10
|
Configuration
Installer reference guide
231
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1B – 2022.09
#
Code
Description
[9.P.3]
[7-0A]
Add zone pump fixed PWM
: Fixed pump
speed for additional (direct) zone.
▪
20~95% (default: 95)
Main zone pump fixed PWM
The speed of the main zone pump can be fixed with this setting.
#
Code
Description
[9.P.4]
[7-0B]
Main zone pump fixed PWM
: Fixed pump
speed for main (mixed) zone.
▪
20~95% (default: 95)
Mixing valve turning time
If a third party mixing valve is installed in combination with controller EKMIKPOA,
the valve turning time must be set accordingly.
For this setting, space heating/cooling and tank operation MUST be off:
[C.2]
Space
heating/cooling
=0 (
Off
) and [C.3]
Tank
=0 (
Off
). See
#
Code
Description
[9.P.5]
[7-0C]
Mixing valve turning time
: Time in
seconds for the mixing valve to turn from one
side to the other.
▪
20~300 sec (default: 125)
In case a bizone kit is installed, antiblockage of kit pump(s) and kit mixing valve
#
Code
Description
[9.I]
[3-0D]
In case a bizone kit is installed, antiblockage of
kit pump(s) and kit mixing valve
▪
0:
disabled
▪
1:
enabled
NOTICE
The unit reboots as soon as a bizone kit is connected. After reboot of the unit we
recommend to set [3-0D]=1.
10.5.10 Commissioning
Overview
The following items are listed in the submenu:
A
Commissioning
User profile
Installer settings
Information
Operation
[A]
Commissioning
[A.1]
Operation test run
[A.2]
Actuator test run
[A.3]
Air purge
[A.4]
UFH screed dryout
About commissioning
See: