Operation manual

9

E(D/B)(H/L)Q011~016BB

Unit and options for air to water heat pump system

4PW67905-1 – 01.2011

What can the schedule timer NOT do?

The schedule timer can not change the operation mode from space
heating to space cooling or vice versa.

How to interpret the programmed actions

To be able to understand the behaviour of your installation when the
schedule timer is enabled, it is important to keep in mind that the
"last" programmed command overruled the "preceding" programmed
command and will remain active until the "next" programmed
command occurs.

Example: imagine the actual time is 17:30 and actions are
programmed at 13:00, 16:00 and 19:00. The "last" programmed
command (16:00) overruled the "previous" programmed command
(13:00) and will remain active until the "next" programmed command
(19:00) occurs.

So in order to know the actual setting, one should consult the last
programmed command. It is clear that the "last" programmed
command may date from the day before. Refer to 

"Consulting

programmed actions" on page 12

.

4.7.

Programming and consulting the schedule timer

Getting started

Programming the schedule timer is flexible (you can add, remove or
alter programmed actions whenever required) and straightforward
(programming steps are limited to a minimum). However, before
programming the schedule timer, remind:

Familiarise yourself with the icons and the buttons. You will need
them when programming. Refer to 

"4.3. Name and function of

buttons and icons" on page 4

.

Fill out the form at the very end of this manual. This form can
help you define the required actions for each day. Keep in mind
that:
-

In the space heating and domestic water heating program, 4 
actions can be programmed per weekday. The same actions 
are repeated on a weekly basis.

-

In the space cooling, quiet mode, and booster heater mode

(1)

 

program, 4 actions can be programmed per mode. The same 
actions are repeated on a daily basis.

Take your time to enter all data accurately.

Try to program the actions in a chronological way: start with
action 1 for the first action and end with the highest number for
the last action. This is not a requirement but will simplify the
interpretation of the program later.

If 2 or more actions are programmed for the same day and at the
same time, only the action with the highest action number will be
executed.

You can always alter, add or remove the programmed actions
later.

INFORMATION

The programmed actions are not stored according to
their timing but according to the time of programming.
This means that the action that was programmed first
gets action number 1, even though it is executed after
other programmed action numbers.

When the schedule timer switches space heating or
space cooling 

x

, the controller will also be

switched off. Note that this has no influence on
domestic water heating.

[4-03]=4 or 5. In case no domestic water heating
actions are programmed, enabling or disabling the
schedule timer will only have influence on the space
heating, cooling and quite mode. In this way it is
possible to separate on one hand the space heating,
cooling and quite mode scheduled action as part of
the schedule timer and on the other hand the storage
and reheat operation of the domestic water heating.
In this way, it is easy to disable the space heating and
cooling by disabling the schedule timer with keeping
the storage and reheat domestic water heating
enabled (refer to 

"Scheduled domestic hot water

storage" on page 

15

  and 

"Scheduled/continuous

domestic hot water reheat" on page 15

).

NOTICE

The setting [4-03] shall not be modified. The installer
selected the proper setting for your application.

INFORMATION

The status of this setting is only mentioned to indicate
which settings and functions are applicable for your
application.

[4-03]=0, 1, 2, 3, or 4 is only for domestic hot water tank
with built-in electrical booster heater (EKHW*).

[4-03]=5 is only for domestic hot water tank without
electrical booster heater (EKHTS).

INFORMATION

During schedule timer operation, someone may have
altered the actual settings manually (in other words, the
"last" command was overruled manually). The icon 

p

,

indicating the schedule timer operation, may still be
displayed, giving the impression that the "last" command
settings are still active. The "next" programmed command
will overrule the altered settings and return to the original
program.

(1) Only applicable for tank with built-in electrical booster heater (EKHW*).

Содержание Altherma EBHQ-BB6V3

Страница 1: ...BB6W1 EDLQ011BB6V3 EDLQ014BB6V3 EDLQ016BB6V3 EDLQ011BB6W1 EDLQ014BB6W1 EDLQ016BB6W1 EBHQ011BB6V3 EBHQ014BB6V3 EBHQ016BB6V3 EBHQ011BB6W1 EBHQ014BB6W1 EBHQ016BB6W1 EBLQ011BB6V3 EBLQ014BB6V3 EBLQ016BB6V3 EBLQ011BB6W1 EBLQ014BB6W1 EBLQ016BB6W1 Unit and options for air to water heat pump system ...

