Activate Drive Control Functions – EFB
Controlling the Drive
Fieldbus control of various drive functions requires
configuration to:
•
Tell the drive to accept fieldbus control of the function.
•
Define as a fieldbus input, any drive data required for
control .
•
Define as a fieldbus output, any control data required by
the drive .
The following sections describe, at a general level, the
configuration required for each control function. For the
protocol-specific details, see the document supplied with the
FBA module .
Start/Stop Direction Control
Using the fieldbus for start/stop/direction control of the drive
requires:
•
Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 50: Start/Stop Direction Control Protocol Reference
Drive Parameter
Value
Description
Protocol Reference
Modbus
1
N2
FLN
BACnet
abb drv
dcu profile
1001
EXT1 COMMANDS
10 (COMM)
Start/Stop by fieldbus with Ext1
selected .
40001 bits 0…3
40031 bits 0, 1
BO1
24
BV10
1002
EXT2 COMMANDS
10 (COMM)
Start/Stop by fieldbus with Ext2
selected .
40001 bits 0…3
40031 bits 0, 1
BO1
24
BV10
1003
DIRECTION
3 (REQUEST)
Direction by fieldbus.
4002/40032
40031 bit 3
BO2
22
BV11
•
1.Daikin MicroTech II controls communicate with the MD4 over Modbus and all parameters are factory set. No field adjustments are recommended.
• 2 .The reference provides direction control – a negative reference provides reverse rotation .
Input Reference Select
Using the fieldbus to provide input references to the drive
requires:
•
Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 51: Input Reference Select Protocol Reference
Drive Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN
BACnet
abb drv
dcu profile
1102
EXT1/EXT2 SEL
8 (COMM)
Reference set selection by
fieldbus.
40001 bit 11
40031 bit 5
BO5
26
BV13
1103
REF1 SEL
8 (COMM)
Input reference 1 by fieldbus.
40002
AO1
60
AV16
1106
REF2 SEL
8 (COMM)
Input reference 2 by fieldbus.
40003
AO2
61
AV17
Reference Scaling
Where required, REFERENCES can be scaled . See the following, as appropriate:
Daikin MicroTech II controls communicate with the MD4 over
Modbus and all parameters are factory set .
No field adjustments are recommended.
f
Ieldbus
C
onTrols
www .DaikinApplied .com 75
OM 1190-1 • MD4 VFD