8 Finishing the outdoor unit installation
Installation manual
18
3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
3P600450-1D – 2020.08
8
Finishing the outdoor unit
installation
8.1
To finish the outdoor unit
installation
DANGER: RISK OF ELECTROCUTION
▪ Make sure that the system is earthed properly.
▪ Turn off the power supply before servicing.
▪ Install the switch box cover before turning on the power
supply.
1
Insulate and fix the refrigerant piping and cables as follows:
g
b
a
f
e
c
d
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Field wiring (if applicable)
e
Liquid pipe
f
Liquid pipe insulation
g
Finishing tape
2
Install the service cover.
9
Configuration
9.1
About standby electricity saving
function
The standby electricity saving function:
▪ turns OFF the power supply to the outdoor unit and,
▪ turns ON the standby electricity saving mode on the indoor unit.
The standby electricity saving function works with following units:
3MXM40, 3MXM52, 3AMXM52
FTXM, FTXP, FTXJ, FVXM
If another indoor unit is used, the connector for standby electric
saving must be plugged in.
The standby electricity saving function is turned off before shipping.
9.1.1
To turn on standby electricity saving
function
Prerequisite:
The main power supply MUST be turned off.
1
Remove the service cover.
2
Disconnect the selective standby electricity saving connector.
3
Turn on the main power supply.
9.2
About priority room function
INFORMATION
▪ The priority room function requires initial settings to be
made during the installation of the unit. Ask the
customer in which rooms he plans to use this function
and make the necessary settings during installation.
▪ The priority room setting is only applicable for an air
conditioner indoor unit and only one room can be set.
The indoor unit for which the priority room setting is applied takes
priority in the following cases:
▪
Operation mode priority:
If the priority room function is set on an
indoor unit, all other indoor units enter the standby mode.
▪
Priority during high-power operation:
If the indoor unit on which
the priority room function is set operates at high power, the other
indoor units will run with reduced capabilities.
▪
Quiet operation priority:
If the indoor unit on which the priority
room function is set to quiet operation, the outdoor unit will also
run quietly.
Ask the customer in which rooms he plans to use this function and
make the necessary settings during installation. Setting it in the
guest rooms is convenient.
9.2.1
To set the priority room function
1
Remove the switch cover on the service PCB.
2
Set the switch (SW4) for the indoor unit for which you want to
activate the priority room function to ON.
E
D
C
B
A
E
D
C
B
A
A
1
2
3
4
5
1×
SW4
OFF
ON
2
1
3
Reset the power.
9.3
About night quiet mode
The night quiet mode function makes the outdoor unit run more
quietly at nighttime. This will reduce the cooling capacity of the unit.
Explain Night quiet mode to the customer and confirm if customer
wants to use this mode.
9.3.1
To turn on the night quiet mode
1
Remove the switch cover on the service PCB.