Страница 2: ... according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenan...

Страница 3: ...out electrical booster heater EKHTS in 2 different sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermostat kit option An optional room thermostat EKRTW EKRTWA or EKRTR can be connected to the unit Refer to the operation manual of the room thermostat for more information 3 2 Sc...

Страница 4: ...his gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping 4 2 Operating the digital controller Operat...

Страница 5: ...er 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is active 15 COMPRESSOR ICON ç...

Страница 6: ...torage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set in permission level 2 or 3 refer to 5 Field settings on page 13 the quiet mode button will not be operable 35 BIVALENT FUNCTION OR EXTERNAL BACKUP HEATER ACTI...

Страница 7: ...t upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time of day when space heating demand is lowest Continuous The unit will continuously heat up the domestic water tank untill the reheat set point is reached In this case a balance with the space heating dem...

Страница 8: ...e actual temperature set point only appears on the display after pressing one of the buttons wi or wj If no button is pressed for 5 seconds the temperature set point will automatically disappear from the display again Temperature range for domestic water heating For EKHW only 30 C to 78 C For EKHTS only 30 C to 60 C 3 Press the v button to deactivate domestic water heating w Icon w disappears from...

Страница 9: ...on with a set point weather dependent or manually set Four actions can be programmed These actions are repeated daily 3 Quiet mode refer to Programming space cooling quiet mode or booster heater mode on page 11 Switch the mode on or off at a scheduled time Four actions can be programmed per mode These actions are repeated daily 4 Domestic water heating refer to Programming space heating or domesti...

Страница 10: ...t a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later INFORMATION The programmed actions are not stored according to their timing but according to the time of programming This me...

Страница 11: ...he programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For domestic water heating use the ba button to enable or disable the x action 10 Use the pi and pj button...

Страница 12: ... select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater mode 1 use the ba button to enable or disable the x action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed make sure that the display sh...

Страница 13: ...e button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the next day by means of the pi and pj buttons The selected day is blinking You can return to st...

Страница 14: ...peat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and level 2 3 is done by simultaneously pressing buttons pfi and pfj i...

Страница 15: ...i2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer outdoor temperatures i e Hi2_A colder water is required Tt Target water temperature TA Ambient outdoor temperature Shift value Shift value 2 Disinfection function Applies only to installations with a d...

Страница 16: ... hysteresis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot water user interface set point TDHW e g 55 C is reached B Scheduled reheat operation activated at 6 06 heat up domestic hot water untill domestic hot water reheat set point 6 07 e g 45 C is reach...

Страница 17: ...ing automatic storage during night default setting If it seems that the domestic hot water night storage operation is not sufficient for your needs an additional scheduled reheat during daytime can be set NOTICE The setting 4 03 shall not be modified The installer selected the proper setting for your application INFORMATION The status of this setting is only mentioned to indicate which settings an...

Страница 18: ...r to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case weather dependent set point see field setting 1 Weather dependent set point on page 14 is selected d 03 Local shift value weather dependent determines the shift value of the weather dependent set point arou...

Страница 19: ...Fri Mon Sun All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 fixed 5 C 03 Set point only in combination with domestic hot water tank with built in electrical booster heater EKHW 70 55 80 5 C 04 Interval only in combination with domestic hot water tank without electrical booster h...

Страница 20: ...stallation related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Cooling set point lower limit 5 5 18 1 C 04 Installation related setting Automatic set back function 05 Set back operation 0 OFF 0 1 1 06 Set back operation start time 23 00 0 00 23 00 1 00 hou...

Страница 21: ... Not applicable Do not change the default value E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Do not change the default value depending on model 03 Liquid refrigerant temperature Read only 1 C 04 Inlet water temperature Read only 1 C F Installation related setting 00 Installation related setting 01 Installation related setting 02 ...

Страница 22: ...void injury give the piping time to return to normal temperature or be sure to wear proper gloves Do not touch any switch with wet fingers Touching a switch with wet fingers can cause electrical shock WARNING Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrige...

Страница 23: ... shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correct...

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...4PW67905 1 01 2011 Copyright 2011 Daikin ...

Отзывы: