Troubleshooting

Table of anomalies and remedies

 In case of water leaks or anomalous functioning 

immediately cut off the power supply and close the 
water taps.

  Should one of the following anomalies occur, contact 

an authorised service centre or an authorised qualified 
person, but do not intervene personally.

The ventilation does not activate even if there is hot or 
cold water in the hydraulic circuit.

The appliance leaks water during the heating function.

-  The appliance leaks water only during the cooling 

function.

The appliance makes an excessive noise.

There are formations of dew on the front panel.

The interventions must be carried out by a qualified installer 
or by a specialised service centre.

Effect

Cause

Remedy

A delayed activation of the ventilation 
respect to the new temperature or 
function settings.

The circuit valve needs some time to 
open and as a result the hot or cold 
water takes time to circulate in the 
appliance.

Wait for 2 or 3 minutes to open the 
circuit valve.

The appliance does not activate the 
ventilation.

No hot or cold water in the system.

Check that the water boiler or cooler 
are functioning correctly.

The ventilation does not activate even if 
there is hot or cold water in the hydraulic 
circuit.

The hydraulic valve remains closed.

Dismount the valve body and check if 
the water circulation is restored. 
Check the working efficiency of the 
valve by powering it separately with 
230V. If it activates the problem could 
be the electronic control.

The fan motor is blocked or burnt out.

Check the windings of the motor and 
the free rotation of the fan.

The micro-switch that stops the 
ventilation when the filter grill is opened 
does not close correctly.

Check that by closing the grill the micro-
switch contact is activated.

The electrical connections are not 
correct.

Check the electrical connections.

The appliance leaks water during the 
heating function.

Leaks in the hydraulic connections of 
the system.

Check the leak and fully tighten the 
connections.

Leaks in the valve unit.

Check the state of the gaskets.

There are formations of dew on the 
front panel.

Thermal insulation detached.

Check the correct positioning of the 
thermo-acoustic insulation paying 
attention to that in the front above the 
finned battery.

There are drops of water on the air 
outlet grill.

In situations of high humidity (>60%) 
condensation could form, especially at 
the minimum ventilation speeds.

As soon as the humidity starts falling 
the phenomenon disappears. In any 
case the presence of a few drops of 
water in the appliance does not indicate 
a malfunction.

Содержание Altherma FWXV15AATV3

Страница 1: ...FWXV10AATV3 FWXV15AATV3 FWXV20AATV3 FWXM10AATV3 FWXM15AATV3 FWXM20AATV3 INSTALLATION MANUAL Daikin Altherma Heat pump convector...

Страница 2: ...achine in a rapid unmistakable way Symbols U User Refers to pages containing instructions or information for the user I Installer Refers to pages containing instructions or information for the install...

Страница 3: ...chine 8 2 5 Remove side 9 2 6 Vertical floor or wall installation FWXV series 9 2 7 Horizontal or ceiling installation FWXM series 10 2 8 Hydraulic connections 10 2 9 Condensation discharge 11 2 10 Fi...

Страница 4: ...e direct air flow Do not leave the room closed for long periods Periodically open the windows to ensure a correct change of air This instruction leaflet is an integral part of the appliance and conseq...

Страница 5: ...urce of danger It is forbidden to climb onto the appliance or rest any object on it The external parts of the appliance can reach temperatures of more than 70 C Product range There are 2 types of DAIK...

Страница 6: ...3 FWXV15AATV3 FWXV20AATV3 A mm 999 1199 1399 U M FWXM10AATV3 FWXM15AATV3 FWXM20AATV3 A mm 725 925 1125 FWXV FWXM 135 mm 601 mm 999 mm 1199 mm 1399 mm GENERAL Dimensions Overall dimensions Heat pump co...

Страница 7: ...discharge of the condensation outside in case of ceiling installation FWXM series the airflow is not directed towards persons The following descriptions of the various mounting phase and the relative...

Страница 8: ...procedures below Remove the upper grill loosen the fixing screws loosen the fixing screws of the upper grill remove the grill Remove the front grill extract the grill until it is completely out of th...

Страница 9: ...ble drill to make the holes with and insert the toggle bolts 2 for each bracket fix the two brackets Do not over tighten the screws so that the brackets can be adjusted with a spirit level Fully tight...

Страница 10: ...Any counterslope of the discharge line can cause water leakage Toggle bolts Brackets Screws Drainage pipe Hydraulic connections NB the nominal diameter unless otherwise indicated always refers to the...

Страница 11: ...ainer it must be open to the atmosphere and the tube must not be immerged in water to avoid problems of adhesiveness and counter pressure that would interfere with the normal outflow If there is a hei...

Страница 12: ...ame collection bowl insulate the bowl condensation discharge pipe along all of its length Venting of the battery Filling the system Evacuating air while filling the system When starting up the system...

Страница 13: ...egory III Maintenance Cleaning the outside Routine maintenance is indispensable to keep the heat pump convector in perfect working condition safe and reliable over the years This can be done every six...

Страница 14: ...the seat lit the grill and slide it outwards then remove the filter by pulling it outwards Extraction of filter cells After a period of continuous operation and in consideration of the concentration o...

Страница 15: ...oler with the mobile panel missing or out of position After finishing the cleaning of the filter check that the panel is mounted correctly Cleaning filtering seats For the versions with a grill with f...

Страница 16: ...not activate even if there is hot or cold water in the hydraulic circuit The hydraulic valve remains closed Dismount the valve body and check if the water circulation is restored Check the working ef...

Страница 17: ...drainage pipe The condensation discharge does not need an inclination for correct drainage The connection pipes and the valve unit are not insulated well Check the insulation of the pipes The applianc...

Страница 18: ...18 S I U...

Страница 19: ...19 S I U...

Страница 20: ...Copyright 2019 Daikin...

Отзывы: