10
|
Configuration
Installer reference guide
193
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
#
Code
Description
[9.B.2]
[2-0B]
Ext. amb. sensor offset
: Offset on the
ambient temperature measured on the external
outdoor temperature sensor.
▪
–5°C~5°C, step 0.5°C
Averaging time
The average timer corrects the influence of ambient temperature variations. The
weather-dependent setpoint calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
Description
[9.B.3]
[1-0A]
Averaging time
:
▪
0: No averaging
▪
1: 12 hours
▪
2: 24 hours
▪
3: 48 hours
▪
4: 72 hours
Brine low pressure switch
When a brine low pressure switch is installed, the unit must be configured to work
with the switch. When the switch is removed or disconnected, this setting must be
set to OFF.
#
Code
Description
N/A
[C-0B]
Activation of the brine low pressure switch
▪
0: OFF
▪
1: On
Bivalent
Alarm output
Alarm output
#
Code
Description
[9.D]
[C–09]
Alarm output
: Indicates the logic of the alarm
output on the digital I/O PCB during
malfunctioning.
▪
0
Abnormal
: The alarm output will be
powered when an alarm occurs. By setting this
value, a distinction is made between the
detection of an alarm, and the detection of a
power failure.
▪
1
Normal
: The alarm output will NOT be
powered when an alarm occurs.
See also table below (Alarm output logic).