ARC433 Series

Si10-416_B

372

Operation

5.11TIMER Operation

Timer functions are useful for automatically switching the 
air conditioner on or off at night or in the morning. You can 
also use OFF TIMER and ON TIMER in combination.

„

To use OFF TIMER 
operation

• Check that the clock is correct.

If not, set the clock to the present time. 

1. Press “OFF TIMER button”.

is displayed.

blinks.

2. Press “TIMER Setting button” 

until the time setting reaches the 
point you like.

• Every pressing of either button increases 

or decreases the time setting by 10 
minutes. Holding down either button 
changes the setting rapidly.

3. Press “OFF TIMER button” 

again.

• The TIMER lamp lights up.

„

4. Press “CANCEL button”.

•  The TIMER lamp goes off.

To cancel the OFF TIMER 
Operation

Содержание ARC433B46

Страница 1: ...ARC433 Series Si10 416_B 212 Remote Controllers ARC433B46 B47 TEMP ON OFF POWERFUL MODE FAN SWING QUIET SENSOR ECONO MOLDPROOF TIMER ON CANCEL OFF 1 2 5 6 9 10 12 11 16 18 17 13 15 14 3 4 7 8 ...

Страница 2: ...utton It selects the operation mode AUTO DRY COOL HEAT FAN 8 QUIET button OUTDOOR UNIT QUIET operation 9 FAN setting button It selects the airflow rate setting 10 SWING button 11 MOLD PROOF button MOLD PROOF operation 12 SENSOR button INTELLIGENT EYE operation 13 ON TIMER button 14 OFF TIMER button 15 TIMER setting button 16 TIMER CANCEL button 17 CLOCK button 18 RESET button Restart the unit if i...

Страница 3: ... the same type and replace the two old batteries together When the system is not used for a long time take the batteries out We recommend replacing once a year although if the remote controller display begins to fade or if reception deteriorates please replace with new alkali batteries Using manganese batteries reduces the lifespan The attached batteries are provided for the initial use of the sys...

Страница 4: ...a curtain the unit will not operate Do not drop the remote controller Do not get it wet The maximum distance for communication is about 7m To fix the remote controller holder on the wall 1 Choose a place from where the signals reach the unit 2 Fix the holder to a wall a pillar etc with the screws supplied with the holder 3 Place the remote controller in the remote controller holder Remote controll...

Страница 5: ...or receiver will reduce the sensitivity Wipe off dust with soft cloth Signal communication may be disabled if an electronic starter type fluorescent lamp such as inverter type lamps is in the room Consult the shop if that is the case If the remote controller signals happen to operate another appliance move that appliance to somewhere else or consult the shop ...

Страница 6: ...ed temperature setting For cooling 26 C 28 C For heating 20 C 24 C Be careful not to cool heat the room too much Keeping the temperature setting at a moderate level helps save energy Cover windows with a blind or a curtain Blocking sunlight and air from outdoors increases the cooling heating effect Clogged air filters cause inefficient operation and waste energy Clean them once in about every two ...

Страница 7: ...air conditioner will operate with the same operation mode To start operation 1 Press MODE selector button and select a operation mode Each pressing of the button advances the mode setting in sequence AUTO DRY COOL HEAT FAN 2 Press ON OFF button The OPERATION lamp lights up To stop operation 3 Press ON OFF button again Then OPERATION lamp goes off Cooling only Heat pump ...

Страница 8: ...ress to lower the temperature To change the air flow rate 5 Press FAN setting button Indoor unit quiet operation When the airflow is set to the noise from the indoor unit will become quieter Use this when making the noise quieter The unit might lose capacity when the airflow rate rate is set to a weak level DRY mode AUTO or HEAT or COOL or FAN mode The airflow rate setting is Five levels of airflo...

Страница 9: ...m switches into defrosting operation to take away the frost During defrosting operation hot air does not flow out of indoor unit This air conditioner cools the room by blowing the hot air in the room outside so if the outside temperature is high performance drops At smaller airflow rates the cooling heating effect is also smaller In AUTO operation the system selects a temperature setting and an ap...

Страница 10: ...played on the LCD and the flaps will begin to swing 2 When the flap has reached the desired position press SWING button once more The flap will stop moving disappears from the LCD To adjust the vertical blades 3 Press SWING button is displayed on the LCD 4 When the louvers have reached the desired position press the SWING The louvers will stop moving disappears from the LCD button once more louver...

Страница 11: ...circulates cold air which tends to collected at the bottom of the room and hot air which tends to collect near the ceiling throughout the room preventing areas of cold and hot developing ATTENTION Always use a remote controller to adjust the flaps angle If you attempt to move it forcibly with hand when it is swinging the mechanism may be broken Be careful when adjusting the louvers Inside the air ...

Страница 12: ...on the LCD Airflow rate is set to AUTO COOL DRY The flap will go up HEAT The flap will go down To cancel COMFORT AIRFLOW 2 Press COMFORT AIRFLOW button again The flaps will return to the memory position from before COMFORT AIRFLOW mode disappears from the LCD Notes on COMFORT AIRFLOW POWERFUL operation and COMFORT AIRFLOW operation cannot be used at the same time Priority is given to POWERFUL oper...

Страница 13: ...on again disappears from the LCD NOTE Notes on POWERFUL operation In COOL and HEAT mode In DRY mode In FAN mode When using priority room setting See Note for multi system POWERFUL Operation can only be set when the unit is running Pressing the operation stop button causes the settings to be canceled and the disappears from the LCD Priority is given to the function of whichever button is pressed la...

Страница 14: ...OUTDOOR UNIT QUIET operation If using a multi system this function will work only when the OUTDOOR UNIT QUIET operation is set on all operated indoor units However if using priority room setting see Note for multi system This function is available in COOL HEAT and AUTO modes This is not available in FAN and DRY mode POWERFUL operation and OUTDOOR UNIT QUIET operation cannot be used at the same tim...

Страница 15: ... rate for HOME LEAVE operation 1 Press HOME LEAVE button Make sure is displayed in the remote controller display Initial setting Selectable range temperature Airflow rate temperature Airflow rate Cooling 25 C 18 32 C 5 step and Heating 25 C 10 30 C 5 step and 2 Adjust the set temperature with or as you like you like 3 Adjust the airflow rate with FAN setting button as When using HOME LEAVE operati...

Страница 16: ... the set temperature for normal operation Is there a set temperature and airflow rate which is most comfortable a set temperature and airflow rate which you use the most HOME LEAVE operation is a function that allows you to record your favorite set temperature and airflow rate You can start your favorite operation mode simply by pressing the HOME LEAVE button on the remote controller This function...

Страница 17: ...emote controller operations Once the temperature and air flow rate for HOME LEAVE operation are set those settings will be used whenever HOME LEAVE operation is used in the future To change these settings please refer to the Before using HOME LEAVE operation section above HOME LEAVE operation is only available in COOL and HEAT mode Cannot be used in AUTO DRY and FAN mode HOME LEAVE operation runs ...

Страница 18: ...nit is running Pressing the operation stop button causes the settings to be canceled and the disappears from the LCD ECONO operation is a function which enables efficient operation by limiting the power consumption of the outdoor unit operating frequency ECONO operation functions in AUTO COOL DRY and HEAT modes POWERFUL operation and ECONO operation cannot be used at the same time Priority is give...

Страница 19: ...n for two seconds one more time disappears from the LCD NOTE MOLD PROOF operation is a function which reduces the spread of mold by using Fan mode to lower the humidity inside the indoor unit MOLD PROOF operation will operate for approximately one hour after dry or cooling mode is turned off This function is not designed to remove existing dust or mold MOLD PROOF operation is not available when th...

Страница 20: ...nt To start INTELLIGENT EYE operation 1 Press SENSOR button is displayed on the LCD To cancel the INTELLIGENT EYE operation 2 Press SENSOR button again disappears from the LCD EX When somebody in the room Normal operation When nobody in the room 20 min after start energy saving operation Somebody back in the room Back to normal operation ...

Страница 21: ...ation range Sensor detection sensitivity changes according to indoor unit location the speed of passersby temperature range etc The sensor also mistakenly detects pets sunlight fluttering curtains and light reflected off of mirrors as passersby INTELLIGENT EYE operation will not go on during powerful operation Night set mode will not go on during you use INTELLIGENT EYE operation Do not place larg...

Страница 22: ...t the clock is correct If not set the clock to the present time 1 Press OFF TIMER button is displayed blinks 2 Press TIMER Setting button until the time setting reaches the point you like Every pressing of either button increases or decreases the time setting by 10 minutes Holding down either button changes the setting rapidly 3 Press OFF TIMER button again The TIMER lamp lights up 4 Press CANCEL ...

Страница 23: ...s canceled when remote controller batteries are replaced When operating the unit via the ON OFF Timer the actual length of operation may vary from the time entered by the user Maximum approx 10 minutes When the OFF TIMER is set the air conditioner automatically adjusts the temperature setting 0 5 C up in COOL 2 0 C down in HEAT to prevent excessive cooling heating for your pleasant sleep ...

Страница 24: ... Holding down either button changes the setting rapidly 3 Press ON TIMER button again The TIMER lamp lights up To cancel ON TIMER operation 4 Press CANCEL button The TIMER lamp goes off ATTENTION In the following cases set the timer again After a breaker has turned OFF After a power failure After replacing batteries in the remote controller Example Present time 11 00 p m The unit operating OFF TIM...

Страница 25: ...eration mode in the room where the unit is first run is given priority but the following situations are exceptions so please keep this in mind If the operation mode of the first room is FAN Mode then using Heating Mode in any room after this will give priority to heating In this situation the air conditioner running in FAN Mode will go on standby and the operation lamp will flash COOL DRY and FAN ...

Страница 26: ...e controllers When clearing OUTDOOR UNIT QUIET operation clear one of the operating indoor units using their remote controller However OUTDOOR UNIT QUIET operation display remains on the remote controller for other rooms We recommend you release all rooms using their remote controllers With the Priority Room Setting present but inactive or not present NIGHT QUIET Mode requires initial programming ...

Страница 27: ... Rooms A B C and D are all operating If the unit in Room A enters POWERFUL operation operation capacity will be concentrated in Room A In such a case the cooling heating efficiency of the units in Rooms B C and D may be slightly reduced Room A is the Priority Room in the examples Just by setting the unit in Room A to QUIET operation the air conditioner starts OUTDOOR UNIT QUIET operation You don t...

Отзывы: