Daikin 3P419248-1-KA Скачать руководство пользователя страница 1

Installation and operation manual

BRC1E53

1

3P419248-1-KA – 2015.09

The  English  text  is  the  original  instruction.  Other  languages  are
translations of the original instructions.
Refer 

to 

http://www.daikineurope.com/support-and-manuals/

product-information/ 

for more detailed user reference guides.

Installation: see 

page 2

.

1.

General safety precautions

Please read these 

"1. General safety precautions"

 carefully before

installing  air  conditioning  equipment  and  be  sure  to  install  it
correctly.
Failure to follow these instructions properly may result in property
damage or personal injury, which may be serious depending on the
circumstances.

2.

Features and functions

The BRC1E53 is a state of the art remote controller that offers full
control over your installation.

1 BASIC REMOTE CONTROLLER
The basic remote controller functions are:

ON/OFF,

operation mode change-over,

temperature adjustment,

air volume adjustment,

airflow direction adjustment.

2 CLOCK FUNCTION
The clock functions are:

12/24 hours real time clock,

automatic daylight saving time.

3 SCHEDULE FUNCTION
The schedule timer functions are:

a maximum of 5 actions can be programmed for each day of
the week,

3 independent schedules can be programmed,

schedule can be enabled/disabled at any time,

linked  to  a  cool  temperature  and/or  heat  temperature  or  an
OFF operation (with or without a setback temperature),

"last  command"  overrules  previous  command  until  next
scheduled command.

4 SETBACK
The setback function maintains the room temperature in a specific
range  when  the  occupants  are  out  for  a  longer  period  and  the
airconditioning is switched OFF.

5 PROHIBIT BUTTON/FUNCTION
Buttons,  functions  and/or  modes  can  be  locked  to  limit  the  user
action.

6 DETAILED DISPLAY POSSIBILITY
Additionally  possible  to  display  the  outdoor  temperature  or  room
temperature.

7 Duty rotation
Auto  backup  unit  and  auto  rotation  to  maximize  your
airconditioners' life.

8 Demand control
Make up an energy reduction schedule.

9 Quiet mode
Schedule a quiet mode for your outdoor unit(s).

10 INTERLOCK WITH 2 EXTERNAL SIGNALS
(Only  available  when  the  BRP7A51  Digital  Input  Adapter  is
connected)

Connect up to two switch contacts (contact B1 and B2).

Typical  application:  hotel  interlock  with  field  supplied  window
contact B1 and key card B2.

3.

Name and function of switches

1 OPERATION MODE SELECTOR BUTTON
To select the operation mode of your preference.

2 FAN SPEED/AIRFLOW DIRECTION SETTING BUTTON
To enter the fan speed/airflow direction setting screen.

3 MENU/ENTER BUTTON
To enter the main menu or the selected setting item.

4 UP/DOWN BUTTON
To raise/lower the set temperature, to highlight the next item on the
upper/lower side or to change the selected item.

5 RIGHT/LEFT BUTTON
To highlight the next item on the right/left-hand side.

6 ON/OFF BUTTON
To start or stop the system.

7 OPERATION LAMP
Lights up during operation or blinks if a malfunction occurs.

8 CANCEL BUTTON
To return to the previous screen.

9 LCD (with backlight)
When  pushing  any  operation  button,  the  backlight  will  be  lit  for
approximately  30  seconds.  When  1  indoor  unit  is  controlled  by  2
remote controllers, the backlight of the remote controller operated
earlier than the other one will be lit.

4.

Name and function of icons

To change between the standard display and the detailed display
refer to 

"17.4 To select the display mode"

.

Standard display

Detailed display

1 OPERATION MODE

2 FAN SPEED
Indicates the fan speed that is set for the air conditioner. If the air
conditioner does not have fan speed control function, the fan speed
will not be displayed.

3 SET/SETBACK TEMPERATURE DISPLAY
When  the unit  is turned on, 

Set to

 indicates the temperatures that

are set for the air conditioner.
When the unit is turned off, 

Setback

 indicates the temperatures that

are set for the setback function.

4 DEFROST/HOT START 
Indicates that the defrost/hot start mode is active.

5 MESSAGE
Messages can be displayed.

6 VENTILATION/CLEANING

Ventilation mode icons 

 

 

 indicate the current

ventilation mode (HRV only) (

AUTOMATIC

ENERGY RECLAIM VENT.

,

BYPASS

).

Air Cleaning unit icon 

 indicates that the air cleaning unit

(option) is operational.

7

 DISPLAY

Indicates that the key lock is set or the menu button is prohibited.

8

  DISPLAY

Indicates that schedule timer or OFF timer is enabled.

