Group 34: Panel Display Process Variables
This group defines the content for control panel display (middle area), when the control panel is in the output mode.
Table 40: Group 34: Panel Display Process Variables
Code Description
Range
Resolution
Default
S
3401 SIGNAL1 PARAM
100…199
1
103
Selects the first parameter (by number) displayed on the control panel.
• Definitions in this group define display content when the control panel is in the control mode.
• Any Group 01 parameter number can be selected, page __ .
• Using the following parameters, the display value can be scaled, converted to convenient units,
and/or displayed as a bar graph .
• The figure identifies selections made by parameters in this group.
100 = not selected – First parameter not displayed .
101…199 = Displays parameter 0101…0199 . If parameter does not exist, the display shows “n .a .” .
3402 SIGNAL1 MIN
Depends on
selection
0 .0 Hz
Defines the minimum expected value for the first display parameter. Use parameters 3402, 3403,
3406, and 3407, for example to convert a Group 01 parameter, such as 0102 SPEED (in rpm) to the
speed of a conveyor driven by the motor (in ft/min) . For such a conversion, the source values in the
figure are the min. and max. motor speed, and the display values are the corresponding min. and
max . conveyor speed . Use parameter 3405,
to select the proper units for the display .
Note:
Selecting units does not convert values .
3403 SIGNAL1 MAX
Depends on
selection
—
600 .0 Hz
Defines the maximum expected value for the first display parameter.
3404 OUTPUT1 DSP FORM
0…9
1
9
Defines the decimal point location for the first display parameter.
3404 Value
Display
Range
0
+ 3
-32768…+32767 (Signed)
1
+ 3 .1
2
+ 3 .14
3
+ 3 .142
4
3 0…65535
(Unsigned)
5 3 .1
6 3 .14
7 3 .142
1…7 – Defines the decimal point location.
• Enter the number of digits desired to the right of the decimal point .
• See table for example using pi (3 .14159) .
8 = BAR METER – Specifies a bar meter display.
9 = DIRECT – Decimal point location can vary depending on source signal but does not affect unit operation .
3405 OUTPUT1 DSP UNIT
0…127
1
4
Selects the units used with the first display parameter.
0 = NOT SEL
12 = mV
24 = GPM
36 = l/s
48 = gal/m
60 = ft wg
1 = A
13 = kW
25 = PSI
37 = l/min
49 = gal/h
61 = lbsi
2 = V
14 = W
26 = CFM
38 = l/h
50 = ft3/s
62 = ms
3 = Hz
15 = kWh
27 = ft
39 = m3/s
51 = ft3/m
63 = Mrev
4 = %
16 = °F
28 = MGD
40 = m3/m
52 = ft3/h
64 = d
5 = s
17 = hp
29 = inHg
41 = kg/s
53 = lb/s
65 = inWC
6 = h
18 = MWh
30 = FPM
42 = kg/m
54 = lb/m
66 = m/min
7 = rpm
19 = m/s
31 = kb/s
43 = kg/h
55 = lb/h
67 = Nm
8 = kh
20 = m3/h
32 = kHz
44 = mbar
56 = FPS
68 = Km3/h
9 = °C
21 = dm3/s
33 = Ohm
45 = Pa
57 = ft/s
10 = lb ft
22 = bar
34 = ppm
46 = GPS
58 = inH2O
11 = mA
23 = kPa
35 = pps
47 = gal/s
59 = in wg
117 = %ref
119 = %dev
121 = % SP
123 = Iout
125 = Fout
127 = Vdc
118 = %act
120 = % LD
122 = %FBK
124 = Vout
126 = Tout
a
CTual
s
Ignals
and
p
arameTers
www .DaikinApplied .com 57