Earthing
313
more than 4mm
2
.
The monitor system usually can adopt the one-point ground.
Please connect the ground end of 3-pin socket in the monitor system to the ground port of
the system (protection ground cable)
Appendix 7.4 The Shortcut Way to Check the Electric
System by Digital Multimeter
For 220V AC socket, from the top to the bottom, E (ground cable), N (neutral cable), L(live
cable). Please refer to the following figure.
There is a shortcut way to check these thee cables connection are standard or not (not the
accurate check).
In the following operations, the multimeter range shall be at 750V.
For E (earth cable)
Turn the digital multimeter to 750V AC, use your one hand to hold the metal end, and then the
other hand insert the pen to the E port of the socket. See the following figure. If the multimeter
shows 0, then you can see current earth cable connection is standard. If the value is more than
10, then you can know there is inductive current and the earth cable connection is not proper.
Содержание XVR4 Series
Страница 1: ...DIGITAL VIDEO RECORDER User s Manual V1 1 0 ZHEJIANG DAHUA VISION TECHNOLOGY CO LTD ...
Страница 42: ...The Grand Tour 29 Operation Function selection box with left mouse button Select privacy mask zone Table 3 20 ...
Страница 44: ...Connecting Basics 31 Figure 4 2 ...
Страница 96: ...Local Configurations 83 Figure 5 50 ...
Страница 197: ...Local Configurations 184 Figure 5 153 Figure 5 154 Double click the video or click Step 7 ...
Страница 202: ...Local Configurations 189 Figure 5 158 Figure 5 159 ...
Страница 310: ...Glossary 297 Abbreviations Full term VGA Video Graphics Array WAN Wide Area Network ...
Страница 328: ...Earthing 315 ...