3 About the box
Installation manual
5
23EA
Daikin Altherma 3 R F
4P629088-1C – 2021.11
Piping installation (see
WARNING
Field piping method MUST be in accordance with the
instructions
from
this
manual.
See
12].
WARNING
The discharge pipes from the pressure relief valves MUST
terminate in a safe and visible position without forming any
risk to persons in the vicinity.
WARNING
▪ Discharge piping, tundish, drain valves, etc. MUST be
positioned away from any electrical components.
▪ The discharge pipe away from the tundish MUST
terminate in a safe, visible position without forming any
risk to persons in the vicinity.
WARNING
▪ Do NOT install any valves between the domestic hot
water tank and relief valves/expansion vessel.
▪ Do NOT install shut-off valves between the expansion
relief valve and the domestic hot water tank.
16])
DANGER: RISK OF ELECTROCUTION
WARNING
Electrical wiring connection method MUST be in
accordance with the instructions from this manual. See
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
WARNING
Make sure that the electrical wiring does NOT touch the
refrigerant gas pipe, which can be very hot.
a
a
Refrigerant gas pipe
WARNING
The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, ALWAYS
connect the backup heater power supply and the earth
cable.
Commissioning (see
WARNING
Commissioning method MUST be in accordance with the
instructions
from
this
manual.
See
WARNING
Air purging heat emitters or collectors.
Before you
purge air from heat emitters or collectors, check if
or
is displayed on the home screen of the user interface.
▪ If not, you can purge air immediately.
▪ If yes, make sure that the room where you want to
purge air is sufficiently ventilated.
Reason:
Refrigerant
might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.
Maintenance and service (see
CAUTION
Water coming out of the valve may be very hot.
WARNING
If the internal wiring is damaged, it has to be replaced by
the manufacturer, its service agent or similarly qualified
persons.
DANGER: RISK OF BURNING/SCALDING
The water in the tank can be very hot.
CAUTION
Make sure to open the valve (if equipped) towards the
expansion vessel, otherwise the overpressure will be
generated.
3
About the box
INFORMATION
This unit is a heating only model. Therefore, all references
to cooling in this document are NOT applicable.
3.1
Indoor unit
▪ At delivery, the unit MUST be checked for damage. Any damage
MUST be reported immediately to the claims agent of the carrier.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
▪ Unpack the indoor unit completely according to the instructions
mentioned on the unpacking instructions sheet.