4 Installation
Installation manual
8
EAVH/9W
Daikin Altherma – Low temperature split
4P556067-1 – 2018.10
NOTICE
Overpressure bypass valve
(delivered as accessory). We
recommend to install the overpressure bypass valve in the
space heating water circuit.
▪ Mind the minimum water volume when choosing the
installation location of the overpressure bypass valve
(at the indoor unit, or at the collector). See
"3.2.1 To
check the water volume and flow rate" on page 4
.
▪ Mind the minimum flow rate when adjusting the
overpressure bypass valve setting. See
"3.2.1 To
check the water volume and flow rate" on page 4
and
"6.2.1 To check the minimum flow rate" on page 20
.
NOTICE
Install air purge valves at all local high points.
NOTICE
A pressure relief valve (field supply) with an opening
pressure of maximum 10 bar must be installed on the
domestic cold water inlet connection in accordance with
the applicable legislation.
4.3.2
To connect the recirculation piping
Prerequisite:
Only required if you need recirculation in your system.
1
Remove the top panel from the unit, see
"4.1.1 To open the
indoor unit" on page 5
.
2
Cut out the rubber grommet on top of the unit, and remove the
stop. The recirculation connector is placed below the hole.
3
Route the recirculation piping through the grommet and connect
it to the recirculation connector.
4
Reattach the top panel.
4.3.3
To fill the water circuit
To fill the water circuit, use a field supply filling kit. Make sure you
comply with the applicable legislation.
INFORMATION
Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.
4.3.4
To protect the water circuit against
freezing
About freeze protection
Frost can damage the system. To prevent the hydraulic components
from freezing, the software is equipped with special frost protection
functions such as water pipe freeze prevention and drain prevention
(see installer reference guide) that include the activation of pump in
case of low temperatures.
However, in case of a power failure, these functions cannot
guarantee protection.
Do one of the following to protect the water circuit against freezing:
▪ Add glycol to the water. Glycol lowers the freezing point of the
water.
▪ Install freeze protection valves. Freeze protection valves drain the
water from the system before it can freeze.
NOTICE
If you add glycol to the water, do NOT install freeze
protection valves.
Possible consequence:
Glycol leaking
out of the freeze protection valves.
Freeze protection by glycol
Adding glycol to the water lowers the freezing point of the water.
The required concentration depends on the lowest expected outdoor
temperature, and on whether you want to protect the system from
bursting or from freezing. To prevent the system from freezing, more
glycol is required. Add glycol according to the table below.
INFORMATION
▪ Protection against bursting: the glycol will prevent the
piping from bursting, but NOT the liquid inside the
piping from freezing.
▪ Protection against freezing: the glycol will prevent the
liquid inside the piping from freezing.
Lowest expected
outdoor
temperature
Prevent from
bursting
Prevent from
freezing
–5°C
10%
15%
–10°C
15%
25%
–15°C
20%
35%
–20°C
25%
—
–25°C
30%
—
NOTICE
▪ The required concentration might differ depending on
the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the glycol manufacturer. If necessary, meet the
requirements set by the glycol manufacturer.
▪ The added concentration of glycol should NEVER
exceed 35%.
▪ If the liquid in the system is frozen, the pump will NOT
be able to start. Mind that if you only prevent the
system from bursting, the liquid inside might still freeze.
▪ When water is at standstill inside the system, the
system is very likely to freeze and get damaged.
The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:
If…
Then…
The system contains a domestic
hot water tank
Only use propylene glycol
(a)
The system does NOT contain a
domestic hot water tank
You can use either propylene
glycol
(a)
or ethylene glycol
(a)
Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.
WARNING
Ethylene glycol is toxic.
Содержание Altherma EAVH16S18DA6V
Страница 26: ......
Страница 27: ......
Страница 28: ...4P556067 1 2018 10 Copyright 2018 Daikin 4P556067 1 0000000R ...