Installation manual

Daikin Altherma 3 WS

English

Installation manual

Daikin Altherma 3 WS

EWSAH06UD▲9W▼
EWSAX06UD▲9W▼

▲= 1, 2, 3, …, 9, A, B, C, …, Z
▼= , , 1, 2, 3, …, 9

Содержание Altherma 3 WS EWSAH06UD Series

Страница 1: ...Installation manual Daikin Altherma 3 WS English Installation manual Daikin Altherma 3 WS EWSAH06UD 9W EWSAX06UD 9W 1 2 3 9 A B C Z 1 2 3 9...

Страница 2: ...onnect the power consumption digital inputs 23 6 13 To connect the safety thermostat normally closed contact 23 6 14 To connect the brine low pressure switch 24 6 15 To connect the thermostat for pass...

Страница 3: ...rs and service technicians that allows you to register configure and troubleshoot heating systems The mobile app can be downloaded for iOS and Android devices using the QR codes below Registration to...

Страница 4: ...ured on site and all electrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables WARNING If the supply cord is damaged it MUST be rep...

Страница 5: ...e 4 2 2 To remove the hydro module from the unit 47 It is recommended to use lifting straps to carry the unit up or down staircases 3 2 Domestic hot water tank kit 3 2 1 To remove the accessories from...

Страница 6: ...the following requirements and precautions WARNING Do NOT pierce or burn refrigerant cycle parts Be aware that the refrigerant inside the system is odourless WARNING The appliance shall be stored so...

Страница 7: ...n power supply 416 3 T25 5 Open the installer switch box as follows 2 T25 6 In case you have to install additional options that require access to the main switch box remove the main switch box cover a...

Страница 8: ...hydro module to the main switch box or other locations Route the wires through the grommets of the upper hydro module cover X22Y X11YB X803YA X1YA 7 Remove the upper hydro module cover You can lift up...

Страница 9: ...s as described in 4 2 2 To remove the hydro module from the unit 47 4 2 3 To close the indoor unit 1 If applicable reinstall the left side panel 2 If applicable reinsert the hydro module 3 If applicab...

Страница 10: ...safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded see 5 3 2 To connect the water piping for domestic hot water 413 The minimum fluid pressure to operate is 1 bar 0 1...

Страница 11: ...it WARNING Before during and after filling carefully check the central water loop circuit for leakage INFORMATION The materials used in the central water loop circuit of the unit are chemically resist...

Страница 12: ...ion in accordance with the applicable legislation NOTICE A drain device and pressure relief device must be installed on the cold water inlet connection of the domestic hot water cylinder To avoid back...

Страница 13: ...elief valve combination to the water mains inlet 7 Install the tundish part of the kit in a vertical position within a maximum of 600 mm away from the pressure reducing valve pressure relief valve com...

Страница 14: ...ommet on top of the unit and remove the stop The recirculation connector is located below the space heating cooling water outlet pipe 3 Route the recirculation piping through the grommet and connect i...

Страница 15: ...Selection and sizing of the wiring should be done in accordance with the applicable legislation based on the information mentioned in the table below Make sure that a separate power supply circuit is...

Страница 16: ...anual of the remote indoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 2 External sensor Room 1 7 Room sensor offset Current sensors See the installation manual of the current se...

Страница 17: ...en the unit a 6 Dual cable power supply split power supply Preferential kWh rate power supply with separate normal kWh rate power supply b C1 C2 C3 X5M Z1F X2M C5 C1 Normal kWh rate power supply for t...

Страница 18: ...Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB The voltage free contact shall ensure the minimum applicable load of 15 V DC 10 mA Connect the preferential kWh ra...

Страница 19: ...gs if remote outdoor sensor cannot be installed correctly NOTICE It is recommended to ALWAYS install and connect the ambient sensor If this is not possible and you do NOT connect the sensor to the uni...

Страница 20: ...X5M 3 1 Open the following see 4 2 1 To open the indoor unit 46 1 Top panel 1 3 2 2 User interface panel 3 Installer switch box cover 2 Connect the electricity meters cable to the appropriate terminal...

Страница 21: ...to the appropriate terminals as shown in the illustration below Make sure to put wires 2 and 3 between the installer switch box and main switch box in a cable sleeve field supply so that they are dou...

Страница 22: ...taller switch box and main switch box a Installation of EKRP1HBAA is required b Cable sleeve field supply 1 2 2 1 1 b a X2M 14a 21 L N YC Y2 1 2 3 1 1 b 3 Fix the cable with cable ties to the cable ti...

Страница 23: ...nel 4 Main switch box cover 2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below 1 2 3 4 5 S6S S7S S8S S9S 1 2 1 2 3 4 5 a a Installatio...

Страница 24: ...ow pressure switch Depending on the applicable legislation you might have to install a brine low pressure switch field supply NOTICE Mechanical We recommend to use a mechanical brine low pressure swit...

Страница 25: ...on LED flashing communication problem LD4 Indication of Smart Grid activity LED ON Smart Grid functionality of the indoor unit is controlled by the LAN adapter LED OFF system operating in normal opera...

Страница 26: ...ore information see 6 16 5 Solar inverter energy management system 427 6 16 3 Router Make sure the LAN adapter can be connected via a LAN connection The minimum category for the Ethernet cable is Cat5...

Страница 27: ...y of the cable The positive wire MUST be connected to X2A 1 the negative wire to X2A 2 WARNING Make sure to connect the electricity meter in the correct direction so that it measures the total energy...

Страница 28: ...wire is fully inserted into the terminal bare copper wire CANNOT be visible 1 3 2 1 Open the following see 4 2 1 To open the indoor unit 46 1 Top panel 3 1 2 4 2 User interface panel 3 Front panel 4...

Страница 29: ...r Advanced user pin code The Advanced user pin code is 1234 Additional menu items for the user are now visible 1234 Advanced user User pin code The User pin code is 0000 0000 User To access the instal...

Страница 30: ...as an emergency heater It then takes over the heat load either automatically or by manual interaction When Emergency is set to Automatic and a heat pump failure occurs the backup heater automatically...

Страница 31: ...n 9 3 1 E 03 4 9W Voltage Depending on how the backup heater is connected to the grid and what voltage is supplied the correct value needs to be set In either configuration the backup heater will oper...

Страница 32: ...onfiguration wizard Additional zone The most important settings for the additional leaving water zone can be set here Emitter type For more info about this functionality see 7 2 5 Configuration wizard...

Страница 33: ...inus the reheat hysteresis temperature the tank heats up to the reheat temperature Code Description 5 A 6 08 Reheat hysteresis 2 C 20 C 7 3 Weather dependent curve 7 3 1 What is a weather dependent cu...

Страница 34: ...ter temperature for all ambient temperatures Examples Weather dependent curve when slope is selected X1 X2 c d e Y1 Y2 Y3 Y4 a b Weather dependent curve when offset is selected Y1 Y2 Y3 Y4 X1 X2 a b c...

Страница 35: ...egular outdoor temperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fine tune the weather dependent curve 2 points curve The foll...

Страница 36: ...f the central water loop fluid carefully Code Description 9 M A 04 Water loop freezing temperature 0 2 C 1 2 C 2 4 C 3 6 C 4 9 C 5 12 C 6 15 C 7 18 C NOTICE The Water loop freezing temperature setting...

Страница 37: ...t 1 Limit 2 Limit 3 Limit 4 Priority heater Current sensor offset BBR16 activation BBR16 power limit 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sen...

Страница 38: ...he indoor unit and the room thermostat if applicable The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to t...

Страница 39: ...mple when you select Pump a test run of the pump will start Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permis...

Страница 40: ...a year However applicable legislation might require shorter maintenance intervals NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is ind...

Страница 41: ...2 To connect the drain hose to the drain 410 Fluid pressure Check whether the fluid pressure is above 1 bar If it is lower add fluid Pressure relief valve Open the valve CAUTION Discharge may be very...

Страница 42: ...e a drain hose and a pump to drain the tank via the access point 2 1 4 Tightening torques for installation Item Tightening torque Tube connection 30 N m Temperature and pressure relief valve 40 N m 10...

Страница 43: ...ater side D Field supplied E Field installed delivered with the unit F DHW tank a1 Space heating water IN 22 mm a2 Space heating water OUT 22 mm b1 Domestic hot water cold water IN 22 mm b2 Domestic h...

Страница 44: ...0 V 6 9 kW 3N 400 V 6 9 kW User installed options User installed options Remote user interface Remote user interface Human Comfort Interface Ext indoor thermistor External indoor thermistor Digital I...

Страница 45: ...for combined 3F backup heater compressor power supply 6 9 kW English Translation Only for dual cable power supply Only for dual cable power supply Only for single cable power supply Only for single c...

Страница 46: ...ired On OFF thermostat Only for wireless On OFF thermostat Only for wireless On OFF thermostat 9 Current sensors 9 Current sensors SWB Switch box 10 Brine pressure loss detection 10 Brine pressure los...

Страница 47: ...ial kWh rate unit power supply installation Only with EKGSPOWCAB Compressor power supply 230 V earth Only with EKGSPOWCAB POWER SUPPLY FIELD SUPPLY OPTIONAL PART Only for EKCSENS INDOOR UNIT STANDARD...

Страница 48: ...re parts Contact your local Daikin dealer Installed by name address tel No completion date TECHNICAL SPECIFICATIONS EN12897 2016 Maximum water supply pressure to pressure reducing valve 16 bar Operati...

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ...4P675760 1C 2023 02 Copyright 2021 Daikin 4P675760 1 C 00000003 Verantwortung f r Energie und Umwelt...