4 Piping installation

Installation manual

8

ETVH/9W(G)

Daikin Altherma 3 H HT F

4P586454-1 – 2019.07

3

Route the recirculation piping through the grommet and connect
it to the recirculation connector.

4

Reattach the top panel.

4.2.3

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  must  remain  open  after
commissioning.

4.2.4

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see the installer reference guide) that include the activation of pump
in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water from the system before it can freeze.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

About freeze protection by glycol

Adding glycol to the water lowers the freezing point of water.

WARNING

Ethylene glycol is toxic.

WARNING

Due  to  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

Types of glycol

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.

Required concentration of glycol

The  required  concentration  of  glycol  depends  on  the  lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from freezing, more glycol is required.

Add glycol according to the table below.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

–30°C

35%

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Содержание Altherma 3 H HT F ETVH16S18DA6V

Страница 1: ... manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18DA6V G ETVH16S23DA6V G ETVH16S18DA9W G ETVH16S23DA9W G ETVX16S18DA6V G ETVX16S23DA6V G ETVX16S18DA9W G ETVX16S23DA9W G ...

Страница 2: ...emme mukaisesti za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint haszná...

Страница 3: ...kup heater 19 6 2 5 Configuration wizard Main zone 20 6 2 6 Configuration wizard Additional zone 20 6 2 7 Configuration wizard Tank 21 6 3 Weather dependent curve 21 6 3 1 What is a weather dependent curve 21 6 3 2 2 points curve 22 6 3 3 Slope offset curve 22 6 3 4 Using weather dependent curves 23 6 4 Settings menu 23 6 4 1 Main zone 23 6 4 2 Additional zone 24 6 4 3 Information 24 6 5 Menu stru...

Страница 4: ...pliance or an operating electric heater 3 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C Mind the measurement guidelines Maximum height difference between indoor unit and outdoor unit 10 m Maxim...

Страница 5: ...owing cases 3 2 2 To lower the switch box on the indoor unit 45 3 3 2 To connect the drain hose to the drain 46 When you need access to the high voltage switch box 2 T25 5 If you need access to the high voltage components remove the high voltage switch box cover 4 T25 3 2 2 To lower the switch box on the indoor unit During the installation you will need access to the inside of the indoor unit To h...

Страница 6: ...ain hose to the drain See 3 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum allowed deviation is 1 1 NOTICE Do NOT tilt the unit forwards 0 1 1 3 3 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan The drain...

Страница 7: ...g the water piping 4 2 1 To connect the water piping 1 Connect the O rings and shut off valves to the outdoor unit water connection pipes of the indoor unit 2 Connect the outdoor unit field piping to the shut off valves 3 Connect the O rings and shut off valves to the space heating cooling water pipes of the indoor unit 4 Connect the space heating cooling field piping of both zones to the shut off...

Страница 8: ...rms galvanic corrosion cells that cause severe damage to the system Therefore it is important that the water treatment is correctly executed by a qualified water specialist a glycol with corrosion inhibitors is selected to counteract acids formed by the oxidation of glycols no automotive glycol is used because their corrosion inhibitors have a limited lifetime and contain silicates which can foul ...

Страница 9: ... taps after all air is purged 4 Check for water leaks 4 2 6 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity Outdoor water piping insulation See the installation manual of the outdoor unit or the installer reference guide 5 Electrical installation DANGER RISK OF...

Страница 10: ...2 0 75 1 25 mm Must be sheathed Maximum length 200 m See below LAN adapter System requirements LAN adapter System requirements The requirements posed on the Daikin Altherma system depend on the LAN adapter application system layout app control or Smart Grid application App control Item Requirement LAN adapter software It is recommended to ALWAYS keep the LAN adapter software up to date Unit contro...

Страница 11: ...11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required if preferential kWh rate power supply is interrupted when active OR if no power consumption of the indoor unit is allowed at the preferential kWh rate power supply when active INFORMATION The prefer...

Страница 12: ... equal to Zmax d 6T1 Connect the backup heater power supply as follows X6M F1B Q1DI a b a Factory mounted cable connected to the backup heater contactor inside the switch box K5M b Field wiring see table below Model power supply Connections to backup heater power supply 6V 6V 1N 230 V 1N 50 Hz 230 V AC SWB 4 3 6 5 2 1 K5M 14 13 Q1DI 1 2 3 4 5 6 7 8 F1B I I I I N L X6M BRN GRY BLU1 BLU2 Model power...

Страница 13: ... with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Open the following see 3 2 1 To open the indoor unit 44 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below A 6 5 4 3 S3S S2S B A B X5M 3 ...

Страница 14: ...arm output 3 Wire between X2M and A4P A4P Installation of EKRP1HB is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HB is required b Prewiring between X2M 7 9 and Q1L thermal protector backup heater Do NOT change 3 Fix the cable with cable ties to the cable tie mountings 5 2 7 To connect the space cooling heating ON OFF output Wires 2 1 0 75 mm Maximum load 0 3 A 250 V AC 1...

Страница 15: ...l 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M X1 a X2 a Installation of EKRP1HB is required 3 Fix the cable with cable ties to the cable tie mountings 5 2 9 To connect the power consumption digital inputs Wires 2 per input signal 0 75 mm Power l...

Страница 16: ...0 3 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safety thermostat we recommend the following The safety thermostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There is a minimum...

Страница 17: ...ou can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 9 1 5 2 Accessin...

Страница 18: ...ut cannot be adjusted Backup heater type The backup heater is adapted to be connected to most common European electricity grids The type of backup heater must be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domesti...

Страница 19: ...A E 0D Glycol Filled system Is the system filled with glycol 0 No 1 Yes 6 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity grids If the backup heater is available the voltage configuration and capacity must be set on the user interface The capacities for the different steps of the backup heater must be set for the energy meteri...

Страница 20: ...Control Defines how the operation of the unit is controlled There are 3 possibilities Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling demand of the room External room thermostat Unit operation is decided by the external thermostat or equivalent e g heat pump convector Room thermo...

Страница 21: ...top can be programmed This feature puts a stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0A Comfort setpoint 30 C 6 0E C Eco setpoint The storage economic temperature denotes the lower desired tank temperature It is the desired temperature when a storage economic action is scheduled prefe...

Страница 22: ...leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperatures For exa...

Страница 23: ...imum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum and minimum setpoints for that zone or for the tank When the maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve of a zone or tank Yo...

Страница 24: ... in external room thermostat control For more info about the functionality see 6 4 1 Main zone 423 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 6 4 3 Information Dealer information The installer can fill in his contact number here Code Description 8 3 N A Number that users can call in case of problems ...

Страница 25: ...g 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevent...

Страница 26: ...gislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor unit and the room thermostat if applicable The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed ac...

Страница 27: ...he list Example Pump 4 Select OK to confirm Result The actuator test run starts It stops automatically when done 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to confirm Possible actuator test runs Backup heater 1 test Backup heater 2 test Pump test INFORMATION Make sure that all air is purged before executing the test run Also avoid disturbances in the water c...

Страница 28: ...d ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system and what to do in case of problems Show the user what to do for the maintenance of the unit Explain the user about energy saving tips as described in the operation manual ...

Страница 29: ...ater cold water IN loose nut 3 4 b2 Domestic hot water hot water OUT loose nut 3 4 c1 Water IN connection c2 Water OUT connection d Pump e Backup heater f Shut off valve male female 1 g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve l Loose nut 1 B1L Flow sensor B1PW Space heating water pressure sensor M3S 3 way valve space heating domestic hot water R1T...

Страница 30: ... wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P On OFF thermostat PC power circuit A3P Heat pump convector A4P Digital I O PCB A8P Demand PCB A11P MMI user interface of the indoor unit Main PCB A13P LAN adapter A14P PCB of ...

Страница 31: ...sed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact 16 V DC detection voltage supplied by PCB English Translation Shut off valve Shut off valve SWB1 Switch box 7 Option PCBs 7 Option PCBs Alarm output Alarm output Changeover to ext heat source Changeover to external heat source Max load Maximum load Min load ...

Страница 32: ...re 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core communication communication...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...4P586454 1 2019 07 Copyright 2019 Daikin 4P586454 1 0000000U ...

Отзывы: