Configuration Mode Settings

The setup screens for Configuration Mode are as follows:

1. 

Temperature Scale 

(F or C)

 

Choose Fahrenheit or Celsius.

  Press the 

up

 or 

down

 button to select.

  Press the 

right

 button to advance to the next screen.

2. 

1

st

 Stage Temperature Differential

 (1°F to 5°F) (0.5°C to 2.5°C)

Set the number of degrees between your “setpoint” temperature and your “turn on” 
temperature.

  Press the 

up

 or 

down

 button to set differential value.

  Press the 

right 

button to advance to the next screen.

4. 

Staged Off Outputs

  

  Select whether the outputs for heating and cooling are staged off independently or 

are satisfied simultaneously.

  1 = outputs staged off independently     
  0 = outputs off simultaneously
  Press the 

up

 or 

down

 button to set.

  Press the 

right 

button to advance to the next screen.

5. 

Minimum Deadband

 (1°F to 9°F) (1°C to 5°C) 

  Set the minimum separation between heat setpoint and cool setpoint in 

Auto 

Changeover

 Mode.

  Press the 

up

 or 

down

 button to set deadband value.

  Press the 

right 

button to advance to the next screen.

3. 

2

nd

 Stage Temperature Differential

 (1°F to 5°F) (0.5°C to 2.5°C) 

  Set the number of degrees between when stage 1 turns on and when stage 2 turns on.
  Press the 

up

 or 

down

 button to set differential value.

  Press the 

right 

button to advance to the next screen.

6. 

Maximum Heat Setpoint

 (55°F to 90°F) (13°C to 32°C) 

 

Adjust to control the maximum heat set temperature allowed.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

7. 

Minimum Cool Setpoint

 (55°F to 90°F) (13°C to 32°C) 

 

Adjust to control the minimum cool set temperature allowed.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

9. 

Temperature Sensor

 (1-3) 

 

1. Only on-board sensor determines room temperature.

 

2. Only remote sensor determines room temperature.

 

3. Average temperature of on-board and remote sensor.

 

 

Note:

 

If there is no remote sensor, option 1 must be selected.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

configuration

 button for two seconds to exit configuration.

8. 

Room Temperature Offset

 (+9°F to -9°F) (+4.5°C to -4.5°C) 

 

Adjust to calibrate displayed room temperature to match actual room temperature. 

 

 

Note:

 

When not set to 0, 

 

will display.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

Mode of Operation

The 

910121746

 is a non-programmable, manual or auto changeover, 2-stage heat, 2-stage cool thermostat. An 

outdoor sensor can be used to monitor the outdoor temperature.

The thermostat activates the heating appliance when the room temperature is below the set heat temperature (by 
the differential temperature). The 

910121746

 will stop outputting when the call for heat has been satisfied. 

When the room temperature is greater than the set cool temperature (by the differential temperature), the cooling 
device is activated. The 

910121746

 will stop outputting when the call for cooling is satisfied. 

The 

910121746

 has four possible operating modes: 

OFF

Heat

Cool

 and 

Heat & Cool

 mode. In off mode, the 

thermostat will not turn on heating or cooling devices. The manual fan can be turned on in all operating modes using 
the fan button. In heat mode, the thermostat controls the heating system. In the cool mode, the thermostat controls 
the cooling system. In heat & cool mode, the thermostat controls both the heating and cooling systems.

Pressing the UP and DOWN buttons simultaneously for 2 seconds then releasing them causes the thermostat to 
output from the “O” terminal for 5 seconds. “ Or” will show on the display. This will result in the unit going into a night 
set-back override.

Pressing the UP and DOWN buttons simultaneously for 5 seconds causes the thermostat to output from the “O” 
terminal for 10 seconds. “ rS” will show on the display. This will result in the unit being reset.

Button Functions

UP

 – Used to increase the time, set temperatures and to adjust configuration 

settings. 

DOWN

 – Used to decrease the time, set temperatures and to adjust 

configuration settings.

SYS (left)

 –  Used to change from OFF, HEAT, COOL and AUTO changeover 

modes

FAN (right)

 – Used to turn on and off the indoor fan.

DOWN and SYS

 – Pressed simultaneously to display outdoor remote temperature if remote sensor is 

connected.

