background image

10 Maintenance and service

Installation manual

35

ETV23EA6V
Daikin Altherma 3 H HT F
4P644729-1 – 2021.02

10

Maintenance and service

NOTICE

General  maintenance/inspection  checklist.

  Next  to  the

maintenance  instructions  in  this  chapter,  a  general
maintenance/inspection  checklist  is  also  available  on  the
Daikin Business Portal (authentication required).

The 

general 

maintenance/inspection 

checklist 

is

complementary  to  the  instructions  in  this  chapter  and  can
be  used  as  a  guideline  and  reporting  template  during
maintenance.

NOTICE

Maintenance  MUST  be  done  by  an  authorized  installer  or
service agent.

We  recommend  performing  maintenance  at  least  once  a
year. However, applicable legislation might require shorter
maintenance intervals.

10.1

Overview: Maintenance and
service

This chapter contains information about:

▪ The yearly maintenance of the outdoor unit

▪ The yearly maintenance of the indoor unit

10.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

NOTICE: Risk of electrostatic discharge

Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.

10.3

Checklist for yearly maintenance of
the indoor unit

Check the following at least once a year:

▪ Water pressure

▪ Magnetic filter/dirt separator

▪ Water pressure relief valve

▪ Relief valve hose

▪ Pressure relief valve of the domestic hot water tank

▪ Switch box

▪ Descaling

▪ Chemical disinfection

▪ Temperature and pressure relief valve

Water pressure

Keep water pressure above 1 bar. If it is lower, add water.

Magnetic filter/dirt separator

b

a

c

d

a

Screw connection

b

Magnetic sleeve

c

Drain valve

d

Drain cap

The yearly maintenance of the magnetic filter/dirt separator consists
of:

▪ Checking if both parts of the magnetic filter/dirt separator are

still screwed tight (a).

▪ Emptying the dirt separator as follows:

1

Take off the magnetic sleeve (b).

2

Unscrew the drain cap (d).

3

Connect a drain hose to the bottom of the water filter so that the
water  and  dirt  can  be  collected  in  a  suitable  container  (bottle,
sink...).

4

Open the drain valve for a couple of seconds (c).

Result: 

Water and dirt will come out.

5

Close the drain valve.

6

Screw the drain cap back on.

7

Reattach the magnetic sleeve.

8

Check the pressure of the water circuit. If required, add water.

NOTICE

▪ When  checking  the  magnetic  filter/dirt  separator  for

tightness,  hold  it  firmly,  so  as  NOT  to  apply  stress  to
the water piping.

▪ Do  NOT  isolate  the  magnetic  filter/dirt  separator  by

closing  the  shut‑off  valves.  To  properly  empty  the  dirt
separator, sufficient pressure is required.

▪ To  prevent  dirt  from  remaining  in  the  dirt  separator,

ALWAYS take off the magnetic sleeve.

▪ ALWAYS  first  unscrew  the  drain  cap,  and  connect  a

drain  hose  to  the  bottom  of  the  water  filter,  then  open
the drain valve.

INFORMATION

For  yearly  maintenance,  you  do  not  have  to  remove  the
water  filter  from  the  unit  to  clean  it.  But  in  case  of  trouble
with  the  water  filter,  you  might  have  to  remove  it  so  that
you  can  thoroughly  clean  it.  Then  you  need  to  do  as
follows:

"10.6.1 To remove the water filter"

 [

4

 37]

"10.6.2  To  clean  the  water  filter  in  case  of
trouble"

 [

4

 38]

"10.6.3 To install the water filter"

 [

4

 38]

Water pressure relief valve

Open the valve and check if it operates correctly. 

The water may be

very hot!

Checkpoints are:

▪ The  water  flow  coming  from  the  relief  valve  is  high  enough,  no

blockage of the valve or in between piping is suspected.

Содержание Altherma 3 H HT F

Страница 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16SU18EA6V ETVH16SU23EA6V ...

Страница 2: ...užívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących norm ...

Страница 3: ...connecting the electrical wiring to the indoor unit 22 7 Configuration 22 7 1 Overview Configuration 22 7 1 1 To access the most used commands 23 7 2 Configuration wizard 24 7 2 1 Configuration wizard Language 24 7 2 2 Configuration wizard Time and date 24 7 2 3 Configuration wizard System 24 7 2 4 Configuration wizard Backup heater 25 7 2 5 Configuration wizard Main zone 26 7 2 6 Configuration wi...

Страница 4: ... facilitate the installation and configuration of heating systems To access Heating Solutions Navigator registration to the Stand By Me platform is required For more information see https professional standbyme daikin eu Daikin e Care Mobile app for installers and service technicians that allows you to register configure and troubleshoot heating systems The mobile app can be downloaded for iOS and...

Страница 5: ...pplicable legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable WARNING Stripped wire Make sure that stripped wire cannot make contact with possible water on the bottom plate Maintenance and service see 10 Maintenance and service 435 WARNING If the internal wiring is damaged it has to be replaced by the manufacturer its se...

Страница 6: ...cklist for the required DHW accessories For installation compliant with section G3 of the Building Regulations you must verify that the following accessories are present Delivered with indoor unit Tundish 15 mm inlet 22 mm outlet Delivered with domestic hot water tank kit Pressure reducing valve pressure relief valve combination Adaptor 22 mm 3 4 Female BSP T piece 22 mm 22 mm 22 mm Tundish 15 mm ...

Страница 7: ...box cover d Front panel e High voltage switch box cover Open 1 Remove the top panel 5 T25 2 Remove the user interface panel Open the hinges at the top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the fro...

Страница 8: ...NOTICE When closing the indoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 46 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 48 3 Slide the indoor unit into positio...

Страница 9: ...ar Water temperature All installed piping and piping accessories valve connections MUST withstand the following temperatures INFORMATION The following illustration is an example and might NOT match your system layout 89 C 75 C 75 C M EXAM PLE Maximum temperature for piping and accessories 5 1 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the in...

Страница 10: ...ssory G3 kit EKUHWG3D to comply with UK legislation See 5 2 2 To connect the water piping for domestic hot water 410 b1 b2 a1 a2 c2 c1 a1 Space heating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from outdoor unit screw connection 1 c2 Water OUT to outdoor u...

Страница 11: ...the pipe connection located at the back of the unit This pipe starts at the pressure relief valve of the domestic hot water tank 9 Connect the 2 tundishes 1 from the pressure relief valve of the domestic hot water tank and 1 from the pressure relief valve of the domestic hot water tank kit to an appropriate drain according to the applicable legislation The following example shows discharge below f...

Страница 12: ...n valves drain the water from the system before it can freeze NOTICE If you add glycol to the water do NOT install freeze protection valves Possible consequence Glycol leaking out of the freeze protection valves Freeze protection by glycol About freeze protection by glycol Adding glycol to the water lowers the freezing point of water WARNING Ethylene glycol is toxic WARNING Due to the presence of ...

Страница 13: ...is added to the water you can use freeze protection valves to drain the water from the system before it can freeze Install freeze protection valves field supply at all lowest points of the field piping Normally closed valves located indoors near the piping entry exit points can prevent that all water from indoor piping is drained when the freeze protection valves open NOTICE When freeze protection...

Страница 14: ...y field supply see addendum book for optional equipment For more information see Installation manual of the heat pump convectors Installation manual of the heat pump convector options Addendum book for optional equipment Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Thermostat type For the additional zone 3 A Thermostat type 3 9 read only Control Item Description R...

Страница 15: ... of preferential kWh rate power supply Interconnection cable main power supply Wires 3 GND 1 5 mm Normal kWh rate power supply Wires 1N Maximum running current 6 3 A Preferential kWh rate power supply contact Wires 2 0 75 1 25 mm Maximum length 50 m Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB The voltage free contact shall ensure the minimum applicable load...

Страница 16: ...3 11 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipmen...

Страница 17: ...e appropriate terminals as shown in the illustration below NOTICE Wiring is different for a NC normally closed valve and a NO normally open valve A M2S B A B 21 28 X2M B 21 29 X2M NO NC 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per meter 0 75 mm Electricity meters 12 V DC pulse detection voltage supplied by PCB 9 A Energy metering IN...

Страница 18: ... following see 4 2 1 To open the indoor unit 47 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of...

Страница 19: ...Maximum load 0 3 A 250 V AC Minimum load 20 mA 5 V DC 9 C Bivalent 1 Open the following see 4 2 1 To open the indoor unit 47 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M X1 a X2 a Installation of EKRP1HBAA is required 3 Fix the cable ...

Страница 20: ... A B X5M 13 14 3 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safety thermostat we recommend the following The safety thermostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There...

Страница 21: ...ollows A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 B A B X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter 0 5 mm Wires high voltage Smart Grid contacts 1 mm 9 8 4 3 Benefit kWh power supply Smart grid 9 8 5 Smart grid operation mode 9 8 6 Allow electrical heaters 9 8 7 Enable room...

Страница 22: ...le excessive cable length with a cable tie 6 3 12 To connect the WLAN cartridge delivered as accessory 1 Insert the WLAN cartridge into the cartridge slot on the user interface of the indoor unit 1 2 6 4 After connecting the electrical wiring to the indoor unit To prevent water ingress to the switch box seal the low voltage wiring intake using the sealing tape delivered as accessory Without low vo...

Страница 23: ...via the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 2 9 Accessing settings via the code in the overview field settings Code For example C 07 See also To access the installer settings 423 7 5 Menu structure Overview installer settings 431 7 1 1 To access the most used commands To change the user permission level You ...

Страница 24: ...ings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of domestic hot water tank is installed Emergency When the heat pump fails to operate the backup heater can serve as an emergency heater It then takes over the heat load either automatically or by manual interaction When Emergency is set to Automatic and a heat pump failure ...

Страница 25: ...on N A E 0D Glycol Filled system Is the system filled with glycol 0 No 1 Yes 7 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity grids If the backup heater is available the voltage configuration and capacity must be set on the user interface The capacities for the different steps of the backup heater must be set for the energy m...

Страница 26: ...rease the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling demand of the room External ro...

Страница 27: ...il the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0A Comfort setpoint 30 C 6 0E C Eco setpoint...

Страница 28: ...Go to the next temperature Confirm changes and proceed 7 3 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so...

Страница 29: ...al and for the tank go to 2 E Main zone WD curve type Viewing which type is selected is also possible via 3 C Additional zone WD curve type 5 E Tank WD curve type Restriction Only available to installers To change the weather dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heati...

Страница 30: ...scription 2 A C 05 External room thermostat type for the main zone 1 1 contact The used external room thermostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 7 4 2 Additional zone Thermostat type Only applicable in external room thermostat c...

Страница 31: ...ctrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention Benefit kWh power supply Power consumption control Energy metering Sensors Bivalent Alarm output Auto restart Power saving function Disable protections Overview field settings Forced defrost Export...

Страница 32: ...cal supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor unit and the room thermostat if applicable The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document...

Страница 33: ...lt The actuator test run starts It stops automatically when ready 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to confirm Possible actuator test runs Backup heater 1 test Backup heater 2 test Pump test INFORMATION Make sure that all air is purged before executing the test run Also avoid disturbances in the water circuit during the test run Shut off valve test ...

Страница 34: ...ble in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system and what to do in case of problems Show the user what to do for the maintenance of the un...

Страница 35: ... b a c d a Screw connection b Magnetic sleeve c Drain valve d Drain cap The yearly maintenance of the magnetic filter dirt separator consists of Checking if both parts of the magnetic filter dirt separator are still screwed tight a Emptying the dirt separator as follows 1 Take off the magnetic sleeve b 2 Unscrew the drain cap d 3 Connect a drain hose to the bottom of the water filter so that the w...

Страница 36: ...in intervals Chemical disinfection If the applicable legislation requires a chemical disinfection in specific situations involving the domestic hot water tank please be aware that the domestic hot water tank is a stainless steel cylinder We recommend to use a non chloride based disinfectant approved for use with water intended for human consumption NOTICE When using means for descaling or chemical...

Страница 37: ...ssible for visual inspection e g with an endoscope 1 2 3 3 Reconnect the pipe to the tank 4 Reinstall the clip to fix the domestic hot water OUT pipe 10 6 About cleaning the water filter in case of trouble INFORMATION For yearly maintenance you do not have to remove the water filter from the unit to clean it But in case of trouble with the water filter you might have to remove it so that you can t...

Страница 38: ...e complete lifetime of the magnetic filter dirt separator a b a Bottom part to be unscrewed b Water filter housing 3 Remove the strainer and the rolled up filter from the water filter housing and clean with water 4 Install the cleaned rolled up filter and strainer in the water filter housing INFORMATION Correctly install the strainer in the magnetic filter dirt separator housing using the protrusi...

Страница 39: ...ting cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from outdoor unit screw connection 1 c2 Water OUT to outdoor unit screw connection 1 d Pump e Backup heater f Shut off valve male female 1 g Expansion vessel h Magnetic filter dirt separator i Safety valve j A...

Страница 40: ...ired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation P...

Страница 41: ...ltage Smart Grid For safety thermostat For safety thermostat For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact 16 V DC detection voltage supplied by PCB Shut off valve Shut off va...

Страница 42: ... core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core OPTIONAL PART OPTIO...

Страница 43: ...talled by name address tel No completion date TECHNICAL SPECIFICATIONS EN12897 2016 Maximum water supply pressure to pressure reducing valve 16 bar Operating pressure set pressure of pressure reducing valve 3 5 bar Maximum primary working pressure heating 2 5 bar Maximum flow temperature 65 oC Expansion vessel pre charge pressure 3 5 bar Expansion valve setting 8 bar Temperature and pressure relie...

Страница 44: ...4P644729 1 2021 02 Copyright 2021 Daikin 4P644729 1 0000000U Verantwortung für Energie und Umwelt ...

Отзывы: