background image

Configuration

When installing a remote sensor you must enable the remote sensor option. See 

Installer/Configuration Menu

 in IM 1178.

Troubleshooting Chart

To function correctly and read temperature accurately, the thermostat (when set up for a remote as outlined above) must have 

constant 24-volt power. If the thermostat temperature is steadily dropping, reading low, or reads 08° when a remote sensor is 

installed, it can be traced to one of the three following conditions.

Condition

Test

Comments

1. Loss of 24-volt power.

On models with batteries, remove the batteries and re-

install thermostat. If the display is blank, check heating and 

cooling system to determine why 24-volt power is absent.

For the sensor to read correctly, the 24-volt system power must 

be present. Some systems may require an isolation relay to 

provide constant power to the thermostat. Limit or safety
devices in the equipment can also cause a power interruption

2. A broken wire on +, SA, - from 

the thermostat to the remote.

Disconnect sensor wires at thermostat. Attach a short piece 
(2') of three-wire shielded cable to (+, SA -) on the subbase. 

Bring the remote sensor to the thermostat, location and 
attach (+, S, -) respectively. Reattach thermostat. If the 

temperature begins to climb (slowly), it is reading correctly. 
If it reads correctly with the 2' length but improperly when 
attached to the wire run, it indicates a fault in the wire run.

Repair or replace the 3 wire shielded cable. Be sure the remote 
wire run is not parallel to line voltage wires that carry heavy in

-

ductive loads, or across fluorescent light ballasts that may cause 

an inductance to be transmitted to the thermostat.

3. A shorted or damaged remote 
sensor.

Because it is an electronic sensor, there are no Ohm values 
to test. If correct conditions as listed in 1 & 2 above and the

temperature stays at or near 08°, it indicates a shorted or

damaged remote sensor.

Replace remote sensor.

Note:

Digital thermostats and remote sensors acclimate very slowly to temperature change. It may take an hour or more for the 

temperature to acclimate to the room temperature from a low temperature reading as outlined above. To expedite the room 

temperature display use the reset instructions listed in the installation instructions for the thermostat model you are working 

with. When reset, the thermostat will default to a room temperature of 70° and begin sensing room temperature. Be sure to 

reconfigure the installer menu for a remote sensor because the reset function may cancel remote sensing.

©2013 Daikin Applied   •   

www.DaikinApplied.com

   •   800.432.1342 

IOM 1175 / Page 4 of 4 

Содержание 910129095

Страница 1: ...0121750 SmartSource Units Models GS GT Indoor Remote Sensor Outdoor Remote Sensor Outdoor Probe IMPORTANT Operator save these instructions for future use Contents Safety 2 Specifications 2 Installation 2 Indoor Sensor 2 Outdoor Sensor 2 Wiring 3 Indoor Remote Sensor Wiring Diagram 3 Outdoor Remote Sensor Wiring Diagram 3 Configuration 4 Troubleshooting Chart 4 2013 Daikin Applied www DaikinApplied...

Страница 2: ... is 12 feet long and should not be cut or spliced so plan the placement of both the probe and interior mounting base accordingly Any excess wire may be coiled or bundled The probe should be connected to E2 as shown in Figure 3 Safety WARNING Wiring connections must be made in accordance with all applicable electrical codes Failure to read and follow all instruc tions carefully before installing or...

Страница 3: ...odel Number Color Dimensions Application 910129096 Classic White 2 1 8 3 1 2 3 4 with 12 sensor lead Compatible with Programmable Touch Screen Thermostat Part No 910121750 with outdoor remote sense Indoor Remote Sensor Wiring Diagram Figure 2 Indoor Remote Sensor 910129095 wiring to Programmable Touch Screen Thermostat 910121750 S E2 G RC RH C S 6 W1 L Y2 Y W4 W3 W2 D A Thermostat Base Remote Indo...

Страница 4: ...h thermostat If the temperature begins to climb slowly it is reading correctly If it reads correctly with the 2 length but improperly when attached to the wire run it indicates a fault in the wire run Repair or replace the 3 wire shielded cable Be sure the remote wire run is not parallel to line voltage wires that carry heavy in ductive loads or across fluorescent light ballasts that may cause an ...

Отзывы: