Part 2. Troubleshooting
2.2. Error based troubleshooting
4/04/17
|
Version 1.1
Page 31
RA R32 Split & multi split M-Series
2.2.2.12. “H8-00” – Compressor input (CT) system abnormality
2.2.2.13. “H9-00” – Outdoor air temperature thermistor abnormality
Faulty outdoor inverter PCB.
Check outdoor inverter PCB.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Restore the power to the outdoor inverter
PCB.
Replace the outdoor inverter PCB when
required.
Stop valve is closed.
Check stop valve.
Open stop valve when required.
Faulty or disturbance of the power supply
(imbalance > 10%). Power drop. Short cir-
cuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
Trigger
Effect
Reset
DC voltage or DC current sensor abnor-
mality based on the compressor running
frequency and the input current.
Unit will not stop operating.
Automatic reset when compressor runs
normally for 60 minutes.
Unit will stop operating if the warning
occurs several times.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty outdoor unit main PCB.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Restore the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals.
Faulty power module.
Input current or compressor current too
low.
Faulty outdoor inverter PCB.
Check outdoor inverter PCB.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Restore the power to the outdoor inverter
PCB.
Replace the outdoor inverter PCB when
required.
Faulty compressor.
Check compressor.
Check connections and wiring of the com-
pressor.
Check expansion valve (liquid back
issue).
Check the refrigerant charge. Refer to the
nameplate for correct charge.
Replace compressor when required.
Investigate reason of breakdown.
Replace expansion valve when required.
Fix possible leak.
Faulty reactor.
Check reactor.
Replace reactor when required.
Trigger
Effect
Reset
Thermistor input voltage is > 4.96 V or
< 0.04 V when power is on.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty outdoor air temperature thermistor.
Check outdoor temperature thermistor.
Replace outdoor temperature thermistor
when required.
Faulty outdoor unit main PCB.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Restore the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals.
Possible cause
Check
Corrective action