      Four-door One-way Access 

Controller 

 

User’s Manual 

 

V1.0.0

 

Содержание DHI-ASC1204B

Страница 1: ...Four door One way Access Controller User s Manual V1 0 0 ...

Страница 2: ...egularly change the credentials to your devices to help ensure that only authorized users are able to access the system 2 Change Default HTTP and TCP Ports Change default HTTP and TCP ports for systems These are the two ports used to communicate and to view video feeds remotely These ports can be changed to any set of numbers between 1025 65535 Avoiding the default ports reduces the risk of outsid...

Страница 3: ...tem is set up for multiple users ensure that each user only has rights to features and functions they need to use to perform their job 10 UPnP UPnP will automatically try to forward ports in your router or modem Normally this would be a good thing However if your system automatically forwards the ports and you leave the credentials defaulted you may end up with unwanted visitors If you manually fo...

Страница 4: ...eras to the PoE Ports on the Back of an NVR Cameras connected to the PoE ports on the back of an NVR are isolated from the outside world and cannot be accessed directly 16 Isolate NVR and IP Camera Network The network your NVR and IP camera resides on should not be the same network as your public computer network This will prevent any visitors or unwanted guests from getting access to the same net...

Страница 5: ...hese limits are designed to provide reasonable protection against harmful interference in a commercial environment Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense For class B device these limits are designed to provide reasonable protection against harmful interference i...

Страница 6: ...ight collect personal data of others such as face fingerprints car plate number Email address phone number GPS and so on You need to be in compliance with the local privacy protection laws and regulations to protect the legitimate rights and interests of other people by implementing measures including but not limited to providing clear and visible identification to inform data subject the existenc...

Страница 7: ...rations description or errors in print If there is any doubt or dispute please refer to our final explanation Upgrade the reader software or try other mainstream reader software if the Guide in PDF format cannot be opened All trademarks registered trademarks and the company names in the Manual are the properties of their respective owners Please visit our website contact the supplier or customer s...

Страница 8: ...nput and output range Please don t dismantle the device arbitrarily Please transport use and store the device within allowed humidity and temperature range Power Requirement Please make sure to use batteries according to requirements otherwise it may result in fire explosion or burning risks of batteries To replace batteries only the same type of batteries can be used The product shall use electri...

Страница 9: ...dd Access Controller 12 3 2 1 Auto Search 12 3 2 2 Manual Add 14 3 3 Add User 16 3 3 1 Card Type 17 3 3 2 Single Add 18 3 4 Add Door Group 20 3 5 Authorize 22 3 5 1 Authorize According to Door Group 22 3 5 2 Authorize According to User 23 4 FAQ 25 1 Question After power on power indicator doesn t turn on or the buzzer doesn t respond 25 2 Question After the reader is connected with the device card...

Страница 10: ...Table of Contents IX 5 Technical Parameters 26 ...

Страница 11: ...alarm 1 Support 5 groups of control output electric lock 4 and alarm output 1 With RS485 port it may extend to connect control module FLASH storage capacity is 16M which may extend to 32M Support max 100 000 card holders and 150 000 card reading records Support illegal intrusion alarm unlock timeout alarm duress card and duress code setup Also support black white list and patrol card setup Support...

Страница 12: ...Overview 2 Figure 1 2 ...

Страница 13: ...lock and reader is shown in Figure 2 1 Figure 2 1 2 2 Device Installation There are two installation modes Mode 1 fix the whole device onto the wall with screws Mode 2 with U shaped guide rail hang the whole device onto the wall the U shaped guide rail is an optional fitting Mode 1 Installation diagram is shown in Figure 2 2 ...

Страница 14: ...into upper groove of the U shaped guide rail Step 3 Push the snap joint at the bottom of the device upwards The installation is completed when you hear the fitting sound 2 3 Disassembly If the device is installed with mode 2 please disassemble it according to Figure 2 4 Align a screwdriver with the snap joint press it down and the snap joint will pop up so the whole device can be disassembled smoo...

Страница 15: ...ve an alarm Device wiring diagram is shown in Figure 2 5 Figure 2 5 Interfaces are described in Table 2 1 Table 2 1 No Port Description No Port Description 1 RS485 communication 7 Reader of door 1 2 Exit button and door contact 8 Reader of door 2 3 Alarm input output 9 Reader of door 3 4 Lock control output 10 Reader of door 4 5 DIP switch 11 Reboot 6 TCP IP software platform port 12 DC 12V power ...

Страница 16: ... and door contact are shown in Figure 2 6 Please refer to Table 2 3 for descriptions of wiring terminals Figure 2 6 Table 2 3 Port Wiring Terminal Description Exit button door contact PUSH1 Exit button of door 1 GND Shared by exit button of door 1 and door contact input of door 1 SR1 Door contact input of door 1 PUSH2 Exit button of door 2 GND Shared by exit button of door 2 and door contact input...

Страница 17: ...by exit button of door 4 and door contact input of door 4 SR4 Door contact input of door 4 2 4 3 Wiring Description of Lock Support 4 groups of lock control outputs serial numbers after the terminals represent corresponding doors Please choose a proper connection mode according to lock type as shown in Figure 2 7 Figure 2 8 and Figure 2 9 Please refer to Table 2 4 for descriptions of wiring termin...

Страница 18: ...r only supports to connect one type of reader 485 or Wiegand Please refer to Table 2 5 for descriptions of wiring terminals corresponding to readers Take door 1 for example other readers are the same Please refer to Table 2 6 for descriptions of reader cable specification and length Table 2 5 Port Wiring Terminal Cable Color Description Entry Reader of Door 1 485 Purple 485 reader 485 Yellow LED B...

Страница 19: ...xternal alarm input ports are able to connect smoke detector and IR detector etc When external alarm is triggered all doors are linked to be normally open GND 2 4 6 Wiring Description of Alarm Output With 1 ch alarm output after internal alarm input such as door timeout or external alarm input triggers an alarm the alarm output device gives an alarm for 15s There are two connection modes of alarm ...

Страница 20: ...fer to Table 2 9 for detailed alarm input and output rules Table 2 9 Alarm Type Alarm Event Alarm Signal Input Port Alarm Signal Output Port Alarm Status External alarm input Trigger no 1 alarm detector ALM1 OUT1 No 1 alarm gives an alarm and links all doors to be normally open Internal alarm input Intrusion alarm or unlock timeout alarm of no 1 door SR1 OUT1 No 1 alarm gives an alarm Intrusion al...

Страница 21: ...ing 1 the switch is at the bottom meaning 0 1 8 are all 0 the system is started normally 1 8 are all 1 the system enters BOOT mode after start 1 3 5 and 7 are 1 while others are 0 After reboot the system restores factory defaults 2 4 6 and 8 are 1 while others are 0 After reboot the system restores factory defaults but user info is retained 2 6 Reboot Insert a needle into reboot hole press it once...

Страница 22: ...orts for different versions Please refer to actual port 3 1 Login Client Install the matching Smart PSS client and double click to run Carry out initialization configuration according to interface prompts and complete login 3 2 Add Access Controller Add access controller in Smart PSS select Auto Search and Add 3 2 1 Auto Search Devices are required to be in the same network segment Step 1 In Devic...

Страница 23: ...ecific operations please refer to User s Manual of Smart PSS Client Step 3 Select the device that needs to be added and click Add The system pops up Prompt Step 4 Click OK The system displays Login Information dialogue box as shown in Figure 3 3 Figure 3 3 Step 5 Input User Name and Password to log in the device and click OK The system displays the added device list as shown in Figure 3 4 Please r...

Страница 24: ...me port user name and password Alternatively double click the device to enter Modify Device interface Click this icon to enter Device Config interface and configure device camera network event storage and system info and When the device is online the icon is Click this icon to exit login and this icon turns to When the device is offline the icon is Click this icon to login with correct device info...

Страница 25: ... fill in according to actual conditions Group Name Select the group of the device User Name and Password User name and password of the device Step 3 Click Add to add a device The system displays the added device list as shown in Figure 3 4 Please refer to Table 3 1 for operation interface Doors of the added controller are displayed under Access tab as shown in Figure 3 7 To add more devices click ...

Страница 26: ...Smart PSS Config 16 Figure 3 7 3 3 Add User Add users and bind with cards so as to distribute authority In New interface click Access to enter Access interface and complete access config here ...

Страница 27: ...g 17 Figure 3 8 3 3 1 Card Type Card type shall be the same with card issuer otherwise it fails to read card number In Access interface click and then click to set the card type as shown in Figure 3 9 and Figure 3 10 ...

Страница 28: ...igure 3 9 Figure 3 10 3 3 2 Single Add Add a single user send a card and input user info Step 1 In Access interface click and then click as shown in Figure 3 11 The system pops up Add User dialog box as shown in Figure 3 12 ...

Страница 29: ...Smart PSS Config 19 Figure 3 11 Figure 3 12 Step 2 Add user info manually including basic info fingerprint info and details Please refer to Table 3 3 for details ...

Страница 30: ...se it only applies to guest card Valid Time set the valid time of card which is 10 years by default Picture user picture max 120K Card no and user ID cannot be repeated Fingerprint Info Collect fingerprints with fingerprint reader and access reader Max 2 fingerprints for every person Support to enter fingerprint name Details Fill in detailed user info according to interface parameters Step 3 Click...

Страница 31: ...Smart PSS Config 21 Figure 3 13 Step 2 Click Add The system pops up Add Door Group dialog box as shown in Figure 3 14 Figure 3 14 ...

Страница 32: ... to Door Group Select a door group add corresponding users to the group so all users in the group obtain authority of all doors in the group Step 1 In Access interface click and then click Access Level as shown in Figure 3 15 Figure 3 15 Step 2 Click The system pops up User Select dialog box Step 3 Select the user s department from dropdown list or enter the user s ID or name directly as shown in ...

Страница 33: ...ization The search list filters user info without card number In the user list cancel the added user and delete the user s authority 3 5 2 Authorize According to User Select a user distribute door group and grant door group authority to the user Step 1 In Access interface click and then click User Right as shown in Figure 3 17 ...

Страница 34: ...Smart PSS Config 24 Figure 3 17 Step 2 Click The system pops up Select Door Group dialog box as shown in Figure 3 18 Figure 3 18 Step 3 Select the door group and click OK to finish authorization ...

Страница 35: ...tect the device Answer Please check whether TCP IP connector is connected properly and whether device IP is in the same network segment 4 Question After swiping card it prompts that card is invalid Answer Please check whether this card number has been added in the controller 5 Question Default IP of access controller Answer Default IP address is 192 168 0 2 6 Question Default port initial user nam...

Страница 36: ... of connected reader 4 groups Working power supply Rated voltage 10V 15V DC rated current 0 75A Period 128 Holiday 128 Unlocking mode Card card password password card or password card fingerprint fingerprint password fingerprint or card or password by period Cross segment networking Support Two door interlocking Support Real time surveillance Support Fire alarm linkage Support Tamper alarm Support...