1 Troubleshooting
Service manual
6
EBLQ+EDLQ011~W1 + EBLQ+EDLQ011~0W1
+ EK(2)CB EKMB9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.4
7H-06 – Abnormal flow (Cooling/defrost)
Trigger
Effect
Reset
Water flow
abnormality
determined mainly
during cooling or
defrost operation.
Unit will stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
NOTICE
Focus the troubleshooting on the space cooling circuit.
1
Check that all stop valves of the water circuit are open. See
"3.3 Water circuit" on page 95
.
Possible cause:
Closed stop valve in the water circuit.
2
Perform a check of the air purge valves. See
.
Possible cause:
Air in the water circuit.
3
"3.3 Water circuit" on page 95
Possible cause:
Water flow is too low.
4
Check the water pressure. See
"3.3 Water circuit" on page 95
.
Possible cause:
Water pressure is too low.
5
Check the water volume. See
"3.3 Water circuit" on page 95
.
Possible cause:
Water volume is too low.
6
Check if a by‑pass is installed in the water circuit. See
"3.3 Water circuit" on page 95
.
Possible cause:
No by‑pass installed in the water circuit.
7
Clean the water filter. See
Possible cause:
Faulty or dirty water filter.
8
Perform an electrical check of the water flow sensor. See
"2.25 Water flow sensor" on page 87
.
Possible cause:
Faulty water flow sensor.
9
Perform a check of the 3-way valve. See
Possible cause:
Faulty 3‑way valve.
10
Perform a check of the water pump. See
Possible cause:
Faulty water pump.
11
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
12
Perform a check of the backup heater. See
.
Possible cause:
Faulty backup heater.
13
Perform a check of the booster heater. See
.
Possible cause:
Faulty booster heater.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.5
7H-07 – Abnormal flow / pump de-
blocking
Trigger
Effect
Reset
Unit detects that the
pump might be
blocked.
Unit will NOT stop
operating. Pump
de‑blocking routine
started (30 minutes).
Automatic reset when
pump is de‑blocked.
To solve the error code
1
No specific check / repair procedures can be performed to solve
this error code. Wait until the pump de–blocking routine is
finished (±30 minutes maximum).
INFORMATION
As long as the pump de‑blocking routine is active, the error
code will be displayed on the user interface.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.6
80-00 – Inlet water thermistor abnormality
Trigger
Effect
Reset
Inlet water thermistor
input is out of range.
Unit will stop
operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1
Perform a check of the inlet water thermistor. See
.
Possible cause:
Faulty inlet water thermistor.
2
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.7
81-00 – Outlet water thermistor
abnormality
Trigger
Effect
Reset
Outlet water
thermistor input is out
of range.
Unit will stop
operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1
Perform a check of the outlet water thermistor. See
.
Possible cause:
Faulty outlet water thermistor.