3 About the box

Installation manual

8

2MXM-A, 3MXM-A, 4MXM-A, 5MXM-A

R32 Split series

3P600450-6M – 2021.12

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

Finishing the outdoor unit installation (see 

"8 Finishing the

outdoor unit installation"

 [

4

 16])

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn OFF the power supply before servicing.

▪ Install  the  switch  box  cover  before  turning  ON  the

power supply.

Commissioning (see 

"10 Commissioning"

 [

4

 17])

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When  performing  the  test  operation,  NOT  ONLY  the
outdoor unit, but the connected indoor unit will operate as
well.  Working  on  an  indoor  unit  while  performing  a  test
operation is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

Maintenance and service (see 

"11 Maintenance and

service"

 [

4

 19])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

WARNING

▪ Before  carrying  out  any  maintenance  or  repair  activity,

ALWAYS  switch  off  the  circuit  breaker  on  the  supply
panel, remove the fuses or open the protection devices
of the unit.

▪ Do NOT touch live parts for 10 minutes after the power

supply is turned off because of high voltage risk.

▪ Please  note  that  some  sections  of  the  electric

component box are hot.

▪ Make sure you do NOT touch a conductive section.

▪ Do NOT rinse the unit. This may cause electric shocks

or fire.

DANGER: RISK OF ELECTROCUTION

▪ Use this compressor on a grounded system only.

▪ Turn the power off before servicing the compressor.

▪ Reattach  the  switch  box  cover  and  service  lid  after

servicing.

CAUTION

ALWAYS wear safety glasses and protective gloves.

DANGER: RISK OF EXPLOSION

▪ Use a pipe cutter to remove the compressor.

▪ Do NOT use the brazing torch.

▪ Use approved refrigerants and lubricants only.

DANGER: RISK OF BURNING/SCALDING

Do NOT touch the compressor with bare hands.

3

About the box

3.1

Outdoor unit

3.1.1

To remove the accessories from the
outdoor unit

1

Lift the outdoor unit.

2

Remove  the  accessories  from  the  unit  (under  service  cover)
and from the bottom of the package.

a

b

c

d

e

i

j

g

h

f

a

Outdoor unit installation manual

b

General safety precautions

c

Fluorinated greenhouse gases label

d

Multilingual fluorinated greenhouse gases label

e

Energy label

f

Screw bag. The screws will be used for fixing the
electrical wire anchor bands.

g

Drain cap (small)

h

Drain cap (large)

i

Reducer assembly

j

Drain socket

4

Unit installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

4.1

Preparing the installation site

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

4.1.1

Installation site requirements of the
outdoor unit

Mind the following spacing guidelines:

Содержание 3MXM40A2V1B

Страница 1: ...Installation manual R32 Split series English Installation manual R32 Split series 2MXM68A2V1B 3MXM40A2V1B 3MXM52A2V1B 3MXM68A2V1B 4MXM68A2V1B 4MXM80A2V1B 5MXM90A2V1B...

Страница 2: ...ringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directive...

Страница 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Страница 4: ...kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respectiv...

Страница 5: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Страница 6: ...mmissioning 18 10 2 Checklist during commissioning 18 10 3 Trial operation and testing 18 10 3 1 About wiring error check 18 10 3 2 To perform a test run 19 10 4 Starting up the outdoor unit 19 11 Mai...

Страница 7: ...sor is run air will be sucked in This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Do NOT open the valves before flaring is comp...

Страница 8: ...y is turned off because of high voltage risk Please note that some sections of the electric component box are hot Make sure you do NOT touch a conductive section Do NOT rinse the unit This may cause e...

Страница 9: ...ating mode 10 46 C DB 15 24 C DB 4 1 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor un...

Страница 10: ...drain socket a c b b b a a a Drain hole Install a drain cap large b Drain hole Install a drain cap small c Drain hole for drain socket 5 Piping installation 5 1 Preparing refrigerant piping 5 1 1 Ref...

Страница 11: ...r the refrigerant piping the better the performance of the system The piping length and height differences must comply with the following requirements Shortest allowable length per room is 3 m Outdoor...

Страница 12: ...ucer no 1 c Reducer no 3 d Flare nut for 15 9 mm e Inter unit piping Connecting a 9 5 mm pipe to a 15 9 mm gas pipe connection port a b d e c a Outdoor unit connection port b Reducer no 6 c Reducer no...

Страница 13: ...e on the manifold indicates 0 1 MPa 1 bar 2 Leave as is for 4 5 minutes and check the pressure If the pressure Then Does not change There is no moisture in the system This procedure is finished Increa...

Страница 14: ...ALWAYS use protective gloves and safety glasses Prerequisite Before charging refrigerant make sure the refrigerant piping is connected and checked leak test and vacuum drying 1 Connect the refrigerant...

Страница 15: ...epending on the model 7 1 Specifications of standard wiring components Component Power supply cable Voltage 220 240 V Phase 1 Frequency 50 Hz Wire type See table below A Interconnection cable indoor o...

Страница 16: ...ng 9 1 1 To turn ON standby electricity saving function Prerequisite The main power supply MUST be turned OFF 1 Remove the service cover 2 Disconnect the selective standby electricity saving connector...

Страница 17: ...2 Set the heat mode lock switch SW5 1 to ON 1 1 4 3 2 1 A 1 2 3 4 5 SW5 4 3 2 1 2 OFF ON 9 5 About cool mode lock Cool mode lock limits the unit to cool operation Forced operation remains possible in...

Страница 18: ...For more information see the indoor unit installation manual and or the indoor installer reference guide Before starting the test run measure the voltage at the primary side of the safety breaker The...

Страница 19: ...of the system 11 Maintenance and service NOTICE General maintenance inspection checklist Next to the maintenance instructions in this chapter a general maintenance inspection checklist is also availa...

Страница 20: ...umber of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board Symbol Meaning PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar trans...

Страница 21: ...A r B s s t t u u d p o o n l l m l w x v A v B v A v B q h 2MXM68 a Heat exchanger k 4 way valve u Thermistor gas b Outdoor air temperature thermistor l Muffler v Room c Heat exchanger thermistor m...

Страница 22: ...2 7CuT 12 7CuT 12 7CuT 12 7CuT 15 9CuT 15 9CuT 15 9CuT 7 9CuT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH d e f...

Страница 23: ...5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 7 9CuT MVD 6 4CuT 15 9CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9...

Страница 24: ...12 7CuT 15 9CuT 9 5CuT 9 5CuT 9 5CuT d e f k a a b c g i j d r A r B r C r D r E s t s t s t s t s t v A v A v B v C v D v E v B v C v D v E u u u u u d p o o n l m l l w x q h y y 5MXM90 a Heat excha...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...3P600450 6M 2021 12 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: