two VentiMatic Shutters & wall louver
Aluminum Wall Louver
Assembly with Bird Screen
(See Note 1)
2.14" 51mm
VentiMatic
Shutter
Assembly
Center Cover
10
3
⁄
8
"
(264mm)
See
Outside
Decorative Exterior Grille Also Available,
see Note 2. (Bird Screen not shown)
Содержание ARQ