Field Settings
SiUS121630EA
222
Trial Operation and Field Settings
5.3.2 Overview of the Field Settings
: factory setting
Note:
Any function that is not available on the indoor unit is not displayed.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
05
06
10
(20)
0
Filter cleaning
sign interval
Longlife
filter
Li
ght
Approx.
2,500
hrs.
H
eav
y Approx.
1,250
hrs.
—
—
—
—
2
Remote controller thermistor
Enabled
Disabled
—
—
—
—
3
Filter cleaning sign
Display
No display
—
—
—
—
12
(22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Compressor
—
Operation
output
Error output
Outdoor air
intake
Presence
sensor
13
(23)
0
High air outlet velocity (for high
ceiling applications)
≤
2.7 m
(
≤
8-7/8 ft)
2.7 ~ 3.0 m
(8-7/8~9-13/16 ft)
3.0 ~ 3.5 m
(9-13/16~11-1/2 ft)
—
—
—
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow
3-way flow
2-way flow
—
—
—
4
Airflow direction range setting
Upper
Normal
Lower
—
—
—
15
(25)
3
Drain pump operation with
humidifying
Not equipped
Equipped
—
—
—
—