background image

4 Piping installation

Installation manual

8

EPRA14~W1

Daikin Altherma 3 H HT

4P586100-1 – 2019.07

1

1

2

3

3

1

1

2

3

4

3.4

To remove the transportation stay

NOTICE

If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.

The  transportation  stays  (2×)  protect  the  unit  during  transport.
During installation they must be removed.

a

a

Transportation stays (2×)

1

Open  the  switch  box  cover.  See 

"3.3  To  open  the  outdoor

unit" on page 7

.

2

Remove the screws (4×) from the transportation stays.

3

Remove the transportation stays (2×), and dispose of them.

4

Reattach the screws to the unit.

4

Piping installation

4.1

Connecting the water piping

4.1.1

To connect the water piping

1

Connect the shut-off valve (with integrated filter) to the outdoor
unit water inlet, using thread sealant.

c

a

b

b

d

1

2

a

Water OUT (screw connection, male, 1")

b

Water IN (screw connection, male, 1")

c

Shut-off valve with integrated filter (delivered as accessory)

d

Thread sealant

2

Connect the field piping to the shut-off valve.

3

Connect the field piping to the outdoor unit water outlet.

NOTICE

About  the  shut-off  valve  with  integrated  filter  (delivered  as
accessory):

▪ The  installation  of  the  valve  at  the  water  inlet  is

mandatory.

▪ Mind the flow direction of the valve.

NOTICE

Install air purge valves at all local high points.

4.1.2

To fill the water circuit

See  the  installation  manual  of  the  indoor  unit,  or  the  installer
reference guide.

4.1.3

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see the installer reference guide) that include the activation of pump
in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water from the system before it can freeze.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

Adding glycol to the water lowers the freezing point of the water.

The required concentration depends on the lowest expected outdoor
temperature,  and  on  whether  you  want  to  protect  the  system  from
bursting or from freezing. To prevent the system from freezing, more
glycol is required. Add glycol according to the table below.

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

Содержание Altherma 3 H HT

Страница 1: ...Installation manual Daikin Altherma 3 H HT English Installation manual Daikin Altherma 3 H HT EPRA14DAV3 EPRA16DAV3 EPRA18DAV3 EPRA14DAW1 EPRA16DAW1 EPRA18DAW1 ...

Страница 2: ...all height unrestricted 1000 X X H 150 H 500 500 300 500 500 300 300 1000 500 1000 500 500 1000 500 1000 500 1000 300 X X H X X H General mm 3D124412 300 150 100 Top side obstacle No top side obstacle 1 ...

Страница 3: ...m в соответствии с положениями 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen määräyksiä za dodržení ustanovení předpisu prema odredbama követi a z zgodnie z postanowieniami Dyrektyw în urma prevederilor 19 20 21 22 23 24 25 ob upoštevanju določb vastavalt nõuetele следвайки клаузите на laikantis nuostatų pateikiamų...

Страница 4: ...uurin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpo...

Страница 5: ... 1 1 About this document Target audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the box of the indoor unit Operation manual Quick guide for basic usage Format Paper in the box of the indoor unit User reference guide Detailed ...

Страница 6: ...s and precautions WARNING Do NOT pierce or burn Do NOT use means to accelerate the defrosting process or to clean the equipment other than those recommended by the manufacturer Be aware that R32 refrigerant does NOT contain an odour WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources example open fla...

Страница 7: ...Insulate the drain hose Install a drain tube heater field supply To connect the drain tube heater see 5 3 To connect the electrical wiring on the outdoor unit on page 11 NOTICE Provide at least 150 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the expected level of snow Use the drain plug with O ring and a hose for drainage 1 2 a b c c 3 d a Dr...

Страница 8: ... or the installer reference guide 4 1 3 To protect the water circuit against freezing About freeze protection Frost can damage the system To prevent the hydraulic components from freezing the software is equipped with special frost protection functions such as water pipe freeze prevention and drain prevention see the installer reference guide that include the activation of pump in case of low temp...

Страница 9: ...he oxidation of glycols no automotive glycol is used because their corrosion inhibitors have a limited lifetime and contain silicates which can foul or plug the system galvanized pipes are NOT used in glycol systems since the presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor Adding glycol to the water circuit reduces the maximum allowed water volume o...

