Programmable Digital Inputs
The drive has five programmable digital inputs. The update
time for the digital inputs is 2 ms . It is possible to delay the
state change of digital inputs with delays defined in group
Group 18: FREQ IN & TRAN OUT . This enables very simple
program sequences by connecting several functions with the
same physical wire, eg to remove branches and leaves from a
pipe by running the fan in reverse before normal operation .
One digital input (DI5) can be programmed as a frequency
input . See section “Frequency Input” .
Table 6: Programmable Digital Inputs Settings
Table 7: Programmable Digital Inputs Diagnostics
Programmable Relay Output
The drive has one programmable relay output . It is possible
to add three additional relay outputs with the optional Relay
Output Extension Module MREL-0 . For more information,
see MREL-01 Relay Output Extension Module User’s Manual
(3AUA0000035974 [English]) .
With a parameter setting it is possible to choose what
information to indicate through the relay output: Ready,
running, fault, alarm, etc . The update time for the relay output
is 2 ms .
A value can be written to a relay output through a serial
communication link .
Table 8: Programmable Relay Output Settings
Table 9: Programmable Relay Output Diagnostics
Frequency Input
Digital input DI5 can be programmed as a frequency input .
Frequency input (0…16000 Hz) can be used as external
reference signal source . The update time for the frequency
input is 50 ms . Update time is shorter when information is
transferred to the application program (50 ms -> 2 ms) .
Table 10: Frequency Input Settings
Table 11: Frequency Input Diagnostics
Parameter
Additional Information
Group 10: AcStart/Stop/Dir
DI as start, stop, direction
Group 11: Reference Select
DI in reference selection, or reference
source
Group 12: Constant Speeds
DI in constant speed selection
Group 16: System Controls
DI as external Run Enable, fault reset
or user macro change signal
Group 18: FREQ IN & TRAN OUT
2109
DI as external emergency stop
command source
2201
DI as acceleration and deceleration
ramp selection signal
2209
DI as zero ramp force signal
Actual Signal
Additional Information
0160
DI status
0414
DI status at the time the latest fault
occurred
Parameter
Additional Information
Group 14: Relay Outputs
RO value selections and operation
times
Actual Signal
Additional Information
0134
ROControl Word through fieldbus
control
0162
RO 1 status
0173
RO 2…4 status . With option MREL-
01 only
Parameter
Additional Information
Group 18: FREQ IN & TRAN OUT
Frequency input minimum and
maximum values and filtering
1103/1106
External reference REF1/2 through
frequency input
4010, 4110, 4210
Frequency input as PID reference
source
Actual Signal
Additional Information
0161
Frequency input value
p
rogram
f
eaTures
www .DaikinApplied .com 25
OM 1190-1 • MD4 VFD