Troubleshooting
Service manual
18
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
2.3.10 89-03 – Heat exchanger frozen
Trigger
Effect
Reset
Evaporation temperature
is too low during defrost.
Unit will NOT stop
operating.
Automatic reset.
Outlet water after heat
exchanger thermistor
<6°C during defrost.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outlet water after heat exchanger thermistor. See
Possible cause:
Faulty outlet water after heat exchanger thermistor.
2
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.11 8F-00 – Abnormal increase outlet water temperature (domestic hot water)
Trigger
Effect
Reset
Outlet water after backup
heater thermistor detects
a too high temperature
during domestic hot
water without electrical
heater.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the water circuit for an external heat source. See
299].
Possible cause:
Increased water temperature due to an external heat source.
2
Perform a check of the outlet water after backup heater thermistor. See
Possible cause:
Faulty outlet water after backup heater thermistor.
3
Perform a check of the backup heater. See
Possible cause:
Faulty backup heater.
4
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.