4.
SUPER
- Rotate TEMP. CONTROL Dial and make Super Location
ON POINT: 0.05°C
OFF POINT: -2.95°C
5.
DETERMINATION
OF
DEFROST
- Starting condition of Defrost Mode
- When accumulated running time of comp. is 8, 10, 12, 18, 30hrs.
- After Checking the condition ‘2.1’ if total time(COMP on time + COMP off time) is
more than 24, 48, 36, 72hrs, then defrost mode starts immediately.
Accumulated running time of
COMP
Total running time of COMP
RT-SENSOR
Door Open
Door Close
Door Open
Door Close
RT 29°C Up
8HR
18HR
24HR
36HR
20<RT< 28°C
12HR
30HR
48HR
72HR
15<RT< 19°C
8HR
12HR
24HR
36HR
RT 14°C Down
8HR
10HR
24HR
36HR
6.
DEFROST
MODE
1) General Defrost Mode
1.1- Start : By determination of defrost
1.2- Process : General operation - Heater on - Pause (6min) - General operation
-Heater defrost : When the temperature at D-sensor is over 10°C, heater turns
off.
-Limit time : 80 min (30 min on D sensor error)
2) Forced Defrost Mode
2.1 Start : Button of M -PCB(SW2) is pushed 1 Time.
2.2 Process : same as General Defrost Mode
-Heater is supposed to be on Initial 30 seconds. (for TEST)
7.
INITIAL
DEFROST
1) When power is on, if the temperature at the D-sensor is under 3.5°C, then General
Defrost Mode starts.
2) When initial defrost mode starts, heater will be on directly and defrost mode will be
started.
8.
PREVENTION
OF COMP.
RESTART
COMP. doesn’t work after COMP. turns off even though R-sensor is on condition. (This
is to protect comp.)
1) General operation : The COMP can’t be on within 6 min.
2) Operation of LOW RT : The COMP can’t be on within 40 min.
33
Содержание ERF-366A
Страница 5: ...3 REAL VIEW 4...
Страница 6: ...4 MACHINE ROOM VIEW 5 SCREW MACHINE...
Страница 7: ...5 REFRIGERANT CYCLE 6 CAPILLARY TUBE...
Страница 9: ...7 WIRING DIAGRAMS 8 7 1 ERF XX6A...
Страница 10: ...7 2 ERF XX6N 9...
Страница 11: ...8 PCB CIRCUIT DIAGRAMS 10 8 1 ERF XX6A...
Страница 12: ...8 2 ERF XX6N 11...
Страница 21: ...11 EXPLODE DRAWING 20...
Страница 22: ...21...