 DISPLAY

Indicates  that  the  clock  needs  to  be  set.  The  schedule  timer
function will not work until the clock is set.

9 EXTERNAL CONTROL ICON 
Indicates that another controller with higher priority is controlling or
disabling your remote controller.

10 CHANGEOVER UNDER CENTRALISED CONTROL ICON 

Indicates  that  the  changeover  of  the  installation  is  under
centralised control assigned to another indoor unit or optional cool/
heat  selector  connected  to  the  outdoor  unit  (=  master  remote
controller).

11 SETBACK ICON 
Flashes when the unit is turned on under the setback control.

12 AIRFLOW DIRECTION 

Is displayed when the airflow direction and swing are set.

13 CLOCK (12/24 Hours real time clock)
Is  displayed  when  the  clock  is  set.  If  the  clock  is  not  set,  - : -  is
displayed.

14 DETAILED SELECTION
Is displayed when the detailed display items are selected.

15 ROTATION 
Indicates one unit is set as back-up and rotation mode is enabled.

16 QUIET MODE 

Indicates  the HVAC system runs in quiet mode or under demand
control.

5.

Description of the operation modes

1 FAN ONLY OPERATION
In this mode, air only circulates without heating or cooling. 

2 DRY OPERATION
In  this  mode,  the  air  humidity  will  be  lowered  with  a  minimal
temperature decrease.
The  temperature  and  fan  speed  are  controlled  automatically  and
cannot be controlled by the remote controller. 
Dry operation will not function if the room temperature is too low.

3 AUTOMATIC OPERATION
In  this  mode,  the  controller  will  automatically  switch  between
heating and cooling as required by the setpoint.

4 COOLING OPERATION
In this mode, cooling will be activated as required by the setpoint or
limit operation.

5 HEATING OPERATION
In this mode, heating will be activated as required by the setpoint or
setback operation.

6 VENTILATION (HRV only)
The ventilation mode operates the HRV; refer to the HRV manual
for more details.

7 SETBACK 

SETBACK is a feature that enables to keep the room temperature
in  a  specific  range  when  the  occupants  are  out  and  the
airconditioning is switched OFF.
For example:

If the room temperature drops below 10°C, heating is started
automatically.  As  soon  as  12°C  is  reached,  the  controller
returns to its original status.

If  the  room  temperature  goes  above  35°C,  cooling  is  started
automatically.  As  soon  as  33°C  is  reached,  the  controller
returns to its original status.

The differential can be adjusted in the Setback configuration menu.
The setback temperature can be set during the unit is turned off on
basic screen or set in the schedule.

6.

Basic operation method

a

Operation mode

b

Temperature:

When the unit is turned on, 

Set to

 indicates the 

temperatures that are set for the air conditioner.

When the unit is turned off, 

Setback

 indicates the 

temperatures that are set for the setback function.

c

Fan speed/Airflow direction

1

Push 

 several times until the desired operation mode 

Cool

,

Heat

Vent

Fan

Dry

, or 

Auto

 is selected.

2

Push 

.  The  operation  lamp  will  light  and  the  system  starts

operating.

3

Use 

 to set the temperature.

4

Push 

.

5

Use 

 to select airflow 

Level

 or 

Direction

 setting.

6

With fan speed setting selected, use 

 to select the desired

fan speed.

7

With airflow direction setting selected, use 

 to change the

setting to 

Swing

Pos. 0

Pos. 1

Pos. 2

Pos. 3

, and 

Pos. 4

.

8

Push 

 to display the basic screen.

9

Push 

. The operation lamp will turn off and the system stops

operating.

Additional features of the controller: KEY LOCK

1

Push 

 for 4 seconds to enable the key lock mode. The key

lock icon is displayed.

2

To cancel the key lock mode, push 

 for 4 seconds. The key

lock icon disappears.

7.

Description of the items in the main menu

1 LOCK
To prohibit buttons, functions or modes.

2 ROTATION
To enable the duty rotation functionality.
(Only available with indoor units that support duty rotation)

3 AIRFLOW DIRECTION

1

/INDIVIDUAL AIR DIRECTION 

(only if the individual airflow function is installed)

To set the airflow direction for each 4 flaps individually.

4 QUICK START

1

 (SkyAir only)

To quickly set the room temperature to a comfortable temperature.

5 VENTILATION
To set the ventilation rate and the ventilation mode (HRV only).

6 ENERGY SAVING OPTIONS
This  allows  you  to  restrict  the  setting  temperature  range  and
display the energy consumption.

Setpoint Range Setting

Energy saving list

Setback condition

Sensing sensor (Low)

1

,

 

2

 (Only if sensing sensor is installed)

Sensing sensor (Stop)

1

,

 

2

 (Only if sensing sensor is installed)

Setpoint Auto Reset

OFF Timer

Auto display OFF
For  more  information  refer  to  the  detailed  user  reference
guide

3

Energy Consumption

1

7 SCHEDULE

4

To set the startup time and operation stop time for any day of the
week. It is possible to set up to 5 actions per day. Both operation
modes  (normal  and  setback)  can  be  selected.  Additionally  the
holiday settings and schedule nr can be set.

8 MAINTENANCE INFORMATION
Is used to display the service contact and model info.

9 CONFIGURATION
To  set  the  LCD  contrast.  You  can  also  switch  between  standard
and detailed display. When detailed display is selected, the detailed
display settings can be changed. You can also set 

Quiet mode

 and

Draft prevention

.

10 CURRENT SETTINGS
This shows a list of the current settings for the available items.

11 CLOCK & CALENDAR
This allows you to set the date and time. Time can be displayed in
either 12 hour or 24 hour time format.

12 LANGUAGE
This allows you to set the displayed language.

8.

Lock

1

Display the main menu.

2

Press the 

 button for 4 seconds.

3

Use 

 to select the 

Lock

 item and press 

.

4

Use the submenu's to prohibit buttons, functions or modes.

For more information refer to the detailed user reference guide

3

.

9.

Rotation

1

Display the main menu.

2

Push the 

 button for 4 seconds. 

3

Use 

 to select the 

Rotation

 function and press 

.

4

Use  the  submenu  to 

Enable

  or 

Disable

 

Rotation

  and  to

configure the rotation cycle.

For  more  information  refer  to  the  detailed  installer  reference
guide

3

.

10. Airflow direction

1

/Individual air direction

For more information refer to the detailed user reference guide

3

.

11. Quick start (SkyAir only)

1

 

1

Display the 

Main Menu

 and proceed step (9) to display the basic

screen (Refer to 

"22. Main menu structure"

 and 

"Appendix"

).

2

Quick Start

 will appear on the basic screen when the Quick Start

function is turned ON.

12. Ventilation

Only in case an HRV is connected. Refer to the HRV manuals for
more information.

13. Energy saving options

For more information refer to the detailed user reference guide

3

.

14. Schedule

14.1 To enable/disable the schedule
1

Display the 

Enable/Disable setting

 screen (14.1) (Refer to 

"22. Main

menu structure"

 and 

"Appendix"

).

2

Use 

 to change the setting to 

Enable

 or 

Disable

.

3

Push 

 to display the confirmation screen.

4

Use 

 to select 

Yes

 and push 

.

14.2 To select the schedule number
1

Display  the 

Select Schedule

  screen  (14.2)  (Refer  to 

"22. Main

menu structure"

 and 

"Appendix"

).

2

Use 

 to change the setting to 

Schedule nr 1

Schedule nr 2

,

or 

Schedule nr 3

.

3

Push 

 to display the confirmation screen.

4

Use 

 to select 

Yes

 and push 

.

14.3 To use the holidays

The schedule timer will be disabled for the days that have been set
as holiday.

1

Display  the 

Holidays

  screen  (14.3)  (Refer  to 

"22. Main  menu

structure"

 and 

"Appendix"

).

2

Use 

 to select the desired day. Push 

 to display 

 to

set the holiday.

3

Push 

 to display the confirmation screen.

4

Use 

 to select 

Yes

 and push 

.

14.4 To change the schedule settings of the selected schedule nr

The schedule timer will be disabled for the days that have been set
as holiday.

1

Display  the 

Settings

  screen  (14.4)  (Refer  to 

"22. Main  menu

structure"

 and 

"Appendix"

).

2

Use 

 to select the desired day (1).

3

Use 

 to highlight the Operation start 

Time

 and 

 to set

the desired Operation start 

Time

 (2).

4

Use 

 to highlight the action and 

 to select the desired

Act

.

5

Use 

  to  highlight  the  temperature  and 

  to  select  the

desired value.

6

To set a different day of the week, use 

 to highlight the day.

Use 

 to change the day.

7

To copy all actions of the day previously set, push 

.

8

When the entire schedule settings are completed, push 

 to

display the confirmation screen.

9

Use 

 to select 

Yes

 and push 

.

15. Filter auto clean

This  function  is  available  only  on  the  model  whose  panel  has
automatic  cleaning  function  of  filter.  Needs  to  be  set  when
operation is OFF.

16. Maintenance information

1

Display the 

Maintenance Information

 screen (16) (Refer to 

"22. Main

menu structure"

 and 

"Appendix"

).

2

The phone number for the 

Contact info 

will appear at the top of the

screen. The model info of the 

Indoor unit

 and 

Outdoor unit

 of your

product will appear on the bottom of the screen.

3

Push 

 to return to the 

Main Menu

.

17. Configuration

17.1 To select quiet mode enable/disable
1

Display the 

Quiet Operation Mode

 settings screen.

2

Display  the 

Enable/Disable

  screen  (17.1)  (Refer  to 

"22. Main

menu structure"

 and 

"Appendix"

).

3

Use 

 to select 

Enable

 or 

Disable

.

4

Push 

 to display the confirmation screen.

5

Use 

 to select 

Yes

 and push 

.

17.2 To select quiet mode settings
1

Display the 

Quiet Operation Mode

 settings screen.

2

Display the 

Settings

 screen (17.2).

3

Use 

 to select the 

start

 or 

End time

.

Installation and

operation manual

3P419248-1-KA

OPERATION

Also  see  operation  manual  attached  to  the  outdoor  and
indoor unit.

WARNING

Do 

NOT

  play  with  the  unit  or  its  remote  controller.

Accidental operation by a child may result in impairment of
bodily functions and harm health.

WARNING

Never  disassemble  the  remote  controller.  Touching  the
interior  parts may  result  in electric  shocks or  fire. Consult
your  Daikin  dealer  or  authorized  contactor  for  internal
inspections and adjustments.

WARNING

To avoid electric shocks, do not operate with wet hands.

WARNING

Do 

NOT

  modify  or  repair  the  remote  controller.  This

may  result  in  electric  shocks  or  fire.  Consult  your
Daikin dealer.

Do 

NOT

 relocate or reinstall the remote controller by

yourself.  Improper  installation  may  result  in  electric
shocks or fire. Consult your Daikin dealer.

Do 

NOT

  use  flammable  materials  (e.g.  hairspray  or

insecticide)  near  the  product.  Do  not  clean  the
product  with  organic  solvents  such  as  paint  thinner.
The use of organic solvents may cause crack damage
to the product, electric shocks, or fire.

INFORMATION

This is the only button that works when the backlight is not
lit.

With icons

With icons and text (default)

With icons

With icons and text

Operation mode

cool

Heat

Vent

Air Clean

Fan

Dry

Auto (Cool)

Auto(Heat)

1

9
4

5

3

2

8

6

7

28

°C 

1

11

3

8

4

5

10

2

9

6

Heat 

Set   to 

28

°C 

Error: Push Menu button

1

11

3

8
7

4

5

10

2

9

6

F r i

11:03

14

13

15

12

16

F r i

11:03

Error: Push Menu button

Heat 

Set   to 

Room

14

13 

15

12

16

Return Setting 

a

c

Cool

Return

Set to

Cool

INFORMATION

When in 

Dry

 or 

Vent

 mode, the fan speed can not be set.

INFORMATION

When in 

Dry

 or 

Vent

 mode, the fan speed can not be set.

1.

This function is not compatible with SkyAir 
RR+RQ units.

2.

In case of a simultaneous operation system, the 
system is controlled by the sensing sensor 
mounted in the master indoor unit.

3.

The detailed user reference guide and installer 
reference guide are available on 

http://

www.daikineurope.com/support-and-manuals/
product-information/ 

.

Return

Setting

Return

Setting

Airflow level/direction

Level

Direction

Position 0

Low

3  4 

Cool

Return

Setting

Set to

Cool

4.

The schedule will not be available when a 
centralised controller or the BRP7A51 Digital 
Input Adapter is connected. 

INFORMATION

Repeat this procedure to turn 

Quick Start

 function off.

Return

Setting

Enable/Disable 

Schedule 

Disable

Setting

Select Schedule

Schedule

Schedule nr 1

Return

INFORMATION (Act column)

There are 3 types of operations:

1.

The temperature setpoints can be configured.

2.

The setback temperature setpoints can be configured.

3.

The  temperature  and  setback  temperature  setpoints
are disabled.

INFORMATION (Cool and Heat column)

__: Indicates  that  the  temperature  setpoint  for  cool/heat
and setback temperature setpoint for this time period is not
specified. The last active setpoint will be utilized.
-  -:  Indicates  that  the  setback  function  is  disabled  for  this
time period with action OFF.

Return

Setting

Schedule

Holidays
 Multiple Selection

Sun Mon Tue Wed Thu Fri Sat

(1)

Setting

Schedule nr 1

Mon

Time     Act     Cool     Heat

6

:00   

      

      

:

  

      

      

:

  

      

      

:

  

      

      

:

  

      

      

Return

(2)

Setting

Schedule nr 1

Mon

Time     Act     Cool     Heat

6 :00   

      

      

:

  

      

:

  

      

      

:

  

      

      

:

  

      

      

ON

OFF

1

2

3