INSTALLATION MANUAL

Daikin Altherma

Heat pump convector

Содержание Altherma FWXM10AATV3

Страница 1: ...FWXV10AATV3 FWXV15AATV3 FWXV20AATV3 FWXM10AATV3 FWXM15AATV3 FWXM20AATV3 INSTALLATION MANUAL Daikin Altherma Heat pump convector ...

Страница 2: ...machine in a rapid unmistakable way Symbols U User Refers to pages containing instructions or information for the user I Installer Refers to pages containing instructions or information for the installer S Service Refers to pages containing instructions or information for the installer TECHNICAL CUSTOMER SERVICE Editorial pictograms Safety pictograms Generic danger Signals to the personnel that th...

Страница 3: ...achine 8 2 5 Remove side 9 2 6 Vertical floor or wall installation FWXV series 9 2 7 Horizontal or ceiling installation FWXM series 10 2 8 Hydraulic connections 10 2 9 Condensation discharge 11 2 10 Filling the system 12 2 11 Evacuating air while filling the system 12 2 12 Electrical connections 13 2 13 Maintenance 13 2 14 Cleaning the outside 13 2 15 Cleaning air suction filter 14 2 16 Energy sav...

Страница 4: ...he direct air flow Do not leave the room closed for long periods Periodically open the windows to ensure a correct change of air This instruction leaflet is an integral part of the appliance and consequently must be kept carefully and must ALWAYS accompany the appliance even when it is passed to a new owner or user or transferred onto another system If it is lost or damaged please contact the loca...

Страница 5: ...ource of danger It is forbidden to climb onto the appliance or rest any object on it The external parts of the appliance can reach temperatures of more than 70 C Product range There are 2 types of DAIKIN heat pump convectors FWXV and FWXM each of which is offered in 3 sizes with different performances and dimensions FWXV series cooler convector with metal cabinet for vertical installation FWXM ser...

Страница 6: ...V3 FWXV15AATV3 FWXV20AATV3 A mm 999 1199 1399 U M FWXM10AATV3 FWXM15AATV3 FWXM20AATV3 A mm 725 925 1125 FWXV FWXM 135 mm 601 mm 999 mm 1199 mm 1399 mm GENERAL Dimensions Overall dimensions Heat pump convector 2 pipes Dimensions ...

Страница 7: ...e discharge of the condensation outside in case of ceiling installation FWXM series the airflow is not directed towards persons The following descriptions of the various mounting phase and the relative designs refer to a version of the machine with fixtures on the left The operations for the mounting of machines with fixtures on the right are exactly the same Only the images are to be considered a...

Страница 8: ...e procedures below Remove the upper grill loosen the fixing screws loosen the fixing screws of the upper grill remove the grill Remove the front grill extract the grill until it is completely out of the seat tilt the grill slide outwards Fixing screws Upper grill Front panel Front grill Remove the frontal panel loosen the fixing screws remove the panel ...

Страница 9: ...able drill to make the holes with and insert the toggle bolts 2 for each bracket fix the two brackets Do not over tighten the screws so that the brackets can be adjusted with a spirit level Fully tighten the four screws to block the two brackets Check the stability by manually moving the brackets to the right and to the left up and down Mount the unit checking that it fits correctly onto the brack...

Страница 10: ...e Any counterslope of the discharge line can cause water leakage Toggle bolts Brackets Screws Drainage pipe Hydraulic connections NB the nominal diameter unless otherwise indicated always refers to the internal diameter To avoid the formation of surface condensation it is always recommended to install electric valve kits except in the case where an electrical control eg electrothermal head is prov...

Страница 11: ...ainer it must be open to the atmosphere and the tube must not be immerged in water to avoid problems of adhesiveness and counter pressure that would interfere with the normal outflow If there is a height difference that could interfere with the outflow of the condensation a pump must be mounted in a vertical installation mount the pump under the lateral drainage tray in a horizontal installation t...

Страница 12: ... same collection bowl insulate the bowl condensation discharge pipe along all of its length Venting of the battery Filling the system Evacuating air while filling the system When starting up the system make sure that the hydraulic unit lockshield is open If there is no electric power and the thermo valve has already been powered use the special cap to press the valve stopper to open it Open all th...

Страница 13: ...tegory III Maintenance Cleaning the outside Routine maintenance is indispensable to keep the heat pump convector in perfect working condition safe and reliable over the years This can be done every six months for some interventions and annually for others by the Technical Service Assistance technically authorised and prepared using always original spare parts Before every cleaning and maintenance ...

Страница 14: ... the seat lit the grill and slide it outwards then remove the filter by pulling it outwards Extraction of filter cells After a period of continuous operation and in consideration of the concentration of impurities in the air or when he intends to restart the plant after a period of inactivity proceed as described Front grill Grill hook Filter ...

Страница 15: ...ooler with the mobile panel missing or out of position After finishing the cleaning of the filter check that the panel is mounted correctly Cleaning filtering seats For the versions with a grill with flaps insert the two lugs into the special slots turn it and hook it up with a slight tap on the upper part Ending Cleaning Operations Energy saving tips Always keep the filters clean when far possibl...

Страница 16: ...s not activate even if there is hot or cold water in the hydraulic circuit The hydraulic valve remains closed Dismount the valve body and check if the water circulation is restored Check the working efficiency of the valve by powering it separately with 230V If it activates the problem could be the electronic control The fan motor is blocked or burnt out Check the windings of the motor and the fre...

Страница 17: ... drainage pipe The condensation discharge does not need an inclination for correct drainage The connection pipes and the valve unit are not insulated well Check the insulation of the pipes The appliance makes a strange noise The fan touches the structure Check the clogging of filters and clean them if necessary The fan is unbalanced The unbalancing causes excessive vibrations of the machine replac...

Страница 18: ...18 S I U ...

Страница 19: ...19 S I U ...

Страница 20: ...Copyright 2019 Daikin ...