Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChWPump
McQuayChill
er
SNVT_switch
95
two bytes
Valid Range
State
Value
Pump Status
0
unused
Pump Off Request
1
unused
Pump On Request
Evaporator Water Flow Rate
This read only network variable indicates the rate of water flow through the evaporator.
Measurement
Units
Data Type
Usable Range
Default Value
Flow Volume
BACnet:
GPM or L/s
L
ON
W
ORKS
:
CFM
OR
L/
S
BACnet: Real
L
ON
W
ORKS
: Fixed Point
Scalar unsigned long
BACnet:0-10,001.55 GPM
0-631 L/S
L
ON
W
ORKS
:
0 to 1337.01
CFM (0 to 631 L/s)
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
148
Present Value
85
Object Name
EvapWaterFlowRate
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoEvapFlowRate McQuayChiller
SNVT_flow
15
two
bytes
File Directory Address
This read only network variable reports the starting address of the configuration-file directory on a
Neuron hosted device. It is used when configuration properties are implemented within configuration
files accessed by ANSI/EIA/CEA-709.1- Read Memory and Write Memory Network-Management
Messages.
Measurement
Units
Data Type
Usable Range
Default Value
Neuron Chip
Address
16-bit address
value
L
ON
W
ORKS
: unsigned long
16,384…64,767 NA
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoFileDirectory Node
SNVT_address
114
two
bytes
Heat Recovery Entering Water Temperature
This read only network variable indicates the temperature of the water entering the heat recovery
section of the condenser.
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar
-40 to 257°F
-40 to 125°C
NA