8.8 Manual operation
Manual operation is controlled by touching buttons and divided into force cooling and forced auto
mode. It transfers between these two modes by pressing the buttons, the cycling order of the
button press is:
8.8.1 Forced
Cooling
8.8.1.1 In forced cooling mode, the remote signal is not accepted.
8.8.1.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose
fan mode is set as low, the A/C operates in the forced auto mode under the
requirements of the forced auto mode.
8.8.1.3 During the start-up and operation, all of the following protecting functions work:
3minutes start-up delay protection, overload protection, outdoor protection, evaporator
Protection against low temperature. If any of the protection functions, the comparative
protecting action is executed.
The forced cooling mode is closed by one touch on the button, meanwhile the operation
light is off, the buzzer buzzes lasts for 1 seconds, then A/C turns to be closedown
status.
8.8.2. Forced Auto
8.8.2.1 Remote control signal can be received in forced auto mode. When receiving the
signals, the forced auto mode will be canceled and the A/C changes to remote control
status and performs operation as the signals indicates.
8.8.2.2 The system performs control according to the remote control auto mode with a set
temperature of 24°C.
8.9 Timer
24 hours timer on or off.
8.10 Protecting Function
8.10.1 Compress with a delay of 3 minutes.
8.10.2 Sensor open and break protection
8.10.3 EEROM error protection.
8.10.4 Current protection function.
Remote mode
Forced auto
Forced cooling
Содержание DSB-300L
Страница 6: ...5 3 OUTLINE AND DIMENSIONS...
Страница 7: ...Heating and cooling DSB 300LH 6 4 Refrigeration cycle diagram...
Страница 8: ...7 Cooling only DSB 300L...
Страница 10: ...6 WIRING DIAGRAM DSB 300L Indoor Unit...
Страница 11: ...10 DSB 300L Outdoor Unit...
Страница 12: ...11 DSB 300LH Indoor Unit...
Страница 13: ...12 DSB 300LH Outdoor Unit...
Страница 21: ...20 9 Exploded View Parts DSB 300L 220 240V 50Hz Indoor Unit...
Страница 23: ...22 DSB 300L 220 240V 50Hz Outdoor Unit...
Страница 25: ...24 DSB 300LH 220 240V 50Hz Indoor Unit...
Страница 27: ...26 DSB 300LH 220 240V 50Hz Outdoor Unit...