Страница 10: ...the liquid inside the piping from freezing Protection against freezing the glycol will prevent the liquid inside the piping from freezing NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from the table above with the specifications provided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer The ...

Страница 11: ... mm 5 1 About electrical compliance Only for EPRA14 18DAV3 Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase 5 2 Guidelines when connecting the electrical wiring Tightening torques Item Tightening torque N m M4 X1M X2M ...

Страница 12: ... 5 mm 1 2 3 1 2 3 3 Optional Drain tube heater cable Make sure the heating element of the drain tube heater is completely inside the drain tube Route the cable through the frame Connect the wires to the terminal block and the earth screw Fix the cable with cable ties Wires 2 GND 0 75 mm Wiring must be double insulated Maximum power allowed for drain tube heater 115 W 0 5 A L N PE 1 2 4 Optional Po...

Страница 13: ...se field supply Recommended fuse 4 pole 16 A or 20 A fuse C curve Q1DI Earth leakage circuit breaker 30 mA field supply 2 Interconnection cable indoor outdoor Route the cable through the frame Connect the wires to the terminal block make sure the numbers match with the numbers on the indoor unit and the earth screw Fix the cable with a cable tie Wires 3 GND 1 5 mm 1 2 3 1 2 3 3 Optional Drain tube...

Страница 14: ...peratures Required accessory delivered with the unit Thermistor fixture 1 2 3 Click 4 5 6 7 6 Finishing the outdoor unit installation 6 1 To close the outdoor unit NOTICE When closing the outdoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 1 1 2 3 2 4 4 3 3 3 1 6 2 To install the discharge grille Install the lower part of the discharge grille 1 Insert the hooks 2 Insert...

Страница 15: ...ball studs 8 7 9 Fix the 6 remaining screws 9 6 6 3 To remove the discharge grille and put the grille in safety position WARNING Rotating fan Before powering ON or servicing the outdoor unit make sure that the discharge grille covers the fan as protection against a rotating fan See 6 2 To install the discharge grille on page 14 6 3 To remove the discharge grille and put the grille in safety positi...

Страница 16: ...he cables and the outdoor unit to prevent the cables from scratching the paint field supply 4 Attach the ends of the cables and tighten them NOTICE Discharge grille Do NOT use too much force to prevent damage to the discharge grille 7 Starting up the outdoor unit See the indoor unit installation manual for configuration and commissioning of the system WARNING Rotating fan Before powering ON or ser...

Страница 17: ... k Air heat exchanger l PCB cooling m Accumulator n Muffler Refrigerant flow Heating Cooling E1HC Crankcase heater E1HHEX Plate heat exchanger heater M1C Compressor M1F Fan motor PRV Refrigerant pressure relief valve S1PH High pressure switch 5 6 MPa S2PH High pressure switch 4 17 MPa S1PL Low pressure switch S1NPH High pressure sensor Y1E Electronic expansion valve main Y3E Electronic expansion v...

Страница 18: ...ted circuit board ACS A5P Printed circuit board flash BS1 BS4 A1P Push button switch C1 C4 A1P A2P Capacitor DS1 A1P DIP switch E1H Drain tube heater field supply E1HC Crankcase heater E1HHEX E3HHEX Plate heat exchanger heaters F1U Field fuse field supply F1U F4U A2P Fuse F6U A1P Fuse T 5 0 A 250 V H1P H7P A1P Light emitting diode service monitor is orange HAP A1P Light emitting diode service moni...

Страница 19: ...X K2R A1P Magnetic relay Y2S K2R A4P Magnetic relay E1H K3R A1P Magnetic relay Y3S K4R A1P Magnetic relay E1HC K2M K11M A2P Magnetic contactor L1R L4R Reactor M1C Compressor motor M1F Fan motor PS A2P Switching power supply Q1DI Earth leakage circuit breaker 30 mA field supply R1 R2 A2P Resistor R1T Thermistor outdoor air R2T Thermistor compressor discharge R3T Thermistor compressor suction R4T Th...

Страница 20: ...4P586100 1 2019 07 Copyright 2019 Daikin 4P586100 1 0000000I ...

Отзывы: