Daikin Altherma EDLQ-BB6V3 Скачать руководство пользователя страница 15

E(D/B)(H/L)Q011~016BB

Unit and options for air to water heat pump system

4PW67905-1 – 01.2011

Operation manual

14

[1] Weather dependent set point

The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: low outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C.

Field settings for heating operation

[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.

[1-01] High ambient temperature (Hi_A): high outdoor
temperature.

[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A). 
Note that the Lo_Ti value should be higher than Hi_Ti, as for
low outdoor temperatures (i.e. Lo_A) warmer water is
required.

[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A). 
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.

Field settings for cooling operation

[1-05] Weather dependent for cooling function enable (1)/
disable (0)

[1-06] Low ambient temperature (Lo2_A): low outdoor
temperature.

[1-07] High ambient temperature (Hi2_A): high outdoor
temperature.

[1-08] Set point at low ambient temperature (Lo2_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo2_A).
Note that the Lo2_Ti value should be higher than Hi2_Ti, as
for low outdoor temperatures (i.e. Lo2_A) less cold water
suffices.

[1-09] Set point at high ambient temperature (Hi2_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi2_A). 
Note that the Hi2_Ti value should be lower than Lo2_Ti, as
for warmer outdoor temperatures (i.e. Hi2_A) colder water is
required.

T

t

Target water temperature

T

A

Ambient (outdoor) temperature

Shift value Shift value

[2] Disinfection function

Applies only to installations with a domestic hot water tank.

The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.

[2-00] Operation interval: day(s) of the week at which the
domestic hot water should be heated.

[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).

[2-02] Start time: time of the day at which the domestic hot
water should be heated.

[2-03] Set point: high water temperature to be reached.

[2-04] Interval: time period defining how long the set point
temperature should be maintained.

T

DHW

Domestic hot water temperature

T

U

User set point temperature (as set on the user interface)

T

H

High set point temperature [2-03]

Time

Lo_Ti

Lo2_Ti

Lo_A

Lo2_A

Hi_A

Hi2_A

TA

Tt

+ 05

00

– 05

Hi_Ti

Hi2_Ti

Shift value

CAUTION

The disinfection function field settings must be configured
by the installer according to the applicable legislation.

WARNING

Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.

When the high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rises above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to the applicable legislation.

CAUTION

Make sure that the disinfection function start time [2-02]
with defined duration [2-04] is not interrupted by possible
domestic hot water demand.

00.00

22.00

24.00

01.00

23.00

t

T

DHW

T

H

T

U

[2-02]

[2-03]

[2-04]

Содержание Altherma EDLQ-BB6V3

Страница 1: ...B6W1 EDLQ011BB6V3 EDLQ014BB6V3 EDLQ016BB6V3 EDLQ011BB6W1 EDLQ014BB6W1 EDLQ016BB6W1 EBHQ011BB6V3 EBHQ014BB6V3 EBHQ016BB6V3 EBHQ011BB6W1 EBHQ014BB6W1 EBHQ016BB6W1 EBLQ011BB6V3 EBLQ014BB6V3 EBLQ016BB6V3...

Страница 2: ...according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction manual specified for a certa...

Страница 3: ...ut electrical booster heater EKHTS in 2 different sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual...

Страница 4: ...is gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no...

Страница 5: ...ler 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon...

Страница 6: ...orage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disa...

Страница 7: ...upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time of...

Страница 8: ...al temperature set point only appears on the display after pressing one of the buttons wi or wj If no button is pressed for 5 seconds the temperature set point will automatically disappear from the di...

Страница 9: ...ion with a set point weather dependent or manually set Four actions can be programmed These actions are repeated daily 3 Quiet mode refer to Programming space cooling quiet mode or booster heater mode...

Страница 10: ...a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will b...

Страница 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Страница 12: ...select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater...

Страница 13: ...button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the but...

Страница 14: ...eat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interfac...

Страница 15: ...2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer ou...

Страница 16: ...hysteresis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic...

Страница 17: ...ng automatic storage during night default setting If it seems that the domestic hot water night storage operation is not sufficient for your needs an additional scheduled reheat during daytime can be...

Страница 18: ...to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case weather...

Страница 19: ...ri Mon Sun All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 fixed 5 C 03 Set poi...

Страница 20: ...tallation related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1...

Страница 21: ...Not applicable Do not change the default value E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Do not change the default value dependi...

Страница 22: ...oid injury give the piping time to return to normal temperature or be sure to wear proper gloves Do not touch any switch with wet fingers Touching a switch with wet fingers can cause electrical shock...

Страница 23: ...shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualifi...

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...4PW67905 1 01 2011 Copyright 2011 Daikin...

Отзывы: