8 Configuration
Installer reference guide
48
EPGA11~ EA9W
Daikin Altherma – Low temperature split
4P556075-1 – 2019.02
#
Code
Description
[3.5]
[0-00]
[0-01]
[0-02]
[0-03]
Set weather-dependent heating:
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪ T
t
: Target leaving water temperature
(additional zone)
▪ T
a
: Outdoor temperature
▪ [0-03]:
Low
outdoor
ambient
temperature. –40°C~+5°C
▪ [0-02]:
High
outdoor
ambient
temperature. 10°C~25°C
▪ [0-01]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below the
low
ambient
temperature.
[9‑05]°C~[9‑06]°C
Note:
This value should be higher
than [0‑00] as for low outdoor
temperatures
warmer
water
is
required.
▪ [0-00]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above the
high
ambient
temperature.
[9‑05]~min(45, [9‑06])°C
Note:
This value should be lower than
[0‑01]
as
for
high
outdoor
temperatures less warm water is
required.
Cooling WD curve
Set weather-dependent cooling for the main zone (if [3.4] = 2):
#
Code
Description
[3.6]
[0-04]
[0-05]
[0-06]
[0-07]
Set weather-dependent cooling:
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪ T
t
: Target leaving water temperature
(additional zone)
▪ T
a
: Outdoor temperature
▪ [0-07]:
Low
outdoor
ambient
temperature. 10°C~25°C
▪ [0-06]:
High
outdoor
ambient
temperature. 25°C~43°C
▪ [0-05]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below the
low
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be higher
than [0‑04] as for low outdoor
temperatures less cold water is
required.
▪ [0-04]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above the
high
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be lower than
[0‑05]
as
for
high
outdoor
temperatures colder water is required.
Emitter type
For more info about this functionality, see
.
#
Code
Description
[3.7]
[2‑0D]
Emitter type
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:
Emitter type
Additional zone
Space heating
setpoint range
[9‑05]~[9‑06]
Target delta T in
heating [1‑0C]
0: Underfloor heating Maximum 55°C
Variable (see [2.B])
1: Fancoil unit
Maximum 55°C
Variable (see [2.B])
2: Radiator
Maximum 65°C
Fixed 8°C
Setpoint range
For more information about this setting, also see
.
#
Code
Description
Leaving water temperature range for the additional leaving water
temperature zone (= the leaving water temperature zone with the
highest leaving water temperature in heating operation and the
lowest leaving water temperature in cooling operation)
[3.8.1]
[9-05]
Heating minimum: 15°C~37°C