52
2
Table of Suction Pressures according to the
change of Outdoor Room Temp.
MODEL
DSB-071AH
DSB-092AH
DSB-093AH
DSB-123AH/PH
DSB-183AH/PH
DSB-240AH-R/PH-R
REFRIGERANT
850g
800g
730g
1200g
1400g
1900g
INDOOR ROOM
TEMP.(DB/WB, °C)
27.0/19.0
27.0/19.0
27.0/19.0
27.0/19.0
27.0/19.0
27.0/19.0
OUTDOOR ROOM
TEMP.(DB/WB, °C)
25.0 / –
30.0 / –
35.0 / –
40.0 / –
45.0 / –
25.0 / –
30.0 / –
35.0 / –
40.0 / –
45.0 / –
25.0 / –
30.0 / –
35.0 / –
40.0 / –
45.0 / –
25.0 / –
30.0 / –
35.0 / –
40.0 / –
45.0 / –
25.0 / –
30.0 / –
35.0 / –
40.0 / –
45.0 / –
25.0 / –
30.0 / –
35.0 / –
40.0 / –
45.0 / –
Bar (gage)
4.77
5.02
5.21
5.31
5.44
4.19
4.42
4.49
4.58
4.77
4.42
4.69
4.91
5.05
5.19
3.73
3.99
4.25
4.43
4.54
4.16
4.31
4.40
4.52
4.71
3.90
4.10
4.29
4.49
4.69
kPa, (gage)
477.6
502.1
520.7
530.5
544.3
419.7
422.3
449.1
457.9
476.6
442.3
468.8
491.3
505.0
518.8
372.7
399.1
424.6
443.3
454.0
415.8
431.5
440.3
452.1
470.7
390.3
409.9
429.5
449.1
469.7
NOTE)
1) These experiments are processed on the condition of the fixed indoor room TEMP.( DB: 27.0°C, WB: 19.0°C)
2) It takes at least ten minutes for the change of suction pressure to be steady-state, after Air conditioner operates
3) To analyze accurately whether refrigerant of Air conditioner leaks or not, you have to check not only suction
pressure but also discharge and suction temperature of compressor
4) These data can be changed slightly according to the temperature of environment or each set(Air conditioner)
Содержание DSB-071AH
Страница 17: ...16 DSB 093AH 123AH 123PH...
Страница 42: ...The Circuit Diagram of Oxygen Generation System 41...
Страница 43: ...42 The Circuit Diagram of Plasma System...
Страница 46: ...45 4 WIRING DIAGRAM Indoor Unit...
Страница 47: ...46...
Страница 48: ...47...
Страница 49: ...48 Outdoor Unit...
Страница 50: ...49...
Страница 52: ...51 Note If the pipe length exceeds the standard length add 30g of refrigerant per extra meter Heat Pump Model...
Страница 63: ...PCBDRIVINGDESCRIPTION...
Страница 64: ...63 1 PCB CIRCUIT DIAGRAM DSB 071AH...
Страница 65: ...3 Heat Pump Model Only...
Страница 66: ...64 DSB 093AH 123AH 123PH...
Страница 67: ...4 Heat Pump Model Only...
Страница 68: ...65 DSB 182A R 182P R...
Страница 69: ...5...
Страница 70: ...66 DSB 183AH 183PH 240A R 240AH R 240P R 240PH R F240P R DSA 183A R 183...
Страница 71: ...6 3AH R 240A R 240AH R Heat Pump Model Only...
Страница 97: ...92 5 U9 KIA7042P RESET IC KIA70 42P OUTLINE INPUT GROUND OUTPUT VCC 1 3 2 OUT GND...
Страница 101: ...96 PROCEDURES PHOTOS 7 Removing the blower Loosen the screw fixed at the holder bearing Remove the blower Fig 8 Fig 7...
Страница 106: ...101 3 EXPLODED DIAGRAM Indoor Unit DSB 071AH...
Страница 108: ...103 DSB 093AH 123AH 123PH...
Страница 110: ...105 E 0 W q Q e w 2 3 4 21 23 10 11 19 15 17 16 2 18 DSB 182A R 182P R 182AH R 182PH R...
Страница 112: ...107 DSB 183AH 183PH 240A R 240AH R 240P R 240PH R F240P R DSA 183A R 183AH R 240A R 240AH R 240AH 240PH...
Страница 114: ...109 DSB 071AH 093AH 123AH 123PH 4 EXPLODED DIAGRAM Outdoor Unit...
Страница 117: ...112 DSB 182A R 182P R 183AH 183PH 182AH R 182PH R DSA 183A R 183AH R...
Страница 120: ...115 DSB 240A R 240AH R 240P R 240PH R F240P R DSA 240A R 240AH R 240AH 240PH...
Страница 123: ...118 DSB 071AH 5 CONTROL BOX ASSEMBLY...
Страница 125: ...120 DSB 093AH 123AH 123PH...
Страница 127: ...122 DSB 182A R 182P R 182AH R 182PH R...
Страница 129: ...124 DSB 183AH 183PH 240AH R 240PH R 240A R 240P R DSA 183AH R 182A R 240A R 240AH R 240AH 240PH 16...