3
|
Components
Service manual
146
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
3.8 Compressor thermal protector
3.8.1 Checking procedures
To perform a mechanical check of the compressor thermal protector
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
230].
Prerequisite:
Remove the compressor insulation.
1
Remove the compressor thermal protection with bracket from the
compressor.
a b
c
a
Compressor thermal protector
b
Bracket
c
Compressor
2
If in doubt, measure the temperature of the compressor thermal protection.
Result:
The temperature MUST be below 104°C.
3
Using a hot air gun, carefully heat the compressor thermal protection to
slightly above 132°C (compressor thermal protection trips at 126~132°C).
INFORMATION
Make sure that the wiring between the compressor thermal protector connector and
the connector on the PCB is properly connected and NOT damaged (check
continuity), see
314].
For single phase units ONLY: Make sure that the high pressure switch (which is wired
in series with the compressor thermal protector) functions correctly, see
4
Disconnect the compressor thermal protector from the intermediate
connector and measure the resistance between pins 1‑2.
Result:
The contact MUST be open (measured resistance = OL).
5
Let the compressor thermal protection cool down below 104°C (reset
temperature is 104~116°C).
6
Again measure the resistance between the pins 1‑2 of the connector of the
compressor thermal protector.
Result:
The contact MUST be closed (measured resistance = 0 Ω).