6 Electrical installation
Installation manual
23
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685229-1A – 2022.05
Connecting the user interface cable to the outdoor unit
Wires: 4×(0.75~1.25 mm²)
Maximum length: 200 m
[2.9]
Control
[1.6]
Room sensor offset
1
Access the electrical connections. See
electrical wiring to the outdoor unit"
2
Connect the user interface cable to the outdoor unit. Fix the
cable with cable ties to the cable tie mountings.
X1B
a
X5M.11
X5M.12
X5M.16
X5M.15
1
2
3
4
P1P2
+
PSU
a
User interface: Required for operation. Delivered with the
unit as accessory.
X5M
180°
11 121516
Installing the user interface, and connecting the user interface
cable to it
You need the following user interface accessories (delivered on top
of the unit):
a
b
c
d
×2
×2
a
Front plate
b
Rear plate
c
Screws
d
Wall plugs
1
Mount the rear plate to the wall.
▪ Use the 2 screws and wall plugs.
▪ Use any of the 6 holes. The holes are compatible with
standard electrical box extenders of 60 mm.
a
b
60 mm
a
Holes
b
Electrical box extender (field supply)
2
Connect the user interface cable to the user interface.
▪ Choose one of the 4 possible wiring intakes (
a
,
b
,
c
or
d
).
▪ If you choose the left or right side, make a hole for the cable
in the part of the casing where the casing is thinner.