If one of following conditions is satisfied, end the defrost and turn into heating mode: 
a. The defrost time has reached to 10 minutes. 
b. When the temperature of outdoor heat exchanger rises up to 15°C.   

3. Defrosting Actions:   

a. Compressor runs. 
b. 4 way valve switches off, 
c. Outdoor fan switches off 
d. Indoor fan running according to anti-cold wind function in heating mode. 

4. Automatic operation mode   

The air conditioner automatically selects one of the following operation modes: cooling, 
heating or fan only according to the temp. difference between room temp. (TA) and set 
temp. (TS). 

TA—TS Operation 

mode 

TA—TS>2

 Cooling 

-1

TA

-TS

+2

 Fan-only 

TA-TS<-1

 

Heating (air-only for cooling only type) 

7.3 Mode conflict 

The indoor units can not work cooling mode and heating at same time.   
Heating mode has a priority. 
7.3.1 Definition  

 

Cooling mode 

Heating Mode 

Fan 

Off 

Cooling mode 

No 

Yes 

No 

No 

Heating Mode 

Yes 

No 

Yes 

No 

Fan No  Yes 

No 

No 

Off 

No No 

No 

No 

No: No mode conflict; 
Yes: Mode conflict 
7.3.2  In case of one Indoor unit working in cooling mode or fan mode, and another indoor 

unit is set to heating mode, the indoor unit working in cooling mode or fan mode will 
change to stand by. The outdoor unit will work in heating mode. 

7.3.3  In case of one Indoor unit working in heating mode, and another indoor unit is set to 

cooling mode or fan mode, the indoor unit setting to cooling mode or fan mode will 
change to stand by. 

 

7.4 Manual switch   

Mode changes when push this button. 
Cooing mode

Æ

 Auto mode

Æ

Unit off

Æ

 Cooing mode 

At Cooing mode, after 30 minutes cooling operation whose fan speed is set as low, the 
A/C operates with a setting temp. of 24

.  

At auto mode, the A/C operates with a set temp. of 24

   

7.5 Timer Function   

Содержание DTB-F071LH-DVI

Страница 1: ...1 Service Manual Split System Air Conditioner Model DTB F071LH DVI DTB F091LH DVI DTB F121LH DVI DTB F181LH DVI DMB F2713LH AVO DAEWOO ELECTRONICS CO LTD by Nemko S M NO DTBF071001...

Страница 2: ...CONTENTS 1 Features 2 Specification 3 Outline and dimension 4 Indoor unit combination 5 Capacity table 6 Wiring diagram 7 Electronic control functions...

Страница 3: ...1 Features 1 Fashion design quality life 2 Low operation noise 3 High efficiency screw fan 4 Equal fast wide angle cooling more comfortable...

Страница 4: ...itch b mm 21x13 37 21x13 37 21x13 37 21x13 37 c Fin spacing mm 1 3 1 3 1 3 1 3 d Fin type code Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium e Tube outside di...

Страница 5: ...650x30x650 650x30x650 650x30x650 Packing W H D mm 715x115x715 715x115x715 715x115x715 715x115x715 Indoor unit panel Net Gross weight panel Kg 3 5 3 5 3 5 3 5 Application area m2 10 14 14 21 18 26 35...

Страница 6: ...00 27000 21000 30000 32000 Rated input power range W 1100 2430 1400 2520 2020 2950 2982 Heating Rated current range A 5 0 11 6 6 4 12 0 9 3 13 8 13 9 Max input consumption W 4500 Max current A 25 Mode...

Страница 7: ...W H D mm 1043X915X395 Outdoor unit Net Gross weight Kg 80 84 Refrigerant type and charge g R410A 2700 Design pressure Hi Lo MPa 4 2 2 5 Liquid side Gas side mm inch 6 35 1 4 9 53 3 8 Max refrigerant...

Страница 8: ...inal heating capacities are based on the following conditions Indoor temp 20 CDB Outdoor temp 7 CDB 6 CWB Equivalent ref Piping 8m horizontal 8 Actual noise level may differ depending on the room stru...

Страница 9: ...8k 580 Body 67 600 Ceiling hole 650 Panel 401 Hook location 611 Hook location 580 Body 422 28 5 600 Ceiling hole 650 Panel Drain side and Tubing side A 600 Hook 265 Panel Chart 4 Body Nut Ceiling Outd...

Страница 10: ...r this condition the single indoor unit capacity will attenuate That means you can not gain the nominal capacity but smaller than it We are out of responsibility if customers don t follow the notice b...

Страница 11: ...9 63 9 09 8 72 8 45 Sensitive capacity kW 8 36 7 99 7 70 7 27 6 98 6 76 32 C D 23 C W Input kW 2 50 2 85 3 21 3 57 3 92 4 28 HEATING OUTDOOR CONDITIONS Indoor Conditions 24 C D 18 C W 12 C D 11 C W 7...

Страница 12: ...6 WIRING DIAGRAM Indoor unit...

Страница 13: ...Outdoor unit M4OA 27HRIN1...

Страница 14: ...25A the compressor stops 9 Outdoor condenser high temperature protection Under cooling mode if T3 65 for 3 minutes the compressor will stop When T3 52 the protection is not valid 10 Outdoor low tempe...

Страница 15: ...T Indoor exchanger temp Indoor fan speed T 34 Off 34 T 37 Breeze 37 T 44 Low speed Indoor exchanger temp up T 44 Setting fan speed T 38 Setting fan speed 33 T 38 Low speed 24 T 33 Breeze Indoor excha...

Страница 16: ...ating at same time Heating mode has a priority 7 3 1 Definition Cooling mode Heating Mode Fan Off Cooling mode No Yes No No Heating Mode Yes No Yes No Fan No Yes No No Off No No No No No No mode confl...

Страница 17: ...automatically sets the unit to previous settings before the power failure when power returns 7 7 Cooling capacity test frequency locked When test the cooling capacity the frequency can be locked at 78...

Страница 18: ...oor communication error P0 Compressor top protection against temperature P1 High pressure protection P2 Low pressure protection P3 Compressor current protection P4 Inverter module protection P5 Outdoo...

Страница 19: ...speed is controlled according ambient temp After the compressor stop 30 seconds later the fan stop When cooling 27 High speed Ambient temp rise 27 Low speed 25 High speed Ambient temp decline 25 Low s...

Страница 20: ...8 Exploded View...

Страница 21: ...ONICS CO LTD 686 AHYEON DONG MAPOGU SEOUL KOREA C P O BOX 8003 SEOUL KOREA TELEX DWELEC K28177 8 CABLE DAEWOOELEC FAX 82 2 364 5588 TEL 82 2 360 7114 8114 http www dwe co kr S M NO DTBF071001 PRINTED...

Отзывы: