9 Installation
Installer reference guide
33
EJHA EHY32AA
Daikin Altherma Hybrid hydrosplit heat pump
4P531180-1 – 2018.06
NOTICE
Cold climates.
If the unit is installed in a cold climate:
▪ Take adequate measures so that the evacuated
condensate CANNOT freeze.
▪ Do NOT use the drain plug and drain hose with the
outdoor unit.
Possible consequence:
Drain water
might freeze, decreasing the heating capacity.
NOTICE
Provide at least 300 mm of free space below the unit.
Additionally, make sure the unit is positioned at least
100 mm above the expected level of snow.
Except in cold climates, use the drain plug and a hose for drainage.
b
c
d
a
a
Drain hole
b
Bottom frame
c
Drain plug (delivered as accessory)
d
Hose (field supply)
9.3.6
To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1
Prepare 2 cables as indicated in the following illustration (field
supply).
2
Place the 2 cables over the outdoor unit.
3
Insert a rubber sheet between the cables and the outdoor unit
to prevent the cables from scratching the paint (field supply).
4
Attach the ends of the cables and tighten them.
9.4
Mounting the gas boiler
9.4.1
To install the gas boiler
1
Lift the unit from the package.
33~36kg
2
The bracket to mount the boiler on the heat pump module is an
accessory of the gasboiler. Fix the wall bracket to the wall with
2 M8 bolts.
2×
3
Lift the boiler. One person lifts the gas boiler on the left side (left
hand on the top and right hand on the bottom) and another
person lifts the gas boiler on the right side (left hand on the
bottom and right hand on the top).
4
Tilt the top of the unit at the position of the wall bracket and
slide the boiler downwards to fix the boiler bracket onto the wall
bracket.
5
Make sure the gas boiler is fixed properly to the wall.