UP and DOWN

 –  Used to override night set back or reset the unit.

FAN

 

(right)

Down

 

button

Up

 

button

SYS

tem 

(left)

Testing the Thermostat

Once the thermostat is configured, it should be thoroughly tested.

 

CAUTION!

Do not energize the air conditioning system when the outdoor temperature is below 50 
degrees. It can result in equipment damage or personal injury.

Heat Test

1. Press 

SYS

 (left) button until heat mode is displayed.

2. Adjust the set temperature so it is 5 degrees above the room temperature.
3. Heat should come on within a few seconds.
4. Adjust the set temperature 2 degrees below the room temperature and the heat 

should turn off. There may be a fan delay on your system.

Cool Test

1. Press 

SYS

 (left) button until cool mode is displayed. 

2. Adjust set temperature so it is 5 degrees below room temperature.
3. A/C should come on within a few seconds.
4. Adjust the set temperature 2 degrees above the room temperature and the A/C 

should turn off. There may be a fan delay on your system.

Fan Test

1.  Press 

FAN

 (right) button. Fan displays. Indoor fan turns ON.

2.  Press 

FAN

 (right) button. Indoor fan turns OFF.

OFF

Operating Modes

There are five possible operating modes for the 

910121746

. Off, Cool, Heat, and Cool & Heat modes are accessed 

by pressing the 

SYS

 (left) button. Program mode is accessed by pressing the 

SYS

 (left) and 

FAN

 (right) buttons 

simultaneously.

OFF Mode

•  In this mode, the thermostat will not turn on the heating or cooling devices
 

 

Note:

 

The indoor fan can be turned on manually in every operating mode by 
pressing the 

FAN

 (right) button. The word 

FAN 

shows on the display and 

the fan icon   appears when the fan operates.

OFF

Heat Mode

•  In this mode, the thermostat controls the heating system. When the heat outputs, 

the flame icon   apprears on the display.

Cool Mode

•  In this mode, the thermostat controls the cooling system. When the cooling 

outputs, the snowflake icon   apprears on the display.

Cool and Heat Mode

 (Auto Changeover)

•  In this mode, the thermostat controls the cooling and heating systems, automatically 

changing over from one to the other as needed.

•  The timing display alternates with the set temperature every 10 seconds in the cool 

and heat mode.

Symptom

Remedy

No display

Check for 24 VAC at thermostat; display is blank when 24 VAC is not 
present

All thermostat buttons are inoperative

Verify 24 VAC is present; unit locks out when 24 VAC is not present

No response with first button press

First button press activates backlight only

Thermostat turns on and off too 
frequently

Adjust temperature differential (see Configuration Mode Settings 2 & 3)

Fan runs continuously

Press FAN (right) button to turn fan off

Status indicator on

WSHP status blink code

Room temperature is not correct

Calibrate thermostat (see Configuration Mode Setting 8) 
If remote sensor is used, check S1 and S2 terminal connections

on display instead of room 
temperature

Check for a bad connection at S1 and S2 terminals, if used 
(see Configuration Mode Setting 9)

Heat or Cool not coming on

Verify wiring is correct, gently pull on each wire to verify there is a good 
connection at terminal block

Alarm light on

Unit in alarm lockout condition

Problem not listed above

Press Reset button once*

* Reset Button Function

: Display is refreshed and configuration settings are unchanged.

Troubleshooting

Daikin Training and Development

Now that you have made an investment in modern, efficient 

Daikin

 equipment, its care should be a high priority. For 

training information on all 

Daikin

 HVAC products, please visit us at 

www.DaikinApplied.com

 and click on Training, 

or call 540-248-9646 and ask for the Training Department.
 

Warranty

All 

Daikin

 equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product 

Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-430285Y. To find your 
local 

Daikin

 Representative, go to 

www.DaikinApplied.com

.

 

Aftermarket Services

To find your local parts office, visit www.DaikinApplied.com or call 

800-37PARTS (800-377-2787)

. To find your 

local service office, visit

 www.DaikinApplied.com

 or call 

800-432-1342

. This document contains the most current 

product information as of this printing. For the most up-to-date product information, please go to  

www.DaikinApplied.com

.

 