7 Commissioning

Installation manual

27

ETBH/9W
Daikin Altherma 3 H HT W
4P586453-1B – 2020.01

7

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during the commissioning
and hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  must  remain  open  after
commissioning.

INFORMATION

Protective  functions  –  "Installer-on-site  mode"

.  The

software  is  equipped  with  protective  functions,  such  as
room antifrost. The unit automatically runs these functions
when necessary.

During  installation  or  service  this  behaviour  is  undesired.
Therefore, the protective functions can be disabled:

At  first  power-on:

  The  protective  functions  are

disabled by default. After 12 h they will be automatically
enabled.

Afterwards:

  An  installer  can  manually  disable  the

protective  functions  by  setting  [9.G]: 

Disable

protections

=

Yes

.  After  his  work  is  done,  he  can

enable  the  protective  functions  by  setting  [9.G]:

Disable protections

=

No

.

7.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The following 

field wiring

 has been carried out according

to this document and the applicable legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between indoor unit and outdoor unit

▪ Between the local supply panel and the indoor unit

▪ Between the indoor unit and the valves (if applicable)

▪ Between  the  indoor  unit  and  the  room  thermostat  (if

applicable)

▪ Between  the  indoor  unit  and  the  domestic  hot  water

tank (if applicable)

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

Backup  heater  circuit  breaker

  F1B  (field  supply)  is

turned ON.

Only for tanks with built-in booster heater:

Booster  heater  circuit  breaker

  F2B  (field  supply)  is

turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There is NO 

water leak

 inside the indoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

automatic air purge

 valves are open.

The 

pressure  relief  valve

  purges  water  when  opened.

Clean water must come out.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions. See "To check the water volume and flow rate"
in 

"4.1 Preparing water piping" 

[

4

 6].

(if  applicable)  The 

domestic  hot  water  tank

  is  filled

completely.

7.2

Checklist during commissioning

The 

minimum  flow  rate

  during  backup  heater/defrost

operation  is  guaranteed  in  all  conditions.  See  "To  check
the  water  volume  and  flow  rate"  in 

"4.1  Preparing  water

piping" 

[

4

 6].

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

Содержание Altherma 3 H HT W

Страница 1: ...Installation manual Daikin Altherma 3 H HT W English Installation manual Daikin Altherma 3 H HT W ETBH16DA6V ETBH16DA9W ETBX16DA6V ETBX16DA9W https daikintechnicaldatahub eu ...

Страница 2: ...sou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących...

Страница 3: ... Additional zone 21 6 2 7 Configuration wizard Tank 22 6 3 Weather dependent curve 22 6 3 1 What is a weather dependent curve 22 6 3 2 2 points curve 23 6 3 3 Slope offset curve 23 6 3 4 Using weather dependent curves 24 6 4 Settings menu 24 6 4 1 Main zone 24 6 4 2 Additional zone 25 6 4 3 Information 25 6 5 Menu structure Overview installer settings 26 7 Commissioning 27 7 1 Checklist before com...

Страница 4: ...e g 1 h a General safety precautions b Addendum book for optional equipment c Indoor unit installation manual d Operation manual e Sealing ring for shut off valve f Shut off valve g Overpressure bypass valve h Wall bracket 3 Unit installation 3 1 Preparing the installation site WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an op...

Страница 5: ... box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user interface panel NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 3 1 2 3 2 2 To close the indoor unit 1 Reinstall th...

Страница 6: ...pen the switch box See 3 2 1 To open the indoor unit 45 Fix the unit to the wall with an Ø8 mm screw 3 3 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Connect a drain tube field supply to the drain pan connector as follows a a Drain p...

Страница 7: ...hanger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performance data for third party tanks CANNOT be provided and performance CANNOT be guaranteed NOTICE Configuration Configuration of a third party tank depends on the size of the heat exchanger coil of the tank For more information see the installer reference guide 4 2 Connecting water piping 4 2 1 To c...

Страница 8: ...the glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been exposed to air Leaving the cap off the glycol container causes the concentration of water to increase The glycol concentration is then lower than assumed As a result the hydraulic components might freeze up after all Take preventive actions to ensure a minimal exposure of the...

Страница 9: ...g service CAUTION Do NOT push or place redundant cable length in the unit NOTICE The distance between the high voltage and low voltage cables should be at least 50 mm 5 1 About electrical compliance Only for the backup heater of the indoor unit See 5 3 2 To connect the backup heater power supply 412 5 2 Guidelines when connecting the electrical wiring Tightening torques Indoor unit Item Tightening...

Страница 10: ...ent Wires 2 0 75 1 25 mm Maximum length 500 m 2 9 Control 1 6 Room sensor offset Item Description in case of DHW tank 3 way valve See Installation manual of the 3 way valve Addendum book for optional equipment Wires 3 0 75 mm Maximum running current 100 mA 9 2 Domestic hot water in case of DHW tank Domestic hot water tank thermistor See Installation manual of the domestic hot water tank Addendum b...

Страница 11: ...ank Power consumption control settings On the user interface make sure to set 9 9 1 1 Power consumption control Continuous 9 9 2 1 Type kW 5 3 1 To connect the main power supply 1 Open the following see 3 2 1 To open the indoor unit 45 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the main power supply In case of normal kWh rate power supply Interconnection cable main power supply ...

Страница 12: ...ble legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the backup heater capacity as listed in the table below Backup heater type Backup heater capacity Power supply Maximum running current Zmax 6...

Страница 13: ...ly SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 5 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor heating and heat pump convectors install a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation For more...

Страница 14: ... illustration below B C A A 6 5 4 3 S3S S2S C B 5 6 3 4 X5M X5M 3 Fix the cable with cable ties to the cable tie mountings 5 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open the following see 3 2 1 To open the indoor unit 45 1 Front panel 1 2 3 2 Switch box cover 3 Switch box...

Страница 15: ...pen the indoor unit 45 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required B C A A 7 Y2 B X2M C X2M A4P X1M a 7 9 Y2 YC A4P a Installation of EKRP1...

Страница 16: ...er consumption digital inputs cable to the appropriate terminals as shown in the illustration below B C A A 1 2 4 5 S6S S7S S8S S9S 3 C B A8P X801M a 5 4 3 2 1 a Installation of EKRP1AHTA is required 3 Fix the cable with cable ties to the cable tie mountings 5 3 10 To connect the safety thermostat normally closed contact Wires 2 0 75 mm Maximum length 50 m Safety thermostat contact 16 V DC detecti...

Страница 17: ...rk as expected The configuration influences the following The calculations of the software What you can see on and do with the user interface How You can configure the system via the user interface First time Configuration wizard When you turn ON the user interface for the first time via the indoor unit the configuration wizard starts to help you configure the system Restart the configuration wiza...

Страница 18: ...ng the dial 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0 1 2 3 4 Turn the left dial to select the second part of the setting 00 01 15 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 5 Turn the right dial to modify the value from 15 to 20 00 01 20 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 6 Press the left dial to confirm the new setting 7 Press the center button to go back to the home screen INFORMATION ...

Страница 19: ...cy is set to Automatic and a heat pump failure occurs the backup heater automatically takes over the heat load and the booster heater in the optional tank takes over the domestic hot water production When Emergency is set to Manual and a heat pump failure occurs the domestic hot water heating and space heating stops To manually recover it via the user interface go to the Malfunctioning main menu s...

Страница 20: ...r you can set the exact heater capacity and this will lead to more accurate energy data Code Description 9 4 1 6 02 Booster heater capacity kW Only applies to domestic hot water tank with an internal booster heater The capacity of the booster heater at nominal voltage Range 0 10 kW 6 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electri...

Страница 21: ...ulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling demand of the room External room thermostat Unit operation is decided by the external thermostat or equivalent e g heat pump ...

Страница 22: ...ing Tank Heat up mode Reheat only Comfort setpoint Only applicable when domestic hot water preparation is Schedule only or Schedule reheat When programming the schedule you can make use of the comfort setpoint as a preset value When you later want to change the storage setpoint you only have to do it in one place The tank will heat up until the storage comfort temperature has been reached It is th...

Страница 23: ...Y2 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water tank Possible actions on this screen Go through the temperatures Change the temperature Go to the next temperature Confirm changes and proceed 6 3 3 Slope offset curve Slope and offset Define the weather dependent c...

Страница 24: ...al zone WD curve type 5 E Tank WD curve type To change the weather dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Zone Go to Additional zone Heating 3 5 Additional zone Heating WD curve Additional zone Cooling 3 6 Additional zone Cooling WD curve Tank 5 C Tank WD curve INFORMATION Maximum and minimum setpoints You cannot...

Страница 25: ...2 contacts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 6 4 2 Additional zone Thermostat type Only applicable in external room thermostat control For more info about the functionality see 6 4 1 Main zone 424 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 6 4 3 Information Dealer information T...

Страница 26: ... meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installer settings Configuration wizard Domestic hot water Backup heater Booster heater Eme...

Страница 27: ...ounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor unit and the room thermostat if applic...

Страница 28: ...d tank temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 7 2 4 To perform an actuator test run Conditions Make sure all operation is disabled Go to C Operation and turn ...

Страница 29: ...esult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 8 Hand over to the user Once the test run is finished and the unit operates properly please make sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings M...

Страница 30: ...ing diagram Indoor unit 3D120613A R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut off valve male female 1 f Magnetic filter dirt separator g Safety valve h Air purge i Drain valve j Backup heater k Loose nut 1 B1L Flow sensor B1PW Space heating water pressure sensor R1T Thermis...

Страница 31: ...rmostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch b...

Страница 32: ... V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electricity meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermost...

Страница 33: ...ation signal 2 core signal 2 core signal 2 core signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H...

Страница 34: ......

Страница 35: ......

Страница 36: ...4P586453 1B 2020 01 Copyright 2019 Daikin 4P586453 1 B 00000002 Verantwortung für Energie und Umwelt ...

Отзывы: