Unit installation
Installer reference guide
49
EPGA11~16DAV3(7) + EA23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
7.2.2 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
1×
2×
2×
6
5
1
3
4
2
8
9
7
7.2.3 To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or
noise may be generated.
The compressor transportation stay must be removed. It is installed under the
compressor leg in order to protect the unit during transport. Proceed as shown in
the figure and procedure below.
1
Remove the nut (a) of the compressor mounting bolt.
2
Remove and discard the transportation stay (b).
3
Re-install the nut (a) of the compressor mounting bolt and tighten to
10.1 N•m